2025-06-05 10:30:37 +08:00

3601 lines
205 KiB
XML

<?xml version="1.0" encoding="UTF-8" standalone="yes"?>
<SCL xmlns="http://www.iec.ch/61850/2003/SCL" xmlns:xsd="http://www.w3.org/2001/XMLSchema" xmlns:xsi="http://www.w3.org/2001/XMLSchema-instance">
<Private type="SchneiderElectric-SFT-Key">BEABE8AE744397CAE51B51E09FABD66E</Private>
<Private type="SchneiderElectric-SFT-EditTime">2022-03-09 17:59:56</Private>
<Private type="SchneiderElectric-SFT-Version">3.3.0</Private>
<Header id="F23-1 station" nameStructure="IEDName" revision="156" toolID="CET850 v2.0" version="1">
<History>
<Hitem revision="0" version="V1" what="Draft 1" when="2022-03-09" who="CET850Config"/>
</History>
</Header>
<Communication>
<SubNetwork name="NONE">
<ConnectedAP apName="P1" iedName="F2E801F">
<Private type="Siemens-Redundant-ConnectedAP">1</Private>
<Private type="Siemens-Redundant-SubnetId">1</Private>
<Address>
<P type="OSI-AP-Title">1,3,9999,23</P>
<P type="OSI-AE-Qualifier">23</P>
<P type="OSI-PSEL">00000001</P>
<P type="OSI-SSEL">0001</P>
<P type="OSI-TSEL">0001</P>
<P type="IP" xsi:type="tP_IP">172.161.7.100</P>
<P type="IP-SUBNET" xsi:type="tP_IP-SUBNET">255.255.0.0</P>
<P type="IP-GATEWAY" xsi:type="tP_IP-GATEWAY">172.161.1.1</P>
</Address>
</ConnectedAP>
</SubNetwork>
</Communication>
<IED configVersion="1.0" desc="F2E801F" manufacturer="SIEMENS" name="F2E801F" type="Siprotec-7SJ6xx">
<Private type="Siemens-PrivateNamespace">SIEMENS EXT</Private>
<Private type="Siemens-Inkrement">2</Private>
<Private type="Siemens-BRCB-StoragePercentageMemoryForBuffer">LD0\LLN0\brcbA|14</Private>
<Private type="Siemens-BRCB-StoragePercentageMemoryForBuffer">LD0\LLN0\brcbB|14</Private>
<Private type="Siemens-BRCB-StoragePercentageMemoryForBuffer">PROT\LLN0\brcbA|14</Private>
<Private type="Siemens-BRCB-StoragePercentageMemoryForBuffer">PROT\LLN0\brcbB|14</Private>
<Private type="Siemens-BRCB-StoragePercentageMemoryForBuffer">DR\LLN0\brcbA|14</Private>
<Private type="Siemens-BRCB-StoragePercentageMemoryForBuffer">CTRL\LLN0\brcbA|14</Private>
<Private type="Siemens-BRCB-StoragePercentageMemoryForBuffer">CTRL\LLN0\brcbB|14</Private>
<Private type="Siemens-NetworkFrequency">50 Hz</Private>
<Private type="Siemens-Owner">F23-1 station</Private>
<Private type="Siemens-s7ManagerName">F2E801F</Private>
<Private type="Siemens-IED-Id">6_IED_26</Private>
<Private type="Siemens-ICD-Language">zh-CN</Private>
<Private type="Siemens-ModifiedDate">03/07/2022 07:39:16</Private>
<Private type="Siemens-ModificationCounter">4</Private>
<Services>
<DynAssociation/>
<SettingGroups>
<SGEdit/>
</SettingGroups>
<GetDirectory/>
<GetDataObjectDefinition/>
<DataObjectDirectory/>
<GetDataSetValue/>
<DataSetDirectory/>
<ConfDataSet max="39" maxAttributes="75"/>
<ReadWrite/>
<ConfReportControl max="10"/>
<GetCBValues/>
<ReportSettings bufTime="Dyn" cbName="Fix" datSet="Dyn" intgPd="Dyn" optFields="Dyn" rptID="Dyn" trgOps="Dyn"/>
<GSESettings appID="Conf" cbName="Conf" datSet="Conf"/>
<GOOSE max="3"/>
<FileHandling/>
<ConfLNs fixLnInst="true" fixPrefix="true"/>
</Services>
<AccessPoint name="P1">
<Server>
<Authentication none="true"/>
<LDevice desc="公用" inst="LD0">
<Private type="Siemens-AlternativeDesc">General</Private>
<Private type="IsNodeProcessed"/>
<LN0 desc="公用" inst="" lnClass="LLN0" lnType="F2T202IN/LD0/LLN0">
<Private type="Siemens-AlternativeDesc">General</Private>
<Private type="Siemens-ControlBlockStorage">urcbA|&lt;ReportControl rptID="F2E801FLD0/LLN0$RP$urcbA01" confRev="0" buffered="false" bufTime="100" name="urcbA"&gt; &lt;Private type="Siemens-PredefinedControlBlock" /&gt; &lt;TrgOps dchg="true" qchg="true" dupd="true" period="true" /&gt; &lt;OptFields seqNum="true" timeStamp="true" dataSet="true" reasonCode="true" dataRef="false" configRef="true" /&gt; &lt;RptEnabled max="1" /&gt; &lt;/ReportControl&gt;</Private>
<Private type="Siemens-ControlBlockStorage">urcbB|&lt;ReportControl rptID="F2E801FLD0/LLN0$RP$urcbB01" confRev="0" buffered="false" bufTime="100" name="urcbB"&gt; &lt;Private type="Siemens-PredefinedControlBlock" /&gt; &lt;TrgOps dchg="true" qchg="true" dupd="true" period="true" /&gt; &lt;OptFields seqNum="true" timeStamp="true" dataSet="true" reasonCode="true" dataRef="false" configRef="true" /&gt; &lt;RptEnabled max="1" /&gt; &lt;/ReportControl&gt;</Private>
<Private type="Siemens-ControlBlockStorage">urcbC|&lt;ReportControl rptID="F2E801FLD0/LLN0$RP$urcbC01" confRev="0" buffered="false" bufTime="100" name="urcbC"&gt; &lt;Private type="Siemens-PredefinedControlBlock" /&gt; &lt;TrgOps dchg="true" qchg="true" dupd="true" period="true" /&gt; &lt;OptFields seqNum="true" timeStamp="true" dataSet="true" reasonCode="true" dataRef="false" configRef="true" /&gt; &lt;RptEnabled max="1" /&gt; &lt;/ReportControl&gt;</Private>
<Private type="Siemens-ControlBlockStorage">urcbD|&lt;ReportControl rptID="F2E801FLD0/LLN0$RP$urcbD01" confRev="0" buffered="false" bufTime="100" name="urcbD"&gt; &lt;Private type="Siemens-PredefinedControlBlock" /&gt; &lt;TrgOps dchg="true" qchg="true" dupd="true" period="true" /&gt; &lt;OptFields seqNum="true" timeStamp="true" dataSet="true" reasonCode="true" dataRef="false" configRef="true" /&gt; &lt;RptEnabled max="1" /&gt; &lt;/ReportControl&gt;</Private>
<Private type="Siemens-ControlBlockStorage">urcbE|&lt;ReportControl rptID="F2E801FLD0/LLN0$RP$urcbE01" confRev="0" buffered="false" bufTime="100" name="urcbE"&gt; &lt;Private type="Siemens-PredefinedControlBlock" /&gt; &lt;TrgOps dchg="true" qchg="true" dupd="true" period="true" /&gt; &lt;OptFields seqNum="true" timeStamp="true" dataSet="true" reasonCode="true" dataRef="false" configRef="true" /&gt; &lt;RptEnabled max="1" /&gt; &lt;/ReportControl&gt;</Private>
<Private type="Siemens-ControlBlockStorage">urcbF|&lt;ReportControl rptID="F2E801FLD0/LLN0$RP$urcbF01" confRev="0" buffered="false" bufTime="100" name="urcbF"&gt; &lt;Private type="Siemens-PredefinedControlBlock" /&gt; &lt;TrgOps dchg="true" qchg="true" dupd="true" period="true" /&gt; &lt;OptFields seqNum="true" timeStamp="true" dataSet="true" reasonCode="true" dataRef="false" configRef="true" /&gt; &lt;RptEnabled max="1" /&gt; &lt;/ReportControl&gt;</Private>
<Private type="Siemens-ControlBlockStorage">urcbG|&lt;ReportControl rptID="F2E801FLD0/LLN0$RP$urcbG01" confRev="0" buffered="false" bufTime="100" name="urcbG"&gt; &lt;Private type="Siemens-PredefinedControlBlock" /&gt; &lt;TrgOps dchg="true" qchg="true" dupd="true" period="true" /&gt; &lt;OptFields seqNum="true" timeStamp="true" dataSet="true" reasonCode="true" dataRef="false" configRef="true" /&gt; &lt;RptEnabled max="1" /&gt; &lt;/ReportControl&gt;</Private>
<Private type="Siemens-ControlBlockStorage">urcbH|&lt;ReportControl rptID="F2E801FLD0/LLN0$RP$urcbH01" confRev="0" buffered="false" bufTime="100" name="urcbH"&gt; &lt;Private type="Siemens-PredefinedControlBlock" /&gt; &lt;TrgOps dchg="true" qchg="true" dupd="true" period="true" /&gt; &lt;OptFields seqNum="true" timeStamp="true" dataSet="true" reasonCode="true" dataRef="false" configRef="true" /&gt; &lt;RptEnabled max="1" /&gt; &lt;/ReportControl&gt;</Private>
<Private type="Siemens-ControlBlockStorage">urcbI|&lt;ReportControl rptID="F2E801FLD0/LLN0$RP$urcbI01" confRev="0" buffered="false" bufTime="100" name="urcbI"&gt; &lt;Private type="Siemens-PredefinedControlBlock" /&gt; &lt;TrgOps dchg="true" qchg="true" dupd="true" period="true" /&gt; &lt;OptFields seqNum="true" timeStamp="true" dataSet="true" reasonCode="true" dataRef="false" configRef="true" /&gt; &lt;RptEnabled max="1" /&gt; &lt;/ReportControl&gt;</Private>
<Private type="Siemens-ControlBlockStorage">urcbJ|&lt;ReportControl rptID="F2E801FLD0/LLN0$RP$urcbJ01" confRev="0" buffered="false" bufTime="100" name="urcbJ"&gt; &lt;Private type="Siemens-PredefinedControlBlock" /&gt; &lt;TrgOps dchg="true" qchg="true" dupd="true" period="true" /&gt; &lt;OptFields seqNum="true" timeStamp="true" dataSet="true" reasonCode="true" dataRef="false" configRef="true" /&gt; &lt;RptEnabled max="1" /&gt; &lt;/ReportControl&gt;</Private>
<DataSet name="dsAlarm">
<FCDA doName="GrAlm" fc="ST" ldInst="LD0" lnClass="CALH" lnInst="1" prefix=""/>
<FCDA doName="GrWrn" fc="ST" ldInst="LD0" lnClass="CALH" lnInst="1" prefix=""/>
<FCDA doName="ErrBoard1" fc="ST" ldInst="LD0" lnClass="CALH" lnInst="1" prefix=""/>
<FCDA doName="ErrBoard2" fc="ST" ldInst="LD0" lnClass="CALH" lnInst="1" prefix=""/>
<FCDA doName="ErrBoard3" fc="ST" ldInst="LD0" lnClass="CALH" lnInst="1" prefix=""/>
<FCDA doName="ErrBoard4" fc="ST" ldInst="LD0" lnClass="CALH" lnInst="1" prefix=""/>
<FCDA doName="ErrBoard5" fc="ST" ldInst="LD0" lnClass="CALH" lnInst="1" prefix=""/>
<FCDA doName="ErrBoardMCPU" fc="ST" ldInst="LD0" lnClass="CALH" lnInst="1" prefix=""/>
</DataSet>
<DataSet name="dsCommState">
<FCDA doName="SPCSO1" fc="ST" ldInst="LD0" lnClass="GGIO" lnInst="1" prefix="Com"/>
<FCDA doName="SPCSO2" fc="ST" ldInst="LD0" lnClass="GGIO" lnInst="1" prefix="Com"/>
<FCDA doName="SPCSO3" fc="ST" ldInst="LD0" lnClass="GGIO" lnInst="1" prefix="Com"/>
</DataSet>
<ReportControl bufTime="100" buffered="true" confRev="1" datSet="dsAlarm" name="brcbA" rptID="LD0/LLN0$BR$brcbA">
<TrgOps dchg="true" dupd="true" period="true" qchg="true"/>
<OptFields configRef="true" dataRef="false" dataSet="true" entryID="true" reasonCode="true" seqNum="true" timeStamp="true"/>
<RptEnabled max="8"/>
</ReportControl>
<ReportControl bufTime="100" buffered="true" confRev="1" datSet="dsCommState" name="brcbB" rptID="LD0/LLN0$BR$brcbB">
<TrgOps dchg="true" dupd="true" period="true" qchg="true"/>
<OptFields configRef="true" dataRef="false" dataSet="true" entryID="true" reasonCode="true" seqNum="true" timeStamp="true"/>
<RptEnabled max="8"/>
</ReportControl>
<DOI desc="模式" name="Mod">
<Private type="Siemens-AlternativeDesc">Mode</Private>
<DAI name="ctlModel">
<Val>status-only</Val>
</DAI>
</DOI>
<DOI desc="性能" name="Beh">
<Private type="Siemens-AlternativeDesc">Behaviour</Private>
</DOI>
<DOI desc="健康状况" name="Health">
<Private type="Siemens-AlternativeDesc">State</Private>
</DOI>
<DOI desc="铭牌" name="NamPlt">
<Private type="Siemens-AlternativeDesc">Info</Private>
<DAI name="configRev">
<Val>160304190901000</Val>
</DAI>
<DAI name="ldNs">
<Val>IEC 61850-7-4:2003</Val>
</DAI>
</DOI>
<DOI desc="本地操作" name="Loc">
<Private type="Siemens-AlternativeDesc">Control Auth</Private>
</DOI>
<DOI desc="运行小时数" name="OpTmh">
<Private type="Siemens-AlternativeDesc">Operating hours</Private>
</DOI>
</LN0>
<LN desc="装置" inst="1" lnClass="CALH" lnType="F2T202IN/LD0/CALH1">
<Private type="Siemens-AlternativeDesc">Fault</Private>
<Private type="IsNodeProcessed"/>
<Private type="Siemens-ControlBlockStorage">urcbA|&lt;ReportControl rptID="F2E801FLD0/CALH1$RP$urcbA01" confRev="0" buffered="false" bufTime="100" name="urcbA"&gt; &lt;Private type="Siemens-PredefinedControlBlock" /&gt; &lt;TrgOps dchg="true" qchg="true" dupd="true" period="true" /&gt; &lt;OptFields seqNum="true" timeStamp="true" dataSet="true" reasonCode="true" dataRef="false" configRef="true" /&gt; &lt;RptEnabled max="1" /&gt; &lt;/ReportControl&gt;</Private>
<Private type="Siemens-ControlBlockStorage">urcbB|&lt;ReportControl rptID="F2E801FLD0/CALH1$RP$urcbB01" confRev="0" buffered="false" bufTime="100" name="urcbB"&gt; &lt;Private type="Siemens-PredefinedControlBlock" /&gt; &lt;TrgOps dchg="true" qchg="true" dupd="true" period="true" /&gt; &lt;OptFields seqNum="true" timeStamp="true" dataSet="true" reasonCode="true" dataRef="false" configRef="true" /&gt; &lt;RptEnabled max="1" /&gt; &lt;/ReportControl&gt;</Private>
<DOI desc="模式" name="Mod">
<Private type="Siemens-AlternativeDesc">Mode</Private>
<DAI name="ctlModel">
<Val>status-only</Val>
</DAI>
</DOI>
<DOI desc="性能" name="Beh">
<Private type="Siemens-AlternativeDesc">Behaviour</Private>
</DOI>
<DOI desc="健康状况" name="Health">
<Private type="Siemens-AlternativeDesc">State</Private>
</DOI>
<DOI desc="铭牌" name="NamPlt">
<Private type="Siemens-AlternativeDesc">Info</Private>
<DAI name="configRev">
<Val>160304190901000</Val>
</DAI>
</DOI>
<DOI desc="故障组告警" name="GrAlm">
<Private type="Siemens-AlternativeDesc">Group alarms</Private>
</DOI>
<DOI desc="事件组告警" name="GrWrn">
<Private type="Siemens-AlternativeDesc">Group Warning</Private>
</DOI>
<DOI desc="交流板故障" name="ErrBoard1">
<Private type="Siemens-AlternativeDesc">PT/CT Board Err</Private>
<DAI name="d">
<Val>ErrBoard1 stands for Error on board 1</Val>
</DAI>
<DAI name="dataNs">
<Val>SIEMENS EXT</Val>
</DAI>
</DOI>
<DOI desc="电源板故障" name="ErrBoard2">
<Private type="Siemens-AlternativeDesc">PS board Err</Private>
<DAI name="d">
<Val>ErrBoard2 stands for Error on board 2</Val>
</DAI>
<DAI name="dataNs">
<Val>SIEMENS EXT</Val>
</DAI>
</DOI>
<DOI desc="开入/开出板故障" name="ErrBoard3">
<Private type="Siemens-AlternativeDesc">BI/O board Err</Private>
<DAI name="d">
<Val>ErrBoard3 stands for Error on board 3</Val>
</DAI>
<DAI name="dataNs">
<Val>SIEMENS EXT</Val>
</DAI>
</DOI>
<DOI desc="通讯板故障" name="ErrBoard4">
<Private type="Siemens-AlternativeDesc">Com Board Er</Private>
<DAI name="d">
<Val>ErrBoard4 stands for Error on board 4</Val>
</DAI>
<DAI name="dataNs">
<Val>SIEMENS EXT</Val>
</DAI>
</DOI>
<DOI desc="扩展板故障" name="ErrBoard5">
<Private type="Siemens-AlternativeDesc">Extend Board Er</Private>
<DAI name="d">
<Val>ErrBoard5 stands for Error on board 5</Val>
</DAI>
<DAI name="dataNs">
<Val>SIEMENS EXT</Val>
</DAI>
</DOI>
<DOI desc="CPU板故障" name="ErrBoardMCPU">
<Private type="Siemens-AlternativeDesc">CPU Board Er</Private>
<DAI name="d">
<Val>ErrBoardMCPU stands for Error on board MCPU</Val>
</DAI>
<DAI name="dataNs">
<Val>SIEMENS EXT</Val>
</DAI>
</DOI>
</LN>
<LN desc="设备" inst="1" lnClass="LPHD" lnType="F2T202IN/LD0/LPHD1" prefix="">
<Private type="Siemens-AlternativeDesc">Device</Private>
<Private type="IsNodeProcessed"/>
<Private type="Siemens-ControlBlockStorage">urcbA|&lt;ReportControl rptID="F2E801FLD0/LPHD1$RP$urcbA01" confRev="0" buffered="false" bufTime="100" name="urcbA"&gt; &lt;Private type="Siemens-PredefinedControlBlock" /&gt; &lt;TrgOps dchg="true" qchg="true" dupd="true" period="true" /&gt; &lt;OptFields seqNum="true" timeStamp="true" dataSet="true" reasonCode="true" dataRef="false" configRef="true" /&gt; &lt;RptEnabled max="1" /&gt; &lt;/ReportControl&gt;</Private>
<Private type="Siemens-ControlBlockStorage">urcbB|&lt;ReportControl rptID="F2E801FLD0/LPHD1$RP$urcbB01" confRev="0" buffered="false" bufTime="100" name="urcbB"&gt; &lt;Private type="Siemens-PredefinedControlBlock" /&gt; &lt;TrgOps dchg="true" qchg="true" dupd="true" period="true" /&gt; &lt;OptFields seqNum="true" timeStamp="true" dataSet="true" reasonCode="true" dataRef="false" configRef="true" /&gt; &lt;RptEnabled max="1" /&gt; &lt;/ReportControl&gt;</Private>
<DOI desc="物理装置铭牌" name="PhyNam">
<Private type="Siemens-AlternativeDesc">Info</Private>
</DOI>
<DOI desc="物理装置健康状况" name="PhyHealth">
<Private type="Siemens-AlternativeDesc">State</Private>
</DOI>
<DOI desc="代理" name="Proxy">
<Private type="Siemens-AlternativeDesc">Proxy</Private>
</DOI>
<DOI desc="装置上电" name="DevStr">
<!-- SIEMENS-spezifisch -->
<Private type="Siemens-AlternativeDesc">Startup</Private>
<DAI name="d">
<Val>DevStr stands for either InitialStart or Resume</Val>
</DAI>
<DAI name="dataNs">
<Val>SIEMENS EXT</Val>
</DAI>
</DOI>
<DOI desc="控制计数" name="CtlNum">
<!-- SIEMENS-spezifisch -->
<Private type="Siemens-AlternativeDesc">Test oper Nr</Private>
<DAI name="d">
<Val>CtlNum stands for number of Test Operations</Val>
</DAI>
<DAI name="dataNs">
<Val>SIEMENS EXT</Val>
</DAI>
</DOI>
</LN>
<LN desc="通信" inst="1" lnClass="GGIO" lnType="F2T202IN/LD0/ComGGIO1" prefix="Com">
<Private type="Siemens-AlternativeDesc">ComGGIO</Private>
<Private type="IsNodeProcessed"/>
<Private type="Siemens-ControlBlockStorage">urcbA|&lt;ReportControl rptID="F2E801FLD0/ComGGIO1$RP$urcbA01" confRev="0" buffered="false" bufTime="100" name="urcbA"&gt; &lt;Private type="Siemens-PredefinedControlBlock" /&gt; &lt;TrgOps dchg="true" qchg="true" dupd="true" period="true" /&gt; &lt;OptFields seqNum="true" timeStamp="true" dataSet="true" reasonCode="true" dataRef="false" configRef="true" /&gt; &lt;RptEnabled max="1" /&gt; &lt;/ReportControl&gt;</Private>
<Private type="Siemens-ControlBlockStorage">urcbB|&lt;ReportControl rptID="F2E801FLD0/ComGGIO1$RP$urcbB01" confRev="0" buffered="false" bufTime="100" name="urcbB"&gt; &lt;Private type="Siemens-PredefinedControlBlock" /&gt; &lt;TrgOps dchg="true" qchg="true" dupd="true" period="true" /&gt; &lt;OptFields seqNum="true" timeStamp="true" dataSet="true" reasonCode="true" dataRef="false" configRef="true" /&gt; &lt;RptEnabled max="1" /&gt; &lt;/ReportControl&gt;</Private>
<DOI desc="模式" name="Mod">
<Private type="Siemens-AlternativeDesc">Mode</Private>
<DAI name="ctlModel">
<Val>status-only</Val>
</DAI>
</DOI>
<DOI desc="性能" name="Beh">
<Private type="Siemens-AlternativeDesc">Behaviour</Private>
</DOI>
<DOI desc="健康状况" name="Health">
<Private type="Siemens-AlternativeDesc">State</Private>
</DOI>
<DOI desc="铭牌" name="NamPlt">
<Private type="Siemens-AlternativeDesc">Info</Private>
<DAI name="configRev">
<Val>160304190901000</Val>
</DAI>
</DOI>
<DOI desc="B口失去链路连接" name="SPCSO1">
<Private type="Siemens-AlternativeDesc">Ethernet port B lost link</Private>
<DAI name="ctlModel">
<Val>status-only</Val>
</DAI>
</DOI>
<DOI desc="C口失去链路连接" name="SPCSO2">
<Private type="Siemens-AlternativeDesc">Ethernet port C lost link</Private>
<DAI name="ctlModel">
<Val>status-only</Val>
</DAI>
</DOI>
<DOI desc="D口失去链路连接" name="SPCSO3">
<Private type="Siemens-AlternativeDesc">Ethernet port D lost link</Private>
<DAI name="ctlModel">
<Val>status-only</Val>
</DAI>
</DOI>
</LN>
</LDevice>
<LDevice desc="保护" inst="PROT">
<Private type="Siemens-AlternativeDesc">Protection</Private>
<Private type="IsNodeProcessed"/>
<LN0 desc="公用" inst="" lnClass="LLN0" lnType="F2T202IN/PROT/LLN0">
<Private type="Siemens-AlternativeDesc">General</Private>
<Private type="Siemens-ControlBlockStorage">urcbA|&lt;ReportControl rptID="F2E801FPROT/LLN0$RP$urcbA01" confRev="0" buffered="false" bufTime="100" name="urcbA"&gt; &lt;Private type="Siemens-PredefinedControlBlock" /&gt; &lt;TrgOps dchg="true" qchg="true" dupd="true" period="true" /&gt; &lt;OptFields seqNum="true" timeStamp="true" dataSet="true" reasonCode="true" dataRef="false" configRef="true" /&gt; &lt;RptEnabled max="1" /&gt; &lt;/ReportControl&gt;</Private>
<Private type="Siemens-ControlBlockStorage">urcbB|&lt;ReportControl rptID="F2E801FPROT/LLN0$RP$urcbB01" confRev="0" buffered="false" bufTime="100" name="urcbB"&gt; &lt;Private type="Siemens-PredefinedControlBlock" /&gt; &lt;TrgOps dchg="true" qchg="true" dupd="true" period="true" /&gt; &lt;OptFields seqNum="true" timeStamp="true" dataSet="true" reasonCode="true" dataRef="false" configRef="true" /&gt; &lt;RptEnabled max="1" /&gt; &lt;/ReportControl&gt;</Private>
<Private type="Siemens-ControlBlockStorage">urcbC|&lt;ReportControl rptID="F2E801FPROT/LLN0$RP$urcbC01" confRev="0" buffered="false" bufTime="100" name="urcbC"&gt; &lt;Private type="Siemens-PredefinedControlBlock" /&gt; &lt;TrgOps dchg="true" qchg="true" dupd="true" period="true" /&gt; &lt;OptFields seqNum="true" timeStamp="true" dataSet="true" reasonCode="true" dataRef="false" configRef="true" /&gt; &lt;RptEnabled max="1" /&gt; &lt;/ReportControl&gt;</Private>
<Private type="Siemens-ControlBlockStorage">urcbD|&lt;ReportControl rptID="F2E801FPROT/LLN0$RP$urcbD01" confRev="0" buffered="false" bufTime="100" name="urcbD"&gt; &lt;Private type="Siemens-PredefinedControlBlock" /&gt; &lt;TrgOps dchg="true" qchg="true" dupd="true" period="true" /&gt; &lt;OptFields seqNum="true" timeStamp="true" dataSet="true" reasonCode="true" dataRef="false" configRef="true" /&gt; &lt;RptEnabled max="1" /&gt; &lt;/ReportControl&gt;</Private>
<Private type="Siemens-ControlBlockStorage">urcbE|&lt;ReportControl rptID="F2E801FPROT/LLN0$RP$urcbE01" confRev="0" buffered="false" bufTime="100" name="urcbE"&gt; &lt;Private type="Siemens-PredefinedControlBlock" /&gt; &lt;TrgOps dchg="true" qchg="true" dupd="true" period="true" /&gt; &lt;OptFields seqNum="true" timeStamp="true" dataSet="true" reasonCode="true" dataRef="false" configRef="true" /&gt; &lt;RptEnabled max="1" /&gt; &lt;/ReportControl&gt;</Private>
<Private type="Siemens-ControlBlockStorage">urcbF|&lt;ReportControl rptID="F2E801FPROT/LLN0$RP$urcbF01" confRev="0" buffered="false" bufTime="100" name="urcbF"&gt; &lt;Private type="Siemens-PredefinedControlBlock" /&gt; &lt;TrgOps dchg="true" qchg="true" dupd="true" period="true" /&gt; &lt;OptFields seqNum="true" timeStamp="true" dataSet="true" reasonCode="true" dataRef="false" configRef="true" /&gt; &lt;RptEnabled max="1" /&gt; &lt;/ReportControl&gt;</Private>
<Private type="Siemens-ControlBlockStorage">urcbG|&lt;ReportControl rptID="F2E801FPROT/LLN0$RP$urcbG01" confRev="0" buffered="false" bufTime="100" name="urcbG"&gt; &lt;Private type="Siemens-PredefinedControlBlock" /&gt; &lt;TrgOps dchg="true" qchg="true" dupd="true" period="true" /&gt; &lt;OptFields seqNum="true" timeStamp="true" dataSet="true" reasonCode="true" dataRef="false" configRef="true" /&gt; &lt;RptEnabled max="1" /&gt; &lt;/ReportControl&gt;</Private>
<Private type="Siemens-ControlBlockStorage">urcbH|&lt;ReportControl rptID="F2E801FPROT/LLN0$RP$urcbH01" confRev="0" buffered="false" bufTime="100" name="urcbH"&gt; &lt;Private type="Siemens-PredefinedControlBlock" /&gt; &lt;TrgOps dchg="true" qchg="true" dupd="true" period="true" /&gt; &lt;OptFields seqNum="true" timeStamp="true" dataSet="true" reasonCode="true" dataRef="false" configRef="true" /&gt; &lt;RptEnabled max="1" /&gt; &lt;/ReportControl&gt;</Private>
<Private type="Siemens-ControlBlockStorage">urcbI|&lt;ReportControl rptID="F2E801FPROT/LLN0$RP$urcbI01" confRev="0" buffered="false" bufTime="100" name="urcbI"&gt; &lt;Private type="Siemens-PredefinedControlBlock" /&gt; &lt;TrgOps dchg="true" qchg="true" dupd="true" period="true" /&gt; &lt;OptFields seqNum="true" timeStamp="true" dataSet="true" reasonCode="true" dataRef="false" configRef="true" /&gt; &lt;RptEnabled max="1" /&gt; &lt;/ReportControl&gt;</Private>
<Private type="Siemens-ControlBlockStorage">urcbJ|&lt;ReportControl rptID="F2E801FPROT/LLN0$RP$urcbJ01" confRev="0" buffered="false" bufTime="100" name="urcbJ"&gt; &lt;Private type="Siemens-PredefinedControlBlock" /&gt; &lt;TrgOps dchg="true" qchg="true" dupd="true" period="true" /&gt; &lt;OptFields seqNum="true" timeStamp="true" dataSet="true" reasonCode="true" dataRef="false" configRef="true" /&gt; &lt;RptEnabled max="1" /&gt; &lt;/ReportControl&gt;</Private>
<DataSet name="dsTripInfo">
<!--FCDA ldInst="PROT" prefix="" lnClass="PDIF" lnInst="1" doName="DifAClc.phsA" fc="MX"/>
<FCDA ldInst="PROT" prefix="" lnClass="PDIF" lnInst="1" doName="DifAClc.phsB" fc="MX"/>
<FCDA ldInst="PROT" prefix="" lnClass="PDIF" lnInst="1" doName="DifAClc.phsC" fc="MX"/>
<FCDA ldInst="PROT" prefix="" lnClass="PDIF" lnInst="1" doName="RstA.phsA" fc="MX"/>
<FCDA ldInst="PROT" prefix="" lnClass="PDIF" lnInst="1" doName="RstA.phsB" fc="MX"/>
<FCDA ldInst="PROT" prefix="" lnClass="PDIF" lnInst="1" doName=".phsC" fc="MX"/-->
<!--CTPT-SupV/-->
<!--T/CCirSupV/-->
<!--Ain/-->
<!--Ain/-->
<FCDA doName="Op" fc="ST" ldInst="PROT" lnClass="PTOC" lnInst="1" prefix="PhI"/>
<FCDA doName="Op" fc="ST" ldInst="PROT" lnClass="PTOC" lnInst="1" prefix="PhII"/>
<FCDA doName="Op" fc="ST" ldInst="PROT" lnClass="PTOC" lnInst="1" prefix="PhIII"/>
<FCDA doName="Op" fc="ST" ldInst="PROT" lnClass="PTOC" lnInst="1" prefix="PhR"/>
<FCDA doName="Op" fc="ST" ldInst="PROT" lnClass="PTOC" lnInst="1" prefix="ZerI"/>
<FCDA doName="Op" fc="ST" ldInst="PROT" lnClass="PTOC" lnInst="1" prefix="ZerII"/>
<FCDA doName="Op" fc="ST" ldInst="PROT" lnClass="PTOC" lnInst="1" prefix="ZerIII"/>
<FCDA doName="Op" fc="ST" ldInst="PROT" lnClass="PTOC" lnInst="1" prefix="ZerR"/>
<FCDA doName="Tr" fc="ST" ldInst="PROT" lnClass="PTRC" lnInst="1" prefix=""/>
<FCDA doName="SPCSO4" fc="ST" ldInst="PROT" lnClass="GGIO" lnInst="1" prefix="NonEle"/>
<FCDA doName="SPCSO5" fc="ST" ldInst="PROT" lnClass="GGIO" lnInst="1" prefix="NonEle"/>
<FCDA doName="SPCSO6" fc="ST" ldInst="PROT" lnClass="GGIO" lnInst="1" prefix="NonEle"/>
<FCDA doName="SPCSO7" fc="ST" ldInst="PROT" lnClass="GGIO" lnInst="1" prefix="NonEle"/>
<FCDA doName="SPCSO8" fc="ST" ldInst="PROT" lnClass="GGIO" lnInst="1" prefix="NonEle"/>
</DataSet>
<DataSet name="dsWarning">
<FCDA doName="Str" fc="ST" ldInst="PROT" lnClass="PTOC" lnInst="1" prefix="PhI"/>
<FCDA doName="Str" fc="ST" ldInst="PROT" lnClass="PTOC" lnInst="1" prefix="PhII"/>
<FCDA doName="Str" fc="ST" ldInst="PROT" lnClass="PTOC" lnInst="1" prefix="PhIII"/>
<FCDA doName="Str" fc="ST" ldInst="PROT" lnClass="PTOC" lnInst="1" prefix="PhR"/>
<FCDA doName="Str" fc="ST" ldInst="PROT" lnClass="PTOC" lnInst="1" prefix="ZerI"/>
<FCDA doName="Str" fc="ST" ldInst="PROT" lnClass="PTOC" lnInst="1" prefix="ZerII"/>
<FCDA doName="Str" fc="ST" ldInst="PROT" lnClass="PTOC" lnInst="1" prefix="ZerIII"/>
<FCDA doName="Str" fc="ST" ldInst="PROT" lnClass="PTOC" lnInst="1" prefix="ZerR"/>
<FCDA doName="Str" fc="ST" ldInst="PROT" lnClass="PTRC" lnInst="1" prefix=""/>
<FCDA doName="SPCSO1" fc="ST" ldInst="PROT" lnClass="GGIO" lnInst="1" prefix="SupV"/>
<FCDA doName="SPCSO2" fc="ST" ldInst="PROT" lnClass="GGIO" lnInst="1" prefix="SupV"/>
<FCDA doName="SPCSO3" fc="ST" ldInst="PROT" lnClass="GGIO" lnInst="1" prefix="SupV"/>
<FCDA doName="SPCSO4" fc="ST" ldInst="PROT" lnClass="GGIO" lnInst="1" prefix="SupV"/>
<FCDA doName="SPCSO6" fc="ST" ldInst="PROT" lnClass="GGIO" lnInst="1" prefix="SupV"/>
</DataSet>
<DataSet name="dsSetting01">
<FCDA doName="Mode" fc="SG" ldInst="PROT" lnClass="PTOC" lnInst="1" prefix="ZerI"/>
<FCDA doName="BlkDir" fc="SG" ldInst="PROT" lnClass="PTOC" lnInst="1" prefix="ZerI"/>
<FCDA doName="DirMod" fc="SG" ldInst="PROT" lnClass="PTOC" lnInst="1" prefix="ZerI"/>
<FCDA doName="StrVal" fc="SG" ldInst="PROT" lnClass="PTOC" lnInst="1" prefix="ZerI"/>
<FCDA doName="OpDlTmms" fc="SG" ldInst="PROT" lnClass="PTOC" lnInst="1" prefix="ZerI"/>
<FCDA doName="Mode" fc="SG" ldInst="PROT" lnClass="PTOC" lnInst="1" prefix="ZerII"/>
<FCDA doName="DirMod" fc="SG" ldInst="PROT" lnClass="PTOC" lnInst="1" prefix="ZerII"/>
<FCDA doName="StrVal" fc="SG" ldInst="PROT" lnClass="PTOC" lnInst="1" prefix="ZerII"/>
<FCDA doName="OpDlTmms" fc="SG" ldInst="PROT" lnClass="PTOC" lnInst="1" prefix="ZerII"/>
<FCDA doName="Mode" fc="SG" ldInst="PROT" lnClass="PTOC" lnInst="1" prefix="ZerIII"/>
<FCDA doName="DirMod" fc="SG" ldInst="PROT" lnClass="PTOC" lnInst="1" prefix="ZerIII"/>
<FCDA doName="StrVal" fc="SG" ldInst="PROT" lnClass="PTOC" lnInst="1" prefix="ZerIII"/>
<FCDA doName="OpDlTmms" fc="SG" ldInst="PROT" lnClass="PTOC" lnInst="1" prefix="ZerIII"/>
<FCDA doName="Mode" fc="SG" ldInst="PROT" lnClass="PTOC" lnInst="1" prefix="ZerR"/>
<FCDA doName="DirMod" fc="SG" ldInst="PROT" lnClass="PTOC" lnInst="1" prefix="ZerR"/>
<FCDA doName="TmACrv" fc="SG" ldInst="PROT" lnClass="PTOC" lnInst="1" prefix="ZerR"/>
<FCDA doName="StrVal" fc="SG" ldInst="PROT" lnClass="PTOC" lnInst="1" prefix="ZerR"/>
<FCDA doName="OpDlTmms" fc="SG" ldInst="PROT" lnClass="PTOC" lnInst="1" prefix="ZerR"/>
<FCDA doName="Mode" fc="SG" ldInst="PROT" lnClass="PTOC" lnInst="1" prefix="PhI"/>
<FCDA doName="BlkDir" fc="SG" ldInst="PROT" lnClass="PTOC" lnInst="1" prefix="PhI"/>
<FCDA doName="PTBlkV" fc="SG" ldInst="PROT" lnClass="PTOC" lnInst="1" prefix="PhI"/>
<FCDA doName="BlkVPhPh" fc="SG" ldInst="PROT" lnClass="PTOC" lnInst="1" prefix="PhI"/>
<FCDA doName="BlkNgv" fc="SG" ldInst="PROT" lnClass="PTOC" lnInst="1" prefix="PhI"/>
<FCDA doName="VCtrl" fc="SG" ldInst="PROT" lnClass="PTOC" lnInst="1" prefix="PhI"/>
<FCDA doName="DirMod" fc="SG" ldInst="PROT" lnClass="PTOC" lnInst="1" prefix="PhI"/>
<FCDA doName="StrVal" fc="SG" ldInst="PROT" lnClass="PTOC" lnInst="1" prefix="PhI"/>
<FCDA doName="OpDlTmms" fc="SG" ldInst="PROT" lnClass="PTOC" lnInst="1" prefix="PhI"/>
<FCDA doName="Mode" fc="SG" ldInst="PROT" lnClass="PTOC" lnInst="1" prefix="PhII"/>
<FCDA doName="VCtrl" fc="SG" ldInst="PROT" lnClass="PTOC" lnInst="1" prefix="PhII"/>
<FCDA doName="DirMod" fc="SG" ldInst="PROT" lnClass="PTOC" lnInst="1" prefix="PhII"/>
<FCDA doName="StrVal" fc="SG" ldInst="PROT" lnClass="PTOC" lnInst="1" prefix="PhII"/>
<FCDA doName="OpDlTmms" fc="SG" ldInst="PROT" lnClass="PTOC" lnInst="1" prefix="PhII"/>
<FCDA doName="Mode" fc="SG" ldInst="PROT" lnClass="PTOC" lnInst="1" prefix="PhIII"/>
<FCDA doName="VCtrl" fc="SG" ldInst="PROT" lnClass="PTOC" lnInst="1" prefix="PhIII"/>
<FCDA doName="DirMod" fc="SG" ldInst="PROT" lnClass="PTOC" lnInst="1" prefix="PhIII"/>
<FCDA doName="StrVal" fc="SG" ldInst="PROT" lnClass="PTOC" lnInst="1" prefix="PhIII"/>
<FCDA doName="OpDlTmms" fc="SG" ldInst="PROT" lnClass="PTOC" lnInst="1" prefix="PhIII"/>
<FCDA doName="Mode" fc="SG" ldInst="PROT" lnClass="PTOC" lnInst="1" prefix="PhR"/>
<FCDA doName="DirMod" fc="SG" ldInst="PROT" lnClass="PTOC" lnInst="1" prefix="PhR"/>
<FCDA doName="TmACrv" fc="SG" ldInst="PROT" lnClass="PTOC" lnInst="1" prefix="PhR"/>
<FCDA doName="StrVal" fc="SG" ldInst="PROT" lnClass="PTOC" lnInst="1" prefix="PhR"/>
<FCDA doName="OpDlTmms" fc="SG" ldInst="PROT" lnClass="PTOC" lnInst="1" prefix="PhR"/>
</DataSet>
<ReportControl bufTime="100" buffered="true" confRev="1" datSet="dsTripInfo" name="brcbA" rptID="PROT/LLN0$BR$brcbA">
<TrgOps dchg="true" dupd="true" period="true" qchg="true"/>
<OptFields configRef="true" dataRef="false" dataSet="true" entryID="true" reasonCode="true" seqNum="true" timeStamp="true"/>
<RptEnabled max="8"/>
</ReportControl>
<ReportControl bufTime="100" buffered="true" confRev="1" datSet="dsWarning" name="brcbB" rptID="PROT/LLN0$BR$brcbB">
<TrgOps dchg="true" dupd="true" period="true" qchg="true"/>
<OptFields configRef="true" dataRef="false" dataSet="true" entryID="true" reasonCode="true" seqNum="true" timeStamp="true"/>
<RptEnabled max="8"/>
</ReportControl>
<DOI desc="模式" name="Mod">
<Private type="Siemens-AlternativeDesc">Mode</Private>
<DAI name="ctlModel">
<Val>status-only</Val>
</DAI>
</DOI>
<DOI desc="性能" name="Beh">
<Private type="Siemens-AlternativeDesc">Behaviour</Private>
</DOI>
<DOI desc="健康状况" name="Health">
<Private type="Siemens-AlternativeDesc">State</Private>
</DOI>
<DOI desc="铭牌" name="NamPlt">
<!-- Die DAI vendor, swRev, d, configRev und ldNs beziehen sich auf das EN100-Modul. Bis auf ldNs haben sie keinen InitValue! Sie werden mit Dummy vorbelegt. Gefuellt werden sie durch die EN100-Software zur Laufzeit. -->
<Private type="Siemens-AlternativeDesc">Info</Private>
<DAI name="configRev">
<Val>210404153620012</Val>
</DAI>
<DAI name="ldNs">
<Val>IEC 61850-7-4:2003</Val>
</DAI>
</DOI>
<DOI desc="运行小时数" name="OpTmh">
<Private type="Siemens-AlternativeDesc">Operating hours</Private>
</DOI>
<DOI desc="过流保护软压板" name="PhOCEna">
<Private type="Siemens-AlternativeDesc">67 Softlink</Private>
<DAI name="ctlModel">
<Val>direct-with-normal-security</Val>
</DAI>
<DAI name="dataNs">
<Val>SIEMENS EXT</Val>
</DAI>
</DOI>
<DOI desc="零序过流保护软压板" name="ZerOCEna">
<Private type="Siemens-AlternativeDesc">67N Softlink</Private>
<DAI name="ctlModel">
<Val>direct-with-normal-security</Val>
</DAI>
<DAI name="dataNs">
<Val>SIEMENS EXT</Val>
</DAI>
</DOI>
<SettingControl numOfSGs="1"/>
</LN0>
<LN desc="设备" inst="1" lnClass="LPHD" lnType="F2T202IN/PROT/LPHD1" prefix="">
<Private type="Siemens-AlternativeDesc">Device</Private>
<Private type="IsNodeProcessed"/>
<Private type="Siemens-ControlBlockStorage">urcbA|&lt;ReportControl rptID="F2E801FPROT/LPHD1$RP$urcbA01" confRev="0" buffered="false" bufTime="100" name="urcbA"&gt; &lt;Private type="Siemens-PredefinedControlBlock" /&gt; &lt;TrgOps dchg="true" qchg="true" dupd="true" period="true" /&gt; &lt;OptFields seqNum="true" timeStamp="true" dataSet="true" reasonCode="true" dataRef="false" configRef="true" /&gt; &lt;RptEnabled max="1" /&gt; &lt;/ReportControl&gt;</Private>
<Private type="Siemens-ControlBlockStorage">urcbB|&lt;ReportControl rptID="F2E801FPROT/LPHD1$RP$urcbB01" confRev="0" buffered="false" bufTime="100" name="urcbB"&gt; &lt;Private type="Siemens-PredefinedControlBlock" /&gt; &lt;TrgOps dchg="true" qchg="true" dupd="true" period="true" /&gt; &lt;OptFields seqNum="true" timeStamp="true" dataSet="true" reasonCode="true" dataRef="false" configRef="true" /&gt; &lt;RptEnabled max="1" /&gt; &lt;/ReportControl&gt;</Private>
<DOI desc="物理装置铭牌" name="PhyNam">
<Private type="Siemens-AlternativeDesc">Info</Private>
</DOI>
<DOI desc="物理装置健康状况" name="PhyHealth">
<Private type="Siemens-AlternativeDesc">State</Private>
</DOI>
<DOI desc="代理" name="Proxy">
<Private type="Siemens-AlternativeDesc">Proxy</Private>
</DOI>
</LN>
<LN desc="零序过流I段" inst="1" lnClass="PTOC" lnType="F2T202IN/PROT/ZerIPTOC1" prefix="ZerI">
<Private type="Siemens-AlternativeDesc">Dir DMT IE&gt;</Private>
<Private type="IsNodeProcessed"/>
<Private type="Siemens-ControlBlockStorage">urcbA|&lt;ReportControl rptID="F2E801FPROT/ZerIPTOC1$RP$urcbA01" confRev="0" buffered="false" bufTime="100" name="urcbA"&gt; &lt;Private type="Siemens-PredefinedControlBlock" /&gt; &lt;TrgOps dchg="true" qchg="true" dupd="true" period="true" /&gt; &lt;OptFields seqNum="true" timeStamp="true" dataSet="true" reasonCode="true" dataRef="false" configRef="true" /&gt; &lt;RptEnabled max="1" /&gt; &lt;/ReportControl&gt;</Private>
<Private type="Siemens-ControlBlockStorage">urcbB|&lt;ReportControl rptID="F2E801FPROT/ZerIPTOC1$RP$urcbB01" confRev="0" buffered="false" bufTime="100" name="urcbB"&gt; &lt;Private type="Siemens-PredefinedControlBlock" /&gt; &lt;TrgOps dchg="true" qchg="true" dupd="true" period="true" /&gt; &lt;OptFields seqNum="true" timeStamp="true" dataSet="true" reasonCode="true" dataRef="false" configRef="true" /&gt; &lt;RptEnabled max="1" /&gt; &lt;/ReportControl&gt;</Private>
<DOI desc="模式" name="Mod">
<Private type="Siemens-AlternativeDesc">Mode</Private>
<DAI name="ctlModel">
<Val>status-only</Val>
</DAI>
</DOI>
<DOI desc="性能" name="Beh">
<Private type="Siemens-AlternativeDesc">Behaviour</Private>
</DOI>
<DOI desc="健康状况" name="Health">
<Private type="Siemens-AlternativeDesc">State</Private>
</DOI>
<DOI desc="铭牌" name="NamPlt">
<Private type="Siemens-AlternativeDesc">Info</Private>
<DAI name="configRev">
<Val>160304190901000</Val>
</DAI>
</DOI>
<DOI desc="启动" name="Str">
<Private type="Siemens-AlternativeDesc">Pickup</Private>
</DOI>
<DOI desc="动作" name="Op">
<Private type="Siemens-AlternativeDesc">TRIP</Private>
</DOI>
<DOI desc="投退" name="Mode">
<Private type="Siemens-AlternativeDesc">enable</Private>
<DAI name="setVal" valKind="Set">
<Val>OFF</Val>
</DAI>
<DAI name="dataNs">
<Val>SIEMENS EXT</Val>
</DAI>
</DOI>
<DOI desc="PT断线闭锁过流方向元件" name="BlkDir">
<Private type="Siemens-AlternativeDesc">PT broken for direction</Private>
<DAI name="setVal" valKind="Set">
<Val>true</Val>
</DAI>
<DAI name="dataNs">
<Val>SIEMENS EXT</Val>
</DAI>
</DOI>
<DOI desc="启动定值" name="StrVal">
<Private type="Siemens-AlternativeDesc">pickup</Private>
<SDI name="setMag">
<DAI name="f" valKind="Set">
<Val>20.000000</Val>
</DAI>
</SDI>
<SDI name="units">
<DAI name="SIUnit">
<Val>A</Val>
</DAI>
<DAI name="multiplier">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="minVal">
<DAI name="f">
<Val>0.150000</Val>
</DAI>
</SDI>
<SDI name="maxVal">
<DAI name="f">
<Val>200.000000</Val>
</DAI>
</SDI>
<SDI name="stepSize">
<DAI name="f">
<Val>0.010000</Val>
</DAI>
</SDI>
</DOI>
<DOI desc="动作延时时间" name="OpDlTmms">
<Private type="Siemens-AlternativeDesc">Time delay</Private>
<DAI name="setVal" valKind="Set">
<Val>100</Val>
</DAI>
<DAI name="minVal">
<Val>0</Val>
</DAI>
<DAI name="maxVal">
<Val>100000</Val>
</DAI>
<DAI name="stepSize">
<Val>10</Val>
</DAI>
</DOI>
<DOI desc="方向闭锁" name="DirMod">
<Private type="Siemens-AlternativeDesc">Phase Direction</Private>
<DAI name="setVal" valKind="Set">
<Val>Non-Directional</Val>
</DAI>
</DOI>
</LN>
<LN desc="零序过流II段" inst="1" lnClass="PTOC" lnType="F2T202IN/PROT/ZerIIPTOC1" prefix="ZerII">
<Private type="Siemens-AlternativeDesc">Dir DMT IE&gt;&gt;</Private>
<Private type="IsNodeProcessed"/>
<Private type="Siemens-ControlBlockStorage">urcbA|&lt;ReportControl rptID="F2E801FPROT/ZerIIPTOC1$RP$urcbA01" confRev="0" buffered="false" bufTime="100" name="urcbA"&gt; &lt;Private type="Siemens-PredefinedControlBlock" /&gt; &lt;TrgOps dchg="true" qchg="true" dupd="true" period="true" /&gt; &lt;OptFields seqNum="true" timeStamp="true" dataSet="true" reasonCode="true" dataRef="false" configRef="true" /&gt; &lt;RptEnabled max="1" /&gt; &lt;/ReportControl&gt;</Private>
<Private type="Siemens-ControlBlockStorage">urcbB|&lt;ReportControl rptID="F2E801FPROT/ZerIIPTOC1$RP$urcbB01" confRev="0" buffered="false" bufTime="100" name="urcbB"&gt; &lt;Private type="Siemens-PredefinedControlBlock" /&gt; &lt;TrgOps dchg="true" qchg="true" dupd="true" period="true" /&gt; &lt;OptFields seqNum="true" timeStamp="true" dataSet="true" reasonCode="true" dataRef="false" configRef="true" /&gt; &lt;RptEnabled max="1" /&gt; &lt;/ReportControl&gt;</Private>
<DOI desc="模式" name="Mod">
<Private type="Siemens-AlternativeDesc">Mode</Private>
<DAI name="ctlModel">
<Val>status-only</Val>
</DAI>
</DOI>
<DOI desc="性能" name="Beh">
<Private type="Siemens-AlternativeDesc">Behaviour</Private>
</DOI>
<DOI desc="健康状况" name="Health">
<Private type="Siemens-AlternativeDesc">State</Private>
</DOI>
<DOI desc="铭牌" name="NamPlt">
<Private type="Siemens-AlternativeDesc">Info</Private>
<DAI name="configRev">
<Val>160304190901000</Val>
</DAI>
</DOI>
<DOI desc="启动" name="Str">
<Private type="Siemens-AlternativeDesc">Pickup</Private>
</DOI>
<DOI desc="动作" name="Op">
<Private type="Siemens-AlternativeDesc">TRIP</Private>
</DOI>
<DOI desc="投退" name="Mode">
<Private type="Siemens-AlternativeDesc">enable</Private>
<DAI name="setVal" valKind="Set">
<Val>ON</Val>
</DAI>
<DAI name="dataNs">
<Val>SIEMENS EXT</Val>
</DAI>
</DOI>
<DOI desc="启动定值" name="StrVal">
<Private type="Siemens-AlternativeDesc">pickup</Private>
<SDI name="setMag">
<DAI name="f" valKind="Set">
<Val>2.500000</Val>
</DAI>
</SDI>
<SDI name="units">
<DAI name="SIUnit">
<Val>A</Val>
</DAI>
<DAI name="multiplier">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="minVal">
<DAI name="f">
<Val>0.150000</Val>
</DAI>
</SDI>
<SDI name="maxVal">
<DAI name="f">
<Val>200.000000</Val>
</DAI>
</SDI>
<SDI name="stepSize">
<DAI name="f">
<Val>0.010000</Val>
</DAI>
</SDI>
</DOI>
<DOI desc="动作延时时间" name="OpDlTmms">
<Private type="Siemens-AlternativeDesc">Time delay</Private>
<DAI name="setVal" valKind="Set">
<Val>0</Val>
</DAI>
<DAI name="minVal">
<Val>0</Val>
</DAI>
<DAI name="maxVal">
<Val>100000</Val>
</DAI>
<DAI name="stepSize">
<Val>10</Val>
</DAI>
</DOI>
<DOI desc="方向闭锁" name="DirMod">
<Private type="Siemens-AlternativeDesc">Phase Direction</Private>
<DAI name="setVal" valKind="Set">
<Val>Non-Directional</Val>
</DAI>
</DOI>
</LN>
<LN desc="零序过流III段" inst="1" lnClass="PTOC" lnType="F2T202IN/PROT/ZerIIPTOC1" prefix="ZerIII">
<Private type="Siemens-AlternativeDesc">Dir DMT IE&gt;&gt;&gt;</Private>
<Private type="IsNodeProcessed"/>
<Private type="Siemens-ControlBlockStorage">urcbA|&lt;ReportControl rptID="F2E801FPROT/ZerIIIPTOC1$RP$urcbA01" confRev="0" buffered="false" bufTime="100" name="urcbA"&gt; &lt;Private type="Siemens-PredefinedControlBlock" /&gt; &lt;TrgOps dchg="true" qchg="true" dupd="true" period="true" /&gt; &lt;OptFields seqNum="true" timeStamp="true" dataSet="true" reasonCode="true" dataRef="false" configRef="true" /&gt; &lt;RptEnabled max="1" /&gt; &lt;/ReportControl&gt;</Private>
<Private type="Siemens-ControlBlockStorage">urcbB|&lt;ReportControl rptID="F2E801FPROT/ZerIIIPTOC1$RP$urcbB01" confRev="0" buffered="false" bufTime="100" name="urcbB"&gt; &lt;Private type="Siemens-PredefinedControlBlock" /&gt; &lt;TrgOps dchg="true" qchg="true" dupd="true" period="true" /&gt; &lt;OptFields seqNum="true" timeStamp="true" dataSet="true" reasonCode="true" dataRef="false" configRef="true" /&gt; &lt;RptEnabled max="1" /&gt; &lt;/ReportControl&gt;</Private>
<DOI desc="模式" name="Mod">
<Private type="Siemens-AlternativeDesc">Mode</Private>
<DAI name="ctlModel">
<Val>status-only</Val>
</DAI>
</DOI>
<DOI desc="性能" name="Beh">
<Private type="Siemens-AlternativeDesc">Behaviour</Private>
</DOI>
<DOI desc="健康状况" name="Health">
<Private type="Siemens-AlternativeDesc">State</Private>
</DOI>
<DOI desc="铭牌" name="NamPlt">
<Private type="Siemens-AlternativeDesc">Info</Private>
<DAI name="configRev">
<Val>160304190901000</Val>
</DAI>
</DOI>
<DOI desc="启动" name="Str">
<Private type="Siemens-AlternativeDesc">Pickup</Private>
</DOI>
<DOI desc="动作" name="Op">
<Private type="Siemens-AlternativeDesc">TRIP</Private>
</DOI>
<DOI desc="投退" name="Mode">
<Private type="Siemens-AlternativeDesc">enable</Private>
<DAI name="setVal" valKind="Set">
<Val>OFF</Val>
</DAI>
<DAI name="dataNs">
<Val>SIEMENS EXT</Val>
</DAI>
</DOI>
<DOI desc="启动定值" name="StrVal">
<Private type="Siemens-AlternativeDesc">pickup</Private>
<SDI name="setMag">
<DAI name="f" valKind="Set">
<Val>5.000000</Val>
</DAI>
</SDI>
<SDI name="units">
<DAI name="SIUnit">
<Val>A</Val>
</DAI>
<DAI name="multiplier">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="minVal">
<DAI name="f">
<Val>0.150000</Val>
</DAI>
</SDI>
<SDI name="maxVal">
<DAI name="f">
<Val>200.000000</Val>
</DAI>
</SDI>
<SDI name="stepSize">
<DAI name="f">
<Val>0.010000</Val>
</DAI>
</SDI>
</DOI>
<DOI desc="动作延时时间" name="OpDlTmms">
<Private type="Siemens-AlternativeDesc">Time delay</Private>
<DAI name="setVal" valKind="Set">
<Val>1000</Val>
</DAI>
<DAI name="minVal">
<Val>0</Val>
</DAI>
<DAI name="maxVal">
<Val>100000</Val>
</DAI>
<DAI name="stepSize">
<Val>10</Val>
</DAI>
</DOI>
<DOI desc="方向闭锁" name="DirMod">
<Private type="Siemens-AlternativeDesc">Phase Direction</Private>
<DAI name="setVal" valKind="Set">
<Val>Non-Directional</Val>
</DAI>
</DOI>
</LN>
<LN desc="零序过流反时限" inst="1" lnClass="PTOC" lnType="F2T202IN/PROT/ZerRPTOC1" prefix="ZerR">
<Private type="Siemens-AlternativeDesc">Dir IDMT IEp</Private>
<Private type="IsNodeProcessed"/>
<Private type="Siemens-ControlBlockStorage">urcbA|&lt;ReportControl rptID="F2E801FPROT/ZerRPTOC1$RP$urcbA01" confRev="0" buffered="false" bufTime="100" name="urcbA"&gt; &lt;Private type="Siemens-PredefinedControlBlock" /&gt; &lt;TrgOps dchg="true" qchg="true" dupd="true" period="true" /&gt; &lt;OptFields seqNum="true" timeStamp="true" dataSet="true" reasonCode="true" dataRef="false" configRef="true" /&gt; &lt;RptEnabled max="1" /&gt; &lt;/ReportControl&gt;</Private>
<Private type="Siemens-ControlBlockStorage">urcbB|&lt;ReportControl rptID="F2E801FPROT/ZerRPTOC1$RP$urcbB01" confRev="0" buffered="false" bufTime="100" name="urcbB"&gt; &lt;Private type="Siemens-PredefinedControlBlock" /&gt; &lt;TrgOps dchg="true" qchg="true" dupd="true" period="true" /&gt; &lt;OptFields seqNum="true" timeStamp="true" dataSet="true" reasonCode="true" dataRef="false" configRef="true" /&gt; &lt;RptEnabled max="1" /&gt; &lt;/ReportControl&gt;</Private>
<DOI desc="模式" name="Mod">
<Private type="Siemens-AlternativeDesc">Mode</Private>
<DAI name="ctlModel">
<Val>status-only</Val>
</DAI>
</DOI>
<DOI desc="性能" name="Beh">
<Private type="Siemens-AlternativeDesc">Behaviour</Private>
</DOI>
<DOI desc="健康状况" name="Health">
<Private type="Siemens-AlternativeDesc">State</Private>
</DOI>
<DOI desc="铭牌" name="NamPlt">
<Private type="Siemens-AlternativeDesc">Info</Private>
<DAI name="configRev">
<Val>160304190901000</Val>
</DAI>
</DOI>
<DOI desc="启动" name="Str">
<Private type="Siemens-AlternativeDesc">Pickup</Private>
</DOI>
<DOI desc="动作" name="Op">
<Private type="Siemens-AlternativeDesc">TRIP</Private>
</DOI>
<DOI desc="投退" name="Mode">
<Private type="Siemens-AlternativeDesc">enable</Private>
<DAI name="setVal" valKind="Set">
<Val>ON</Val>
</DAI>
<DAI name="dataNs">
<Val>SIEMENS EXT</Val>
</DAI>
</DOI>
<DOI desc="反时限特性" name="TmACrv">
<Private type="Siemens-AlternativeDesc">IEC Curve</Private>
<DAI name="setCharact" valKind="Set">
<Val>Normal Inverse</Val>
</DAI>
</DOI>
<DOI desc="启动定值" name="StrVal">
<Private type="Siemens-AlternativeDesc">pickup</Private>
<SDI name="setMag">
<DAI name="f" valKind="Set">
<Val>0.500000</Val>
</DAI>
</SDI>
<SDI name="units">
<DAI name="SIUnit">
<Val>A</Val>
</DAI>
<DAI name="multiplier">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="minVal">
<DAI name="f">
<Val>0.150000</Val>
</DAI>
</SDI>
<SDI name="maxVal">
<DAI name="f">
<Val>100.000000</Val>
</DAI>
</SDI>
<SDI name="stepSize">
<DAI name="f">
<Val>0.010000</Val>
</DAI>
</SDI>
</DOI>
<DOI desc="动作延时时间" name="OpDlTmms">
<Private type="Siemens-AlternativeDesc">Time delay</Private>
<DAI name="setVal" valKind="Set">
<Val>100</Val>
</DAI>
<DAI name="minVal">
<Val>50</Val>
</DAI>
<DAI name="maxVal">
<Val>10000</Val>
</DAI>
<DAI name="stepSize">
<Val>10</Val>
</DAI>
</DOI>
<DOI desc="方向闭锁" name="DirMod">
<Private type="Siemens-AlternativeDesc">Phase Direction</Private>
<DAI name="setVal" valKind="Set">
<Val>Non-Directional</Val>
</DAI>
</DOI>
</LN>
<LN desc="过流I段" inst="1" lnClass="PTOC" lnType="F2T202IN/PROT/PhIPTOC1" prefix="PhI">
<Private type="Siemens-AlternativeDesc">Dir DMT I&gt;</Private>
<Private type="IsNodeProcessed"/>
<Private type="Siemens-ControlBlockStorage">urcbA|&lt;ReportControl rptID="F2E801FPROT/PhIPTOC1$RP$urcbA01" confRev="0" buffered="false" bufTime="100" name="urcbA"&gt; &lt;Private type="Siemens-PredefinedControlBlock" /&gt; &lt;TrgOps dchg="true" qchg="true" dupd="true" period="true" /&gt; &lt;OptFields seqNum="true" timeStamp="true" dataSet="true" reasonCode="true" dataRef="false" configRef="true" /&gt; &lt;RptEnabled max="1" /&gt; &lt;/ReportControl&gt;</Private>
<Private type="Siemens-ControlBlockStorage">urcbB|&lt;ReportControl rptID="F2E801FPROT/PhIPTOC1$RP$urcbB01" confRev="0" buffered="false" bufTime="100" name="urcbB"&gt; &lt;Private type="Siemens-PredefinedControlBlock" /&gt; &lt;TrgOps dchg="true" qchg="true" dupd="true" period="true" /&gt; &lt;OptFields seqNum="true" timeStamp="true" dataSet="true" reasonCode="true" dataRef="false" configRef="true" /&gt; &lt;RptEnabled max="1" /&gt; &lt;/ReportControl&gt;</Private>
<DOI desc="模式" name="Mod">
<Private type="Siemens-AlternativeDesc">Mode</Private>
<DAI name="ctlModel">
<Val>status-only</Val>
</DAI>
</DOI>
<DOI desc="性能" name="Beh">
<Private type="Siemens-AlternativeDesc">Behaviour</Private>
</DOI>
<DOI desc="健康状况" name="Health">
<Private type="Siemens-AlternativeDesc">State</Private>
</DOI>
<DOI desc="铭牌" name="NamPlt">
<Private type="Siemens-AlternativeDesc">Info</Private>
<DAI name="configRev">
<Val>160304190901000</Val>
</DAI>
</DOI>
<DOI desc="启动" name="Str">
<Private type="Siemens-AlternativeDesc">Pickup</Private>
</DOI>
<DOI desc="动作" name="Op">
<Private type="Siemens-AlternativeDesc">TRIP</Private>
</DOI>
<DOI desc="投退" name="Mode">
<Private type="Siemens-AlternativeDesc">enable</Private>
<DAI name="setVal" valKind="Set">
<Val>OFF</Val>
</DAI>
<DAI name="dataNs">
<Val>SIEMENS EXT</Val>
</DAI>
</DOI>
<DOI desc="PT断线闭锁过流方向元件" name="BlkDir">
<Private type="Siemens-AlternativeDesc">PT broken for direction</Private>
<DAI name="setVal" valKind="Set">
<Val>true</Val>
</DAI>
<DAI name="dataNs">
<Val>SIEMENS EXT</Val>
</DAI>
</DOI>
<DOI desc="PT断线闭锁复压元件" name="PTBlkV">
<Private type="Siemens-AlternativeDesc">PT broken for voltage control</Private>
<DAI name="setVal" valKind="Set">
<Val>true</Val>
</DAI>
<DAI name="dataNs">
<Val>SIEMENS EXT</Val>
</DAI>
</DOI>
<DOI desc="低压闭锁定值" name="BlkVPhPh">
<Private type="Siemens-AlternativeDesc">Ph-Ph under voltage Release Threshold</Private>
<SDI name="setMag">
<DAI name="f" valKind="Set">
<Val>50.000000</Val>
</DAI>
</SDI>
<SDI name="units">
<DAI name="SIUnit">
<Val>V</Val>
</DAI>
<DAI name="multiplier">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="minVal">
<DAI name="f">
<Val>1.000000</Val>
</DAI>
</SDI>
<SDI name="maxVal">
<DAI name="f">
<Val>100.000000</Val>
</DAI>
</SDI>
<SDI name="stepSize">
<DAI name="f">
<Val>0.100000</Val>
</DAI>
</SDI>
<DAI name="dataNs">
<Val>SIEMENS EXT</Val>
</DAI>
</DOI>
<DOI desc="负序电压闭锁定值" name="BlkNgv">
<Private type="Siemens-AlternativeDesc">U2 voltage Release Threshold</Private>
<SDI name="setMag">
<DAI name="f" valKind="Set">
<Val>8.000000</Val>
</DAI>
</SDI>
<SDI name="units">
<DAI name="SIUnit">
<Val>V</Val>
</DAI>
<DAI name="multiplier">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="minVal">
<DAI name="f">
<Val>1.000000</Val>
</DAI>
</SDI>
<SDI name="maxVal">
<DAI name="f">
<Val>57.000000</Val>
</DAI>
</SDI>
<SDI name="stepSize">
<DAI name="f">
<Val>0.100000</Val>
</DAI>
</SDI>
<DAI name="dataNs">
<Val>SIEMENS EXT</Val>
</DAI>
</DOI>
<DOI desc="复合电压闭锁" name="VCtrl">
<Private type="Siemens-AlternativeDesc">Voltage Control</Private>
<DAI name="setVal" valKind="Set">
<Val>false</Val>
</DAI>
<DAI name="dataNs">
<Val>SIEMENS EXT</Val>
</DAI>
</DOI>
<DOI desc="启动定值" name="StrVal">
<Private type="Siemens-AlternativeDesc">pickup</Private>
<SDI name="setMag">
<DAI name="f" valKind="Set">
<Val>40.000000</Val>
</DAI>
</SDI>
<SDI name="units">
<DAI name="SIUnit">
<Val>A</Val>
</DAI>
<DAI name="multiplier">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="minVal">
<DAI name="f">
<Val>0.150000</Val>
</DAI>
</SDI>
<SDI name="maxVal">
<DAI name="f">
<Val>200.000000</Val>
</DAI>
</SDI>
<SDI name="stepSize">
<DAI name="f">
<Val>0.010000</Val>
</DAI>
</SDI>
</DOI>
<DOI desc="动作延时时间" name="OpDlTmms">
<Private type="Siemens-AlternativeDesc">Time delay</Private>
<DAI name="setVal" valKind="Set">
<Val>0</Val>
</DAI>
<DAI name="minVal">
<Val>0</Val>
</DAI>
<DAI name="maxVal">
<Val>100000</Val>
</DAI>
<DAI name="stepSize">
<Val>10</Val>
</DAI>
</DOI>
<DOI desc="方向闭锁" name="DirMod">
<Private type="Siemens-AlternativeDesc">Phase Direction</Private>
<DAI name="setVal" valKind="Set">
<Val>Non-Directional</Val>
</DAI>
</DOI>
</LN>
<LN desc="过流II段" inst="1" lnClass="PTOC" lnType="F2T202IN/PROT/PhIIPTOC1" prefix="PhII">
<Private type="Siemens-AlternativeDesc">Dir DMT I&gt;&gt;</Private>
<Private type="IsNodeProcessed"/>
<Private type="Siemens-ControlBlockStorage">urcbA|&lt;ReportControl rptID="F2E801FPROT/PhIIPTOC1$RP$urcbA01" confRev="0" buffered="false" bufTime="100" name="urcbA"&gt; &lt;Private type="Siemens-PredefinedControlBlock" /&gt; &lt;TrgOps dchg="true" qchg="true" dupd="true" period="true" /&gt; &lt;OptFields seqNum="true" timeStamp="true" dataSet="true" reasonCode="true" dataRef="false" configRef="true" /&gt; &lt;RptEnabled max="1" /&gt; &lt;/ReportControl&gt;</Private>
<Private type="Siemens-ControlBlockStorage">urcbB|&lt;ReportControl rptID="F2E801FPROT/PhIIPTOC1$RP$urcbB01" confRev="0" buffered="false" bufTime="100" name="urcbB"&gt; &lt;Private type="Siemens-PredefinedControlBlock" /&gt; &lt;TrgOps dchg="true" qchg="true" dupd="true" period="true" /&gt; &lt;OptFields seqNum="true" timeStamp="true" dataSet="true" reasonCode="true" dataRef="false" configRef="true" /&gt; &lt;RptEnabled max="1" /&gt; &lt;/ReportControl&gt;</Private>
<DOI desc="模式" name="Mod">
<Private type="Siemens-AlternativeDesc">Mode</Private>
<DAI name="ctlModel">
<Val>status-only</Val>
</DAI>
</DOI>
<DOI desc="性能" name="Beh">
<Private type="Siemens-AlternativeDesc">Behaviour</Private>
</DOI>
<DOI desc="健康状况" name="Health">
<Private type="Siemens-AlternativeDesc">State</Private>
</DOI>
<DOI desc="铭牌" name="NamPlt">
<Private type="Siemens-AlternativeDesc">Info</Private>
<DAI name="configRev">
<Val>160304190901000</Val>
</DAI>
</DOI>
<DOI desc="启动" name="Str">
<Private type="Siemens-AlternativeDesc">Pickup</Private>
</DOI>
<DOI desc="动作" name="Op">
<Private type="Siemens-AlternativeDesc">TRIP</Private>
</DOI>
<DOI desc="投退" name="Mode">
<Private type="Siemens-AlternativeDesc">enable</Private>
<DAI name="setVal" valKind="Set">
<Val>ON</Val>
</DAI>
<DAI name="dataNs">
<Val>SIEMENS EXT</Val>
</DAI>
</DOI>
<DOI desc="复合电压闭锁" name="VCtrl">
<Private type="Siemens-AlternativeDesc">Voltage Control</Private>
<DAI name="setVal" valKind="Set">
<Val>false</Val>
</DAI>
<DAI name="dataNs">
<Val>SIEMENS EXT</Val>
</DAI>
</DOI>
<DOI desc="启动定值" name="StrVal">
<Private type="Siemens-AlternativeDesc">pickup</Private>
<SDI name="setMag">
<DAI name="f" valKind="Set">
<Val>40.000000</Val>
</DAI>
</SDI>
<SDI name="units">
<DAI name="SIUnit">
<Val>A</Val>
</DAI>
<DAI name="multiplier">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="minVal">
<DAI name="f">
<Val>0.150000</Val>
</DAI>
</SDI>
<SDI name="maxVal">
<DAI name="f">
<Val>200.000000</Val>
</DAI>
</SDI>
<SDI name="stepSize">
<DAI name="f">
<Val>0.010000</Val>
</DAI>
</SDI>
</DOI>
<DOI desc="动作延时时间" name="OpDlTmms">
<Private type="Siemens-AlternativeDesc">Time delay</Private>
<DAI name="setVal" valKind="Set">
<Val>0</Val>
</DAI>
<DAI name="minVal">
<Val>0</Val>
</DAI>
<DAI name="maxVal">
<Val>100000</Val>
</DAI>
<DAI name="stepSize">
<Val>10</Val>
</DAI>
</DOI>
<DOI desc="方向闭锁" name="DirMod">
<Private type="Siemens-AlternativeDesc">Phase Direction</Private>
<DAI name="setVal" valKind="Set">
<Val>Non-Directional</Val>
</DAI>
</DOI>
</LN>
<LN desc="过流III段" inst="1" lnClass="PTOC" lnType="F2T202IN/PROT/PhIIPTOC1" prefix="PhIII">
<Private type="Siemens-AlternativeDesc">Dir DMT I&gt;&gt;&gt;</Private>
<Private type="IsNodeProcessed"/>
<Private type="Siemens-ControlBlockStorage">urcbA|&lt;ReportControl rptID="F2E801FPROT/PhIIIPTOC1$RP$urcbA01" confRev="0" buffered="false" bufTime="100" name="urcbA"&gt; &lt;Private type="Siemens-PredefinedControlBlock" /&gt; &lt;TrgOps dchg="true" qchg="true" dupd="true" period="true" /&gt; &lt;OptFields seqNum="true" timeStamp="true" dataSet="true" reasonCode="true" dataRef="false" configRef="true" /&gt; &lt;RptEnabled max="1" /&gt; &lt;/ReportControl&gt;</Private>
<Private type="Siemens-ControlBlockStorage">urcbB|&lt;ReportControl rptID="F2E801FPROT/PhIIIPTOC1$RP$urcbB01" confRev="0" buffered="false" bufTime="100" name="urcbB"&gt; &lt;Private type="Siemens-PredefinedControlBlock" /&gt; &lt;TrgOps dchg="true" qchg="true" dupd="true" period="true" /&gt; &lt;OptFields seqNum="true" timeStamp="true" dataSet="true" reasonCode="true" dataRef="false" configRef="true" /&gt; &lt;RptEnabled max="1" /&gt; &lt;/ReportControl&gt;</Private>
<DOI desc="模式" name="Mod">
<Private type="Siemens-AlternativeDesc">Mode</Private>
<DAI name="ctlModel">
<Val>status-only</Val>
</DAI>
</DOI>
<DOI desc="性能" name="Beh">
<Private type="Siemens-AlternativeDesc">Behaviour</Private>
</DOI>
<DOI desc="健康状况" name="Health">
<Private type="Siemens-AlternativeDesc">State</Private>
</DOI>
<DOI desc="铭牌" name="NamPlt">
<Private type="Siemens-AlternativeDesc">Info</Private>
<DAI name="configRev">
<Val>160304190901000</Val>
</DAI>
</DOI>
<DOI desc="启动" name="Str">
<Private type="Siemens-AlternativeDesc">Pickup</Private>
</DOI>
<DOI desc="动作" name="Op">
<Private type="Siemens-AlternativeDesc">TRIP</Private>
</DOI>
<DOI desc="投退" name="Mode">
<Private type="Siemens-AlternativeDesc">enable</Private>
<DAI name="setVal" valKind="Set">
<Val>OFF</Val>
</DAI>
<DAI name="dataNs">
<Val>SIEMENS EXT</Val>
</DAI>
</DOI>
<DOI desc="复合电压闭锁" name="VCtrl">
<Private type="Siemens-AlternativeDesc">Voltage Control</Private>
<DAI name="setVal" valKind="Set">
<Val>false</Val>
</DAI>
<DAI name="dataNs">
<Val>SIEMENS EXT</Val>
</DAI>
</DOI>
<DOI desc="启动定值" name="StrVal">
<Private type="Siemens-AlternativeDesc">pickup</Private>
<SDI name="setMag">
<DAI name="f" valKind="Set">
<Val>5.000000</Val>
</DAI>
</SDI>
<SDI name="units">
<DAI name="SIUnit">
<Val>A</Val>
</DAI>
<DAI name="multiplier">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="minVal">
<DAI name="f">
<Val>0.150000</Val>
</DAI>
</SDI>
<SDI name="maxVal">
<DAI name="f">
<Val>200.000000</Val>
</DAI>
</SDI>
<SDI name="stepSize">
<DAI name="f">
<Val>0.010000</Val>
</DAI>
</SDI>
</DOI>
<DOI desc="动作延时时间" name="OpDlTmms">
<Private type="Siemens-AlternativeDesc">Time delay</Private>
<DAI name="setVal" valKind="Set">
<Val>1000</Val>
</DAI>
<DAI name="minVal">
<Val>0</Val>
</DAI>
<DAI name="maxVal">
<Val>100000</Val>
</DAI>
<DAI name="stepSize">
<Val>10</Val>
</DAI>
</DOI>
<DOI desc="方向闭锁" name="DirMod">
<Private type="Siemens-AlternativeDesc">Phase Direction</Private>
<DAI name="setVal" valKind="Set">
<Val>Non-Directional</Val>
</DAI>
</DOI>
</LN>
<LN desc="过流反时限" inst="1" lnClass="PTOC" lnType="F2T202IN/PROT/ZerRPTOC1" prefix="PhR">
<Private type="Siemens-AlternativeDesc">Dir IDMT Ip</Private>
<Private type="IsNodeProcessed"/>
<Private type="Siemens-ControlBlockStorage">urcbA|&lt;ReportControl rptID="F2E801FPROT/PhRPTOC1$RP$urcbA01" confRev="0" buffered="false" bufTime="100" name="urcbA"&gt; &lt;Private type="Siemens-PredefinedControlBlock" /&gt; &lt;TrgOps dchg="true" qchg="true" dupd="true" period="true" /&gt; &lt;OptFields seqNum="true" timeStamp="true" dataSet="true" reasonCode="true" dataRef="false" configRef="true" /&gt; &lt;RptEnabled max="1" /&gt; &lt;/ReportControl&gt;</Private>
<Private type="Siemens-ControlBlockStorage">urcbB|&lt;ReportControl rptID="F2E801FPROT/PhRPTOC1$RP$urcbB01" confRev="0" buffered="false" bufTime="100" name="urcbB"&gt; &lt;Private type="Siemens-PredefinedControlBlock" /&gt; &lt;TrgOps dchg="true" qchg="true" dupd="true" period="true" /&gt; &lt;OptFields seqNum="true" timeStamp="true" dataSet="true" reasonCode="true" dataRef="false" configRef="true" /&gt; &lt;RptEnabled max="1" /&gt; &lt;/ReportControl&gt;</Private>
<DOI desc="模式" name="Mod">
<Private type="Siemens-AlternativeDesc">Mode</Private>
<DAI name="ctlModel">
<Val>status-only</Val>
</DAI>
</DOI>
<DOI desc="性能" name="Beh">
<Private type="Siemens-AlternativeDesc">Behaviour</Private>
</DOI>
<DOI desc="健康状况" name="Health">
<Private type="Siemens-AlternativeDesc">State</Private>
</DOI>
<DOI desc="铭牌" name="NamPlt">
<Private type="Siemens-AlternativeDesc">Info</Private>
<DAI name="configRev">
<Val>160304190901000</Val>
</DAI>
</DOI>
<DOI desc="启动" name="Str">
<Private type="Siemens-AlternativeDesc">Pickup</Private>
</DOI>
<DOI desc="动作" name="Op">
<Private type="Siemens-AlternativeDesc">TRIP</Private>
</DOI>
<DOI desc="投退" name="Mode">
<Private type="Siemens-AlternativeDesc">enable</Private>
<DAI name="setVal" valKind="Set">
<Val>ON</Val>
</DAI>
<DAI name="dataNs">
<Val>SIEMENS EXT</Val>
</DAI>
</DOI>
<DOI desc="反时限特性" name="TmACrv">
<Private type="Siemens-AlternativeDesc">IEC Curve</Private>
<DAI name="setCharact" valKind="Set">
<Val>Normal Inverse</Val>
</DAI>
</DOI>
<DOI desc="启动定值" name="StrVal">
<Private type="Siemens-AlternativeDesc">pickup</Private>
<SDI name="setMag">
<DAI name="f" valKind="Set">
<Val>5.000000</Val>
</DAI>
</SDI>
<SDI name="units">
<DAI name="SIUnit">
<Val>A</Val>
</DAI>
<DAI name="multiplier">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="minVal">
<DAI name="f">
<Val>0.150000</Val>
</DAI>
</SDI>
<SDI name="maxVal">
<DAI name="f">
<Val>125.000000</Val>
</DAI>
</SDI>
<SDI name="stepSize">
<DAI name="f">
<Val>0.010000</Val>
</DAI>
</SDI>
</DOI>
<DOI desc="动作延时时间" name="OpDlTmms">
<Private type="Siemens-AlternativeDesc">Time delay</Private>
<DAI name="setVal" valKind="Set">
<Val>100</Val>
</DAI>
<DAI name="minVal">
<Val>50</Val>
</DAI>
<DAI name="maxVal">
<Val>10000</Val>
</DAI>
<DAI name="stepSize">
<Val>10</Val>
</DAI>
</DOI>
<DOI desc="方向闭锁" name="DirMod">
<Private type="Siemens-AlternativeDesc">Phase Direction</Private>
<DAI name="setVal" valKind="Set">
<Val>Non-Directional</Val>
</DAI>
</DOI>
</LN>
<LN desc="装置跳闸逻辑" inst="1" lnClass="PTRC" lnType="F2T202IN/PROT/PTRC1" prefix="">
<Private type="Siemens-AlternativeDesc">Total</Private>
<Private type="IsNodeProcessed"/>
<Private type="Siemens-ControlBlockStorage">urcbA|&lt;ReportControl rptID="F2E801FPROT/PTRC1$RP$urcbA01" confRev="0" buffered="false" bufTime="100" name="urcbA"&gt; &lt;Private type="Siemens-PredefinedControlBlock" /&gt; &lt;TrgOps dchg="true" qchg="true" dupd="true" period="true" /&gt; &lt;OptFields seqNum="true" timeStamp="true" dataSet="true" reasonCode="true" dataRef="false" configRef="true" /&gt; &lt;RptEnabled max="1" /&gt; &lt;/ReportControl&gt;</Private>
<Private type="Siemens-ControlBlockStorage">urcbB|&lt;ReportControl rptID="F2E801FPROT/PTRC1$RP$urcbB01" confRev="0" buffered="false" bufTime="100" name="urcbB"&gt; &lt;Private type="Siemens-PredefinedControlBlock" /&gt; &lt;TrgOps dchg="true" qchg="true" dupd="true" period="true" /&gt; &lt;OptFields seqNum="true" timeStamp="true" dataSet="true" reasonCode="true" dataRef="false" configRef="true" /&gt; &lt;RptEnabled max="1" /&gt; &lt;/ReportControl&gt;</Private>
<DOI desc="模式" name="Mod">
<Private type="Siemens-AlternativeDesc">Mode</Private>
<DAI name="ctlModel">
<Val>direct-with-enhanced-security</Val>
</DAI>
</DOI>
<DOI desc="性能" name="Beh">
<Private type="Siemens-AlternativeDesc">Behaviour</Private>
</DOI>
<DOI desc="健康状况" name="Health">
<Private type="Siemens-AlternativeDesc">State</Private>
</DOI>
<DOI desc="铭牌" name="NamPlt">
<Private type="Siemens-AlternativeDesc">Info</Private>
<DAI name="configRev">
<Val>160304190901000</Val>
</DAI>
</DOI>
<DOI desc="跳闸" name="Tr">
<Private type="Siemens-AlternativeDesc">TRIP</Private>
</DOI>
<DOI desc="启动" name="Str">
<Private type="Siemens-AlternativeDesc">Pickup</Private>
</DOI>
</LN>
<LN desc="断路器" inst="1" lnClass="XCBR" lnType="F2T202IN/PROT/XCBR1" prefix="">
<Private type="Siemens-AlternativeDesc">CB</Private>
<Private type="IsNodeProcessed"/>
<Private type="Siemens-ControlBlockStorage">urcbA|&lt;ReportControl rptID="F2E801FPROT/XCBR1$RP$urcbA01" confRev="0" buffered="false" bufTime="100" name="urcbA"&gt; &lt;Private type="Siemens-PredefinedControlBlock" /&gt; &lt;TrgOps dchg="true" qchg="true" dupd="true" period="true" /&gt; &lt;OptFields seqNum="true" timeStamp="true" dataSet="true" reasonCode="true" dataRef="false" configRef="true" /&gt; &lt;RptEnabled max="1" /&gt; &lt;/ReportControl&gt;</Private>
<Private type="Siemens-ControlBlockStorage">urcbB|&lt;ReportControl rptID="F2E801FPROT/XCBR1$RP$urcbB01" confRev="0" buffered="false" bufTime="100" name="urcbB"&gt; &lt;Private type="Siemens-PredefinedControlBlock" /&gt; &lt;TrgOps dchg="true" qchg="true" dupd="true" period="true" /&gt; &lt;OptFields seqNum="true" timeStamp="true" dataSet="true" reasonCode="true" dataRef="false" configRef="true" /&gt; &lt;RptEnabled max="1" /&gt; &lt;/ReportControl&gt;</Private>
<DOI desc="模式" name="Mod">
<Private type="Siemens-AlternativeDesc">Mode</Private>
<DAI name="ctlModel">
<Val>status-only</Val>
</DAI>
</DOI>
<DOI desc="性能" name="Beh">
<Private type="Siemens-AlternativeDesc">Behaviour</Private>
</DOI>
<DOI desc="健康状况" name="Health">
<Private type="Siemens-AlternativeDesc">State</Private>
</DOI>
<DOI desc="铭牌" name="NamPlt">
<Private type="Siemens-AlternativeDesc">Info</Private>
<DAI name="configRev">
<Val>160304190901000</Val>
</DAI>
</DOI>
<DOI desc="本地操作" name="Loc">
<Private type="Siemens-AlternativeDesc">local</Private>
</DOI>
<DOI desc="跳闸总次数" name="OpCnt">
<Private type="Siemens-AlternativeDesc">TripComdCounter</Private>
</DOI>
<DOI desc="位置" name="Pos">
<Private type="Siemens-AlternativeDesc">Position</Private>
<DAI name="ctlModel">
<Val>status-only</Val>
</DAI>
</DOI>
<DOI desc="跳闸闭锁" name="BlkOpn">
<Private type="Siemens-AlternativeDesc">Open block</Private>
<DAI name="ctlModel">
<Val>status-only</Val>
</DAI>
</DOI>
<DOI desc="合闸闭锁" name="BlkCls">
<Private type="Siemens-AlternativeDesc">Close block</Private>
<DAI name="ctlModel">
<Val>status-only</Val>
</DAI>
</DOI>
<DOI desc="A相断开电流累积和" name="SumSwARs1">
<Private type="Siemens-AlternativeDesc">Sum IL1</Private>
<SDI name="units">
<DAI name="SIUnit"/>
</SDI>
<DAI name="d">
<Val>SumSwARs1 stands for Accumulation of interrupted current L1</Val>
</DAI>
</DOI>
<DOI desc="B相断开电流累积和" name="SumSwARs2">
<Private type="Siemens-AlternativeDesc">Sum IL2</Private>
<SDI name="units">
<DAI name="SIUnit"/>
</SDI>
<DAI name="d">
<Val>SumSwARs2 stands for Accumulation of interrupted current L2</Val>
</DAI>
</DOI>
<DOI desc="C相断开电流累积和" name="SumSwARs3">
<Private type="Siemens-AlternativeDesc">Sum IL3</Private>
<SDI name="units">
<DAI name="SIUnit"/>
</SDI>
<DAI name="d">
<Val>SumSwARs3 stands for Accumulation of interrupted current L3</Val>
</DAI>
</DOI>
<DOI desc="断路器操作能力" name="CBOpCap">
<Private type="Siemens-AlternativeDesc">Switch capablty</Private>
<DAI name="stVal">
<Val>None</Val>
</DAI>
</DOI>
<DOI desc="负荷率 0- 50%总天数=" name="LoadPro1">
<Private type="Siemens-AlternativeDesc">Load 0-50%</Private>
<SDI name="units">
<DAI name="SIUnit"/>
</SDI>
<DAI name="d">
<Val>LoadPro1 stands for current load profile 0-50%</Val>
</DAI>
<DAI name="dataNs">
<Val>SIEMENS EXT</Val>
</DAI>
</DOI>
<DOI desc="负荷率50- 70%总天数=" name="LoadPro2">
<Private type="Siemens-AlternativeDesc">Load 50-70%</Private>
<SDI name="units">
<DAI name="SIUnit"/>
</SDI>
<DAI name="d">
<Val>LoadPro2 stands for current load profile 50-70%</Val>
</DAI>
<DAI name="dataNs">
<Val>SIEMENS EXT</Val>
</DAI>
</DOI>
<DOI desc="负荷率70- 85%总天数=" name="LoadPro3">
<Private type="Siemens-AlternativeDesc">Load 70-85%</Private>
<SDI name="units">
<DAI name="SIUnit"/>
</SDI>
<DAI name="d">
<Val>LoadPro3 stands for current load profile 70-85%</Val>
</DAI>
<DAI name="dataNs">
<Val>SIEMENS EXT</Val>
</DAI>
</DOI>
<DOI desc="负荷率85-120%总天数=" name="LoadPro4">
<Private type="Siemens-AlternativeDesc">Load 85-120%</Private>
<SDI name="units">
<DAI name="SIUnit"/>
</SDI>
<DAI name="d">
<Val>LoadPro4 stands for current load profile over 85%</Val>
</DAI>
<DAI name="dataNs">
<Val>SIEMENS EXT</Val>
</DAI>
</DOI>
</LN>
<LN desc="非电量保护" inst="1" lnClass="GGIO" lnType="F2T202A/PROT/NonEleGGIO1" prefix="NonEle">
<Private type="Siemens-AlternativeDesc">NonEleGGIO</Private>
<Private type="IsNodeProcessed"/>
<Private type="Siemens-ControlBlockStorage">urcbA|&lt;ReportControl rptID="F2E801FPROT/NonEleGGIO1$RP$urcbA01" confRev="0" buffered="false" bufTime="100" name="urcbA"&gt; &lt;Private type="Siemens-PredefinedControlBlock" /&gt; &lt;TrgOps dchg="true" qchg="true" dupd="true" period="true" /&gt; &lt;OptFields seqNum="true" timeStamp="true" dataSet="true" reasonCode="true" dataRef="false" configRef="true" /&gt; &lt;RptEnabled max="1" /&gt; &lt;/ReportControl&gt;</Private>
<Private type="Siemens-ControlBlockStorage">urcbB|&lt;ReportControl rptID="F2E801FPROT/NonEleGGIO1$RP$urcbB01" confRev="0" buffered="false" bufTime="100" name="urcbB"&gt; &lt;Private type="Siemens-PredefinedControlBlock" /&gt; &lt;TrgOps dchg="true" qchg="true" dupd="true" period="true" /&gt; &lt;OptFields seqNum="true" timeStamp="true" dataSet="true" reasonCode="true" dataRef="false" configRef="true" /&gt; &lt;RptEnabled max="1" /&gt; &lt;/ReportControl&gt;</Private>
<DOI desc="模式" name="Mod">
<Private type="Siemens-AlternativeDesc">Mode</Private>
<DAI name="ctlModel">
<Val>status-only</Val>
</DAI>
</DOI>
<DOI desc="性能" name="Beh">
<Private type="Siemens-AlternativeDesc">Behaviour</Private>
</DOI>
<DOI desc="健康状况" name="Health">
<Private type="Siemens-AlternativeDesc">State</Private>
</DOI>
<DOI desc="铭牌" name="NamPlt">
<Private type="Siemens-AlternativeDesc">Info</Private>
<DAI name="configRev">
<Val>160304190901000</Val>
</DAI>
</DOI>
<DOI desc="闭锁" name="SPCSO1">
<Private type="Siemens-AlternativeDesc">Non-electrical is Blocked</Private>
<DAI name="ctlModel">
<Val>status-only</Val>
</DAI>
</DOI>
<DOI desc="投入" name="SPCSO2">
<Private type="Siemens-AlternativeDesc">Non-electrical is Active</Private>
<DAI name="ctlModel">
<Val>status-only</Val>
</DAI>
</DOI>
<DOI desc="退出" name="SPCSO3">
<Private type="Siemens-AlternativeDesc">Non-electrical is OFF</Private>
<DAI name="ctlModel">
<Val>status-only</Val>
</DAI>
</DOI>
<DOI desc="重瓦斯跳闸" name="SPCSO4">
<Private type="Siemens-AlternativeDesc">Heavy Gas Trip</Private>
<DAI name="ctlModel">
<Val>status-only</Val>
</DAI>
</DOI>
<DOI desc="轻瓦斯跳闸" name="SPCSO5">
<Private type="Siemens-AlternativeDesc">Light Gas Trip</Private>
<DAI name="ctlModel">
<Val>status-only</Val>
</DAI>
</DOI>
<DOI desc="超温跳闸" name="SPCSO6">
<Private type="Siemens-AlternativeDesc">Over Temperature Trip</Private>
<DAI name="ctlModel">
<Val>status-only</Val>
</DAI>
</DOI>
<DOI desc="高温跳闸" name="SPCSO7">
<Private type="Siemens-AlternativeDesc">High Temperature Trip</Private>
<DAI name="ctlModel">
<Val>status-only</Val>
</DAI>
</DOI>
<DOI desc="压力释放跳闸" name="SPCSO8">
<Private type="Siemens-AlternativeDesc">Pressure Release Trip</Private>
<DAI name="ctlModel">
<Val>status-only</Val>
</DAI>
</DOI>
<DOI desc="重瓦斯告警" name="SPCSO9">
<Private type="Siemens-AlternativeDesc">Heavy Gas Alarm</Private>
<DAI name="ctlModel">
<Val>status-only</Val>
</DAI>
</DOI>
<DOI desc="轻瓦斯告警" name="SPCSO10">
<Private type="Siemens-AlternativeDesc">Light Gas Alarm</Private>
<DAI name="ctlModel">
<Val>status-only</Val>
</DAI>
</DOI>
<DOI desc="超温告警" name="SPCSO11">
<Private type="Siemens-AlternativeDesc">Over Temperature Alarm</Private>
<DAI name="ctlModel">
<Val>status-only</Val>
</DAI>
</DOI>
<DOI desc="高温告警" name="SPCSO12">
<Private type="Siemens-AlternativeDesc">High Temperature Alarm</Private>
<DAI name="ctlModel">
<Val>status-only</Val>
</DAI>
</DOI>
<DOI desc="压力释放告警" name="SPCSO13">
<Private type="Siemens-AlternativeDesc">Pressure Release Alarm</Private>
<DAI name="ctlModel">
<Val>status-only</Val>
</DAI>
</DOI>
<DOI desc="&gt;重瓦斯开入" name="SPCSO14">
<Private type="Siemens-AlternativeDesc">&gt;Heavy Gas</Private>
<DAI name="ctlModel">
<Val>status-only</Val>
</DAI>
</DOI>
<DOI desc="&gt;轻瓦斯开入" name="SPCSO15">
<Private type="Siemens-AlternativeDesc">&gt;Light Gas</Private>
<DAI name="ctlModel">
<Val>status-only</Val>
</DAI>
</DOI>
<DOI desc="&gt;超温开入" name="SPCSO16">
<Private type="Siemens-AlternativeDesc">&gt;Over Temperature</Private>
<DAI name="ctlModel">
<Val>status-only</Val>
</DAI>
</DOI>
<DOI desc="&gt;高温开入" name="SPCSO17">
<Private type="Siemens-AlternativeDesc">&gt;High Temperature</Private>
<DAI name="ctlModel">
<Val>status-only</Val>
</DAI>
</DOI>
<DOI desc="&gt;压力释放" name="SPCSO18">
<Private type="Siemens-AlternativeDesc">&gt;Pressure Release</Private>
<DAI name="ctlModel">
<Val>status-only</Val>
</DAI>
</DOI>
</LN>
<LN desc="测量监视功能" inst="1" lnClass="GGIO" lnType="F2T202IN/PROT/SupVGGIO1" prefix="SupV">
<Private type="Siemens-AlternativeDesc">SupVGGIO</Private>
<Private type="IsNodeProcessed"/>
<Private type="Siemens-ControlBlockStorage">urcbA|&lt;ReportControl rptID="F2E801FPROT/SupVGGIO1$RP$urcbA01" confRev="0" buffered="false" bufTime="100" name="urcbA"&gt; &lt;Private type="Siemens-PredefinedControlBlock" /&gt; &lt;TrgOps dchg="true" qchg="true" dupd="true" period="true" /&gt; &lt;OptFields seqNum="true" timeStamp="true" dataSet="true" reasonCode="true" dataRef="false" configRef="true" /&gt; &lt;RptEnabled max="1" /&gt; &lt;/ReportControl&gt;</Private>
<Private type="Siemens-ControlBlockStorage">urcbB|&lt;ReportControl rptID="F2E801FPROT/SupVGGIO1$RP$urcbB01" confRev="0" buffered="false" bufTime="100" name="urcbB"&gt; &lt;Private type="Siemens-PredefinedControlBlock" /&gt; &lt;TrgOps dchg="true" qchg="true" dupd="true" period="true" /&gt; &lt;OptFields seqNum="true" timeStamp="true" dataSet="true" reasonCode="true" dataRef="false" configRef="true" /&gt; &lt;RptEnabled max="1" /&gt; &lt;/ReportControl&gt;</Private>
<DOI desc="模式" name="Mod">
<Private type="Siemens-AlternativeDesc">Mode</Private>
<DAI name="ctlModel">
<Val>status-only</Val>
</DAI>
</DOI>
<DOI desc="性能" name="Beh">
<Private type="Siemens-AlternativeDesc">Behaviour</Private>
</DOI>
<DOI desc="健康状况" name="Health">
<Private type="Siemens-AlternativeDesc">State</Private>
</DOI>
<DOI desc="铭牌" name="NamPlt">
<Private type="Siemens-AlternativeDesc">Info</Private>
<DAI name="configRev">
<Val>160304190901000</Val>
</DAI>
</DOI>
<DOI desc="PT断线告警" name="SPCSO1">
<Private type="Siemens-AlternativeDesc">Failure VT circuit: broken wire</Private>
<DAI name="ctlModel">
<Val>status-only</Val>
</DAI>
</DOI>
<DOI desc="PT断线10s后告警" name="SPCSO2">
<Private type="Siemens-AlternativeDesc">VT Fuse Failure (alarm &gt;10s)</Private>
<DAI name="ctlModel">
<Val>status-only</Val>
</DAI>
</DOI>
<DOI desc="PT断线瞬时告警" name="SPCSO3">
<Private type="Siemens-AlternativeDesc">VT Fuse Failure (alarm instantaneous)</Private>
<DAI name="ctlModel">
<Val>status-only</Val>
</DAI>
</DOI>
<DOI desc="冷负荷启动" name="SPCSO4">
<Private type="Siemens-AlternativeDesc">Cold Load Pickup</Private>
<DAI name="ctlModel">
<Val>status-only</Val>
</DAI>
</DOI>
<DOI desc="CT 断线12s 后告警" name="SPCSO6">
<Private type="Siemens-AlternativeDesc">CT Broken alarm &gt;12s</Private>
<DAI name="ctlModel">
<Val>status-only</Val>
</DAI>
</DOI>
</LN>
</LDevice>
<LDevice desc="测量" inst="MEAS">
<Private type="Siemens-AlternativeDesc">Measurement</Private>
<Private type="IsNodeProcessed"/>
<LN0 desc="公用" inst="" lnClass="LLN0" lnType="F2T202IN/MEAS/LLN0">
<Private type="Siemens-AlternativeDesc">General</Private>
<Private type="Siemens-ControlBlockStorage">urcbB|&lt;ReportControl rptID="F2E801FMEAS/LLN0$RP$urcbB01" confRev="0" buffered="false" bufTime="100" name="urcbB"&gt; &lt;Private type="Siemens-PredefinedControlBlock" /&gt; &lt;TrgOps dchg="true" qchg="true" dupd="true" period="true" /&gt; &lt;OptFields seqNum="true" timeStamp="true" dataSet="true" reasonCode="true" dataRef="false" configRef="true" /&gt; &lt;RptEnabled max="1" /&gt; &lt;/ReportControl&gt;</Private>
<Private type="Siemens-ControlBlockStorage">urcbC|&lt;ReportControl rptID="F2E801FMEAS/LLN0$RP$urcbC01" confRev="0" buffered="false" bufTime="100" name="urcbC"&gt; &lt;Private type="Siemens-PredefinedControlBlock" /&gt; &lt;TrgOps dchg="true" qchg="true" dupd="true" period="true" /&gt; &lt;OptFields seqNum="true" timeStamp="true" dataSet="true" reasonCode="true" dataRef="false" configRef="true" /&gt; &lt;RptEnabled max="1" /&gt; &lt;/ReportControl&gt;</Private>
<Private type="Siemens-ControlBlockStorage">urcbD|&lt;ReportControl rptID="F2E801FMEAS/LLN0$RP$urcbD01" confRev="0" buffered="false" bufTime="100" name="urcbD"&gt; &lt;Private type="Siemens-PredefinedControlBlock" /&gt; &lt;TrgOps dchg="true" qchg="true" dupd="true" period="true" /&gt; &lt;OptFields seqNum="true" timeStamp="true" dataSet="true" reasonCode="true" dataRef="false" configRef="true" /&gt; &lt;RptEnabled max="1" /&gt; &lt;/ReportControl&gt;</Private>
<Private type="Siemens-ControlBlockStorage">urcbE|&lt;ReportControl rptID="F2E801FMEAS/LLN0$RP$urcbE01" confRev="0" buffered="false" bufTime="100" name="urcbE"&gt; &lt;Private type="Siemens-PredefinedControlBlock" /&gt; &lt;TrgOps dchg="true" qchg="true" dupd="true" period="true" /&gt; &lt;OptFields seqNum="true" timeStamp="true" dataSet="true" reasonCode="true" dataRef="false" configRef="true" /&gt; &lt;RptEnabled max="1" /&gt; &lt;/ReportControl&gt;</Private>
<Private type="Siemens-ControlBlockStorage">urcbF|&lt;ReportControl rptID="F2E801FMEAS/LLN0$RP$urcbF01" confRev="0" buffered="false" bufTime="100" name="urcbF"&gt; &lt;Private type="Siemens-PredefinedControlBlock" /&gt; &lt;TrgOps dchg="true" qchg="true" dupd="true" period="true" /&gt; &lt;OptFields seqNum="true" timeStamp="true" dataSet="true" reasonCode="true" dataRef="false" configRef="true" /&gt; &lt;RptEnabled max="1" /&gt; &lt;/ReportControl&gt;</Private>
<Private type="Siemens-ControlBlockStorage">urcbG|&lt;ReportControl rptID="F2E801FMEAS/LLN0$RP$urcbG01" confRev="0" buffered="false" bufTime="100" name="urcbG"&gt; &lt;Private type="Siemens-PredefinedControlBlock" /&gt; &lt;TrgOps dchg="true" qchg="true" dupd="true" period="true" /&gt; &lt;OptFields seqNum="true" timeStamp="true" dataSet="true" reasonCode="true" dataRef="false" configRef="true" /&gt; &lt;RptEnabled max="1" /&gt; &lt;/ReportControl&gt;</Private>
<Private type="Siemens-ControlBlockStorage">urcbH|&lt;ReportControl rptID="F2E801FMEAS/LLN0$RP$urcbH01" confRev="0" buffered="false" bufTime="100" name="urcbH"&gt; &lt;Private type="Siemens-PredefinedControlBlock" /&gt; &lt;TrgOps dchg="true" qchg="true" dupd="true" period="true" /&gt; &lt;OptFields seqNum="true" timeStamp="true" dataSet="true" reasonCode="true" dataRef="false" configRef="true" /&gt; &lt;RptEnabled max="1" /&gt; &lt;/ReportControl&gt;</Private>
<Private type="Siemens-ControlBlockStorage">urcbI|&lt;ReportControl rptID="F2E801FMEAS/LLN0$RP$urcbI01" confRev="0" buffered="false" bufTime="100" name="urcbI"&gt; &lt;Private type="Siemens-PredefinedControlBlock" /&gt; &lt;TrgOps dchg="true" qchg="true" dupd="true" period="true" /&gt; &lt;OptFields seqNum="true" timeStamp="true" dataSet="true" reasonCode="true" dataRef="false" configRef="true" /&gt; &lt;RptEnabled max="1" /&gt; &lt;/ReportControl&gt;</Private>
<Private type="Siemens-ControlBlockStorage">urcbJ|&lt;ReportControl rptID="F2E801FMEAS/LLN0$RP$urcbJ01" confRev="0" buffered="false" bufTime="100" name="urcbJ"&gt; &lt;Private type="Siemens-PredefinedControlBlock" /&gt; &lt;TrgOps dchg="true" qchg="true" dupd="true" period="true" /&gt; &lt;OptFields seqNum="true" timeStamp="true" dataSet="true" reasonCode="true" dataRef="false" configRef="true" /&gt; &lt;RptEnabled max="1" /&gt; &lt;/ReportControl&gt;</Private>
<Private type="Siemens-ControlBlockStorage">brcbA|&lt;ReportControl rptID="F2E801FMEAS/LLN0$BR$brcbA01" confRev="0" buffered="true" bufTime="100" name="brcbA"&gt; &lt;Private type="Siemens-PredefinedControlBlock" /&gt; &lt;TrgOps dchg="true" qchg="true" dupd="true" period="true" /&gt; &lt;OptFields seqNum="true" timeStamp="true" dataSet="true" reasonCode="true" dataRef="false" entryID="true" configRef="true" /&gt; &lt;RptEnabled max="1" /&gt; &lt;/ReportControl&gt;</Private>
<Private type="Siemens-ControlBlockStorage">brcbB|&lt;ReportControl rptID="F2E801FMEAS/LLN0$BR$brcbB01" confRev="0" buffered="true" bufTime="100" name="brcbB"&gt; &lt;Private type="Siemens-PredefinedControlBlock" /&gt; &lt;TrgOps dchg="true" qchg="true" dupd="true" period="true" /&gt; &lt;OptFields seqNum="true" timeStamp="true" dataSet="true" reasonCode="true" dataRef="false" entryID="true" configRef="true" /&gt; &lt;RptEnabled max="1" /&gt; &lt;/ReportControl&gt;</Private>
<DataSet name="dsAin">
<!--FCDA fc="MX" doName="A" ldInst="MEAS" prefix="M1_" lnClass="MMXU" lnInst="1"/>
<FCDA fc="MX" doName="A" ldInst="MEAS" prefix="M2_" lnClass="MMXU" lnInst="1"/>
<FCDA fc="MX" doName="A" ldInst="MEAS" prefix="M3_" lnClass="MMXU" lnInst="1"/>
<FCDA fc="MX" doName="A" ldInst="MEAS" prefix="M4_" lnClass="MMXU" lnInst="1"/-->
<FCDA doName="SupWh" fc="ST" ldInst="MEAS" lnClass="MMTR" lnInst="1" prefix=""/>
<FCDA doName="SupVArh" fc="ST" ldInst="MEAS" lnClass="MMTR" lnInst="1" prefix=""/>
<FCDA doName="DmdWh" fc="ST" ldInst="MEAS" lnClass="MMTR" lnInst="1" prefix=""/>
<FCDA doName="DmdVArh" fc="ST" ldInst="MEAS" lnClass="MMTR" lnInst="1" prefix=""/>
<FCDA doName="PPV" fc="MX" ldInst="MEAS" lnClass="MMXU" lnInst="2" prefix=""/>
<FCDA doName="A" fc="MX" ldInst="MEAS" lnClass="MMXU" lnInst="2" prefix=""/>
<FCDA doName="PhV" fc="MX" ldInst="MEAS" lnClass="MMXU" lnInst="2" prefix=""/>
<FCDA doName="Hz" fc="MX" ldInst="MEAS" lnClass="MMXU" lnInst="2" prefix=""/>
<FCDA doName="TotW" fc="MX" ldInst="MEAS" lnClass="MMXU" lnInst="2" prefix=""/>
<FCDA doName="TotPF" fc="MX" ldInst="MEAS" lnClass="MMXU" lnInst="2" prefix=""/>
<FCDA doName="TotVA" fc="MX" ldInst="MEAS" lnClass="MMXU" lnInst="2" prefix=""/>
<FCDA doName="TotVAr" fc="MX" ldInst="MEAS" lnClass="MMXU" lnInst="2" prefix=""/>
<FCDA doName="SeqA" fc="MX" ldInst="MEAS" lnClass="MSQI" lnInst="1" prefix=""/>
<FCDA doName="SeqV" fc="MX" ldInst="MEAS" lnClass="MSQI" lnInst="1" prefix=""/>
</DataSet>
<ReportControl bufTime="0" buffered="false" confRev="1" datSet="dsAin" name="urcbA" rptID="MEAS/LLN0$RP$urcbA">
<TrgOps dchg="true" dupd="true" period="true" qchg="true"/>
<OptFields configRef="true" dataRef="false" dataSet="true" entryID="true" reasonCode="true" seqNum="true" timeStamp="true"/>
<RptEnabled max="8"/>
</ReportControl>
<DOI desc="模式" name="Mod">
<Private type="Siemens-AlternativeDesc">Mode</Private>
<DAI name="ctlModel">
<Val>status-only</Val>
</DAI>
</DOI>
<DOI desc="性能" name="Beh">
<Private type="Siemens-AlternativeDesc">Behaviour</Private>
</DOI>
<DOI desc="健康状况" name="Health">
<Private type="Siemens-AlternativeDesc">State</Private>
</DOI>
<DOI desc="铭牌" name="NamPlt">
<Private type="Siemens-AlternativeDesc">Info</Private>
<DAI name="configRev">
<Val>160304190901000</Val>
</DAI>
<DAI name="ldNs">
<Val>IEC 61850-7-4:2003</Val>
</DAI>
</DOI>
</LN0>
<LN desc="计量" inst="1" lnClass="MMTR" lnType="F2T202IN/MEAS/MMTR1" prefix="">
<Private type="Siemens-AlternativeDesc">Energy counter</Private>
<Private type="IsNodeProcessed"/>
<Private type="Siemens-ControlBlockStorage">urcbA|&lt;ReportControl rptID="F2E801FMEAS/MMTR1$RP$urcbA01" confRev="0" buffered="false" bufTime="100" name="urcbA"&gt; &lt;Private type="Siemens-PredefinedControlBlock" /&gt; &lt;TrgOps dchg="true" qchg="true" dupd="true" period="true" /&gt; &lt;OptFields seqNum="true" timeStamp="true" dataSet="true" reasonCode="true" dataRef="false" configRef="true" /&gt; &lt;RptEnabled max="1" /&gt; &lt;/ReportControl&gt;</Private>
<Private type="Siemens-ControlBlockStorage">urcbB|&lt;ReportControl rptID="F2E801FMEAS/MMTR1$RP$urcbB01" confRev="0" buffered="false" bufTime="100" name="urcbB"&gt; &lt;Private type="Siemens-PredefinedControlBlock" /&gt; &lt;TrgOps dchg="true" qchg="true" dupd="true" period="true" /&gt; &lt;OptFields seqNum="true" timeStamp="true" dataSet="true" reasonCode="true" dataRef="false" configRef="true" /&gt; &lt;RptEnabled max="1" /&gt; &lt;/ReportControl&gt;</Private>
<DOI desc="模式" name="Mod">
<Private type="Siemens-AlternativeDesc">Mode</Private>
<DAI name="ctlModel">
<Val>status-only</Val>
</DAI>
</DOI>
<DOI desc="性能" name="Beh">
<Private type="Siemens-AlternativeDesc">Behaviour</Private>
</DOI>
<DOI desc="健康状况" name="Health">
<Private type="Siemens-AlternativeDesc">State</Private>
</DOI>
<DOI desc="铭牌" name="NamPlt">
<Private type="Siemens-AlternativeDesc">Info</Private>
<DAI name="configRev">
<Val>160304190901000</Val>
</DAI>
</DOI>
<DOI desc="正向有功Wp" name="SupWh">
<Private type="Siemens-AlternativeDesc">Wp output</Private>
<SDI name="units">
<DAI name="SIUnit"/>
</SDI>
</DOI>
<DOI desc="正向无功Wq" name="SupVArh">
<Private type="Siemens-AlternativeDesc">Wq output</Private>
<SDI name="units">
<DAI name="SIUnit"/>
</SDI>
</DOI>
<DOI desc="反向有功Wp" name="DmdWh">
<Private type="Siemens-AlternativeDesc">Wp Input</Private>
<SDI name="units">
<DAI name="SIUnit"/>
</SDI>
</DOI>
<DOI desc="反向无功Wq" name="DmdVArh">
<Private type="Siemens-AlternativeDesc">Wq Input</Private>
<SDI name="units">
<DAI name="SIUnit"/>
</SDI>
</DOI>
</LN>
<LN desc="序分量" inst="1" lnClass="MSQI" lnType="F2T202IN/MEAS/MSQI1" prefix="">
<Private type="Siemens-AlternativeDesc">Sym comp value</Private>
<Private type="IsNodeProcessed"/>
<Private type="Siemens-ControlBlockStorage">urcbA|&lt;ReportControl rptID="F2E801FMEAS/MSQI1$RP$urcbA01" confRev="0" buffered="false" bufTime="100" name="urcbA"&gt; &lt;Private type="Siemens-PredefinedControlBlock" /&gt; &lt;TrgOps dchg="true" qchg="true" dupd="true" period="true" /&gt; &lt;OptFields seqNum="true" timeStamp="true" dataSet="true" reasonCode="true" dataRef="false" configRef="true" /&gt; &lt;RptEnabled max="1" /&gt; &lt;/ReportControl&gt;</Private>
<Private type="Siemens-ControlBlockStorage">urcbB|&lt;ReportControl rptID="F2E801FMEAS/MSQI1$RP$urcbB01" confRev="0" buffered="false" bufTime="100" name="urcbB"&gt; &lt;Private type="Siemens-PredefinedControlBlock" /&gt; &lt;TrgOps dchg="true" qchg="true" dupd="true" period="true" /&gt; &lt;OptFields seqNum="true" timeStamp="true" dataSet="true" reasonCode="true" dataRef="false" configRef="true" /&gt; &lt;RptEnabled max="1" /&gt; &lt;/ReportControl&gt;</Private>
<DOI desc="模式" name="Mod">
<Private type="Siemens-AlternativeDesc">Mode</Private>
<DAI name="ctlModel">
<Val>status-only</Val>
</DAI>
</DOI>
<DOI desc="性能" name="Beh">
<Private type="Siemens-AlternativeDesc">Behaviour</Private>
</DOI>
<DOI desc="健康状况" name="Health">
<Private type="Siemens-AlternativeDesc">State</Private>
</DOI>
<DOI desc="铭牌" name="NamPlt">
<Private type="Siemens-AlternativeDesc">Info</Private>
<DAI name="configRev">
<Val>160304190901000</Val>
</DAI>
</DOI>
<DOI desc="电流" name="SeqA">
<Private type="Siemens-AlternativeDesc">Current</Private>
<SDI name="c1">
<SDI name="units">
<DAI name="SIUnit"/>
</SDI>
<DAI name="db">
<Val>10000</Val>
</DAI>
</SDI>
<SDI name="c2">
<SDI name="units">
<DAI name="SIUnit"/>
</SDI>
<DAI name="db">
<Val>10000</Val>
</DAI>
</SDI>
<SDI name="c3">
<SDI name="units">
<DAI name="SIUnit"/>
</SDI>
<DAI name="db">
<Val>10000</Val>
</DAI>
</SDI>
<DAI name="seqT">
<Val>pos-neg-zero</Val>
</DAI>
</DOI>
<DOI desc="电压" name="SeqV">
<Private type="Siemens-AlternativeDesc">Voltage</Private>
<SDI name="c1">
<SDI name="units">
<DAI name="SIUnit"/>
</SDI>
<DAI name="db">
<Val>10000</Val>
</DAI>
</SDI>
<SDI name="c2">
<SDI name="units">
<DAI name="SIUnit"/>
</SDI>
<DAI name="db">
<Val>10000</Val>
</DAI>
</SDI>
<SDI name="c3">
<SDI name="units">
<DAI name="SIUnit"/>
</SDI>
<DAI name="db">
<Val>10000</Val>
</DAI>
</SDI>
<DAI name="seqT">
<Val>pos-neg-zero</Val>
</DAI>
</DOI>
</LN>
<LN desc="设备" inst="1" lnClass="LPHD" lnType="F2T202IN/PROT/LPHD1" prefix="">
<Private type="Siemens-AlternativeDesc">Device</Private>
<Private type="IsNodeProcessed"/>
<Private type="Siemens-ControlBlockStorage">urcbA|&lt;ReportControl rptID="F2E801FMEAS/LPHD1$RP$urcbA01" confRev="0" buffered="false" bufTime="100" name="urcbA"&gt; &lt;Private type="Siemens-PredefinedControlBlock" /&gt; &lt;TrgOps dchg="true" qchg="true" dupd="true" period="true" /&gt; &lt;OptFields seqNum="true" timeStamp="true" dataSet="true" reasonCode="true" dataRef="false" configRef="true" /&gt; &lt;RptEnabled max="1" /&gt; &lt;/ReportControl&gt;</Private>
<Private type="Siemens-ControlBlockStorage">urcbB|&lt;ReportControl rptID="F2E801FMEAS/LPHD1$RP$urcbB01" confRev="0" buffered="false" bufTime="100" name="urcbB"&gt; &lt;Private type="Siemens-PredefinedControlBlock" /&gt; &lt;TrgOps dchg="true" qchg="true" dupd="true" period="true" /&gt; &lt;OptFields seqNum="true" timeStamp="true" dataSet="true" reasonCode="true" dataRef="false" configRef="true" /&gt; &lt;RptEnabled max="1" /&gt; &lt;/ReportControl&gt;</Private>
<DOI desc="物理装置铭牌" name="PhyNam">
<Private type="Siemens-AlternativeDesc">Info</Private>
</DOI>
<DOI desc="物理装置健康状况" name="PhyHealth">
<Private type="Siemens-AlternativeDesc">State</Private>
</DOI>
<DOI desc="代理" name="Proxy">
<Private type="Siemens-AlternativeDesc">Proxy</Private>
</DOI>
</LN>
<LN desc="测量值" inst="2" lnClass="MMXU" lnType="F2T202IN/MEAS/MMXU2" prefix="">
<Private type="Siemens-AlternativeDesc">Mea.Value (MCT)</Private>
<Private type="IsNodeProcessed"/>
<Private type="Siemens-ControlBlockStorage">urcbA|&lt;ReportControl rptID="F2E801FMEAS/MMXU2$RP$urcbA01" confRev="0" buffered="false" bufTime="100" name="urcbA"&gt; &lt;Private type="Siemens-PredefinedControlBlock" /&gt; &lt;TrgOps dchg="true" qchg="true" dupd="true" period="true" /&gt; &lt;OptFields seqNum="true" timeStamp="true" dataSet="true" reasonCode="true" dataRef="false" configRef="true" /&gt; &lt;RptEnabled max="1" /&gt; &lt;/ReportControl&gt;</Private>
<Private type="Siemens-ControlBlockStorage">urcbB|&lt;ReportControl rptID="F2E801FMEAS/MMXU2$RP$urcbB01" confRev="0" buffered="false" bufTime="100" name="urcbB"&gt; &lt;Private type="Siemens-PredefinedControlBlock" /&gt; &lt;TrgOps dchg="true" qchg="true" dupd="true" period="true" /&gt; &lt;OptFields seqNum="true" timeStamp="true" dataSet="true" reasonCode="true" dataRef="false" configRef="true" /&gt; &lt;RptEnabled max="1" /&gt; &lt;/ReportControl&gt;</Private>
<DOI desc="模式" name="Mod">
<Private type="Siemens-AlternativeDesc">Mode</Private>
<DAI name="ctlModel">
<Val>status-only</Val>
</DAI>
</DOI>
<DOI desc="性能" name="Beh">
<Private type="Siemens-AlternativeDesc">Behaviour</Private>
</DOI>
<DOI desc="健康状况" name="Health">
<Private type="Siemens-AlternativeDesc">State</Private>
</DOI>
<DOI desc="铭牌" name="NamPlt">
<Private type="Siemens-AlternativeDesc">Info</Private>
<DAI name="configRev">
<Val>160304190901000</Val>
</DAI>
</DOI>
<DOI desc="总有功功率" name="TotW">
<Private type="Siemens-AlternativeDesc">P</Private>
<SDI name="units">
<DAI name="SIUnit"/>
</SDI>
<DAI name="db">
<Val>10000</Val>
</DAI>
</DOI>
<DOI desc="总无功功率" name="TotVAr">
<Private type="Siemens-AlternativeDesc">Q</Private>
<SDI name="units">
<DAI name="SIUnit"/>
</SDI>
<DAI name="db">
<Val>10000</Val>
</DAI>
</DOI>
<DOI desc="总视在功率" name="TotVA">
<Private type="Siemens-AlternativeDesc">S</Private>
<SDI name="units">
<DAI name="SIUnit"/>
</SDI>
<DAI name="db">
<Val>10000</Val>
</DAI>
</DOI>
<DOI desc="平均功率因数" name="TotPF">
<Private type="Siemens-AlternativeDesc">cos</Private>
<SDI name="units">
<DAI name="SIUnit"/>
</SDI>
<DAI name="db">
<Val>10000</Val>
</DAI>
</DOI>
<DOI desc="频率" name="Hz">
<Private type="Siemens-AlternativeDesc">f</Private>
<SDI name="units">
<DAI name="SIUnit"/>
</SDI>
<DAI name="db">
<Val>100</Val>
</DAI>
</DOI>
<DOI desc="线电压" name="PPV">
<Private type="Siemens-AlternativeDesc">U</Private>
<SDI name="phsAB">
<SDI name="units">
<DAI name="SIUnit"/>
</SDI>
<DAI name="db">
<Val>2000</Val>
</DAI>
</SDI>
<SDI name="phsBC">
<SDI name="units">
<DAI name="SIUnit"/>
</SDI>
<DAI name="db">
<Val>2000</Val>
</DAI>
</SDI>
<SDI name="phsCA">
<SDI name="units">
<DAI name="SIUnit"/>
</SDI>
<DAI name="db">
<Val>2000</Val>
</DAI>
</SDI>
</DOI>
<DOI desc="相电压" name="PhV">
<Private type="Siemens-AlternativeDesc">UE</Private>
<SDI name="phsA">
<SDI name="units">
<DAI name="SIUnit"/>
</SDI>
<DAI name="db">
<Val>2000</Val>
</DAI>
</SDI>
<SDI name="phsB">
<SDI name="units">
<DAI name="SIUnit"/>
</SDI>
<DAI name="db">
<Val>2000</Val>
</DAI>
</SDI>
<SDI name="phsC">
<SDI name="units">
<DAI name="SIUnit"/>
</SDI>
<DAI name="db">
<Val>2000</Val>
</DAI>
</SDI>
<SDI name="neut">
<SDI name="units">
<DAI name="SIUnit"/>
</SDI>
<DAI name="db">
<Val>2000</Val>
</DAI>
</SDI>
</DOI>
<DOI desc="电流" name="A">
<Private type="Siemens-AlternativeDesc">I</Private>
<SDI name="phsA">
<SDI name="units">
<DAI name="SIUnit"/>
</SDI>
<DAI name="db">
<Val>10000</Val>
</DAI>
</SDI>
<SDI name="phsB">
<SDI name="units">
<DAI name="SIUnit"/>
</SDI>
<DAI name="db">
<Val>10000</Val>
</DAI>
</SDI>
<SDI name="phsC">
<SDI name="units">
<DAI name="SIUnit"/>
</SDI>
<DAI name="db">
<Val>10000</Val>
</DAI>
</SDI>
<SDI name="neut">
<SDI name="units">
<DAI name="SIUnit"/>
</SDI>
<DAI name="db">
<Val>10000</Val>
</DAI>
</SDI>
</DOI>
</LN>
<LN desc="测量值" inst="1" lnClass="MMXN" lnType="F2T202IN/MEAS/MMXN1" prefix="">
<Private type="Siemens-AlternativeDesc">OperatingMV</Private>
<Private type="IsNodeProcessed"/>
<Private type="Siemens-ControlBlockStorage">urcbA|&lt;ReportControl rptID="F2E801FMEAS/MMXN1$RP$urcbA01" confRev="0" buffered="false" bufTime="100" name="urcbA"&gt; &lt;Private type="Siemens-PredefinedControlBlock" /&gt; &lt;TrgOps dchg="true" qchg="true" dupd="true" period="true" /&gt; &lt;OptFields seqNum="true" timeStamp="true" dataSet="true" reasonCode="true" dataRef="false" configRef="true" /&gt; &lt;RptEnabled max="1" /&gt; &lt;/ReportControl&gt;</Private>
<Private type="Siemens-ControlBlockStorage">urcbB|&lt;ReportControl rptID="F2E801FMEAS/MMXN1$RP$urcbB01" confRev="0" buffered="false" bufTime="100" name="urcbB"&gt; &lt;Private type="Siemens-PredefinedControlBlock" /&gt; &lt;TrgOps dchg="true" qchg="true" dupd="true" period="true" /&gt; &lt;OptFields seqNum="true" timeStamp="true" dataSet="true" reasonCode="true" dataRef="false" configRef="true" /&gt; &lt;RptEnabled max="1" /&gt; &lt;/ReportControl&gt;</Private>
<DOI desc="模式" name="Mod">
<Private type="Siemens-AlternativeDesc">Mode</Private>
<DAI name="ctlModel">
<Val>status-only</Val>
</DAI>
</DOI>
<DOI desc="性能" name="Beh">
<Private type="Siemens-AlternativeDesc">Behaviour</Private>
</DOI>
<DOI desc="健康状况" name="Health">
<Private type="Siemens-AlternativeDesc">State</Private>
</DOI>
<DOI desc="铭牌" name="NamPlt">
<Private type="Siemens-AlternativeDesc">Info</Private>
<DAI name="configRev">
<Val>160304190901000</Val>
</DAI>
</DOI>
<DOI desc="有功功率 (1ph)" name="Watt">
<Private type="Siemens-AlternativeDesc">P (1ph)</Private>
<SDI name="units">
<DAI name="SIUnit"/>
</SDI>
<DAI name="db">
<Val>10000</Val>
</DAI>
</DOI>
<DOI desc="无功功率 (1ph)" name="VolAmpr">
<Private type="Siemens-AlternativeDesc">Q (1ph)</Private>
<SDI name="units">
<DAI name="SIUnit"/>
</SDI>
<DAI name="db">
<Val>10000</Val>
</DAI>
</DOI>
<DOI desc="功率因数 (1ph)" name="PwrFact">
<Private type="Siemens-AlternativeDesc">cos (1ph)</Private>
<SDI name="units">
<DAI name="SIUnit"/>
</SDI>
<DAI name="db">
<Val>10000</Val>
</DAI>
</DOI>
<DOI desc="频率" name="Hz">
<Private type="Siemens-AlternativeDesc">f</Private>
<SDI name="units">
<DAI name="SIUnit"/>
</SDI>
<DAI name="db">
<Val>100</Val>
</DAI>
</DOI>
</LN>
</LDevice>
<LDevice desc="录波" inst="DR">
<Private type="Siemens-AlternativeDesc">Disturb Rec</Private>
<Private type="IsNodeProcessed"/>
<LN0 desc="公用" inst="" lnClass="LLN0" lnType="F2T202IN/MEAS/LLN0">
<Private type="Siemens-AlternativeDesc">General</Private>
<Private type="Siemens-ControlBlockStorage">urcbA|&lt;ReportControl rptID="F2E801FDR/LLN0$RP$urcbA01" confRev="0" buffered="false" bufTime="100" name="urcbA"&gt; &lt;Private type="Siemens-PredefinedControlBlock" /&gt; &lt;TrgOps dchg="true" qchg="true" dupd="true" period="true" /&gt; &lt;OptFields seqNum="true" timeStamp="true" dataSet="true" reasonCode="true" dataRef="false" configRef="true" /&gt; &lt;RptEnabled max="1" /&gt; &lt;/ReportControl&gt;</Private>
<Private type="Siemens-ControlBlockStorage">urcbB|&lt;ReportControl rptID="F2E801FDR/LLN0$RP$urcbB01" confRev="0" buffered="false" bufTime="100" name="urcbB"&gt; &lt;Private type="Siemens-PredefinedControlBlock" /&gt; &lt;TrgOps dchg="true" qchg="true" dupd="true" period="true" /&gt; &lt;OptFields seqNum="true" timeStamp="true" dataSet="true" reasonCode="true" dataRef="false" configRef="true" /&gt; &lt;RptEnabled max="1" /&gt; &lt;/ReportControl&gt;</Private>
<Private type="Siemens-ControlBlockStorage">urcbC|&lt;ReportControl rptID="F2E801FDR/LLN0$RP$urcbC01" confRev="0" buffered="false" bufTime="100" name="urcbC"&gt; &lt;Private type="Siemens-PredefinedControlBlock" /&gt; &lt;TrgOps dchg="true" qchg="true" dupd="true" period="true" /&gt; &lt;OptFields seqNum="true" timeStamp="true" dataSet="true" reasonCode="true" dataRef="false" configRef="true" /&gt; &lt;RptEnabled max="1" /&gt; &lt;/ReportControl&gt;</Private>
<Private type="Siemens-ControlBlockStorage">urcbD|&lt;ReportControl rptID="F2E801FDR/LLN0$RP$urcbD01" confRev="0" buffered="false" bufTime="100" name="urcbD"&gt; &lt;Private type="Siemens-PredefinedControlBlock" /&gt; &lt;TrgOps dchg="true" qchg="true" dupd="true" period="true" /&gt; &lt;OptFields seqNum="true" timeStamp="true" dataSet="true" reasonCode="true" dataRef="false" configRef="true" /&gt; &lt;RptEnabled max="1" /&gt; &lt;/ReportControl&gt;</Private>
<Private type="Siemens-ControlBlockStorage">urcbE|&lt;ReportControl rptID="F2E801FDR/LLN0$RP$urcbE01" confRev="0" buffered="false" bufTime="100" name="urcbE"&gt; &lt;Private type="Siemens-PredefinedControlBlock" /&gt; &lt;TrgOps dchg="true" qchg="true" dupd="true" period="true" /&gt; &lt;OptFields seqNum="true" timeStamp="true" dataSet="true" reasonCode="true" dataRef="false" configRef="true" /&gt; &lt;RptEnabled max="1" /&gt; &lt;/ReportControl&gt;</Private>
<Private type="Siemens-ControlBlockStorage">urcbF|&lt;ReportControl rptID="F2E801FDR/LLN0$RP$urcbF01" confRev="0" buffered="false" bufTime="100" name="urcbF"&gt; &lt;Private type="Siemens-PredefinedControlBlock" /&gt; &lt;TrgOps dchg="true" qchg="true" dupd="true" period="true" /&gt; &lt;OptFields seqNum="true" timeStamp="true" dataSet="true" reasonCode="true" dataRef="false" configRef="true" /&gt; &lt;RptEnabled max="1" /&gt; &lt;/ReportControl&gt;</Private>
<Private type="Siemens-ControlBlockStorage">urcbG|&lt;ReportControl rptID="F2E801FDR/LLN0$RP$urcbG01" confRev="0" buffered="false" bufTime="100" name="urcbG"&gt; &lt;Private type="Siemens-PredefinedControlBlock" /&gt; &lt;TrgOps dchg="true" qchg="true" dupd="true" period="true" /&gt; &lt;OptFields seqNum="true" timeStamp="true" dataSet="true" reasonCode="true" dataRef="false" configRef="true" /&gt; &lt;RptEnabled max="1" /&gt; &lt;/ReportControl&gt;</Private>
<Private type="Siemens-ControlBlockStorage">urcbH|&lt;ReportControl rptID="F2E801FDR/LLN0$RP$urcbH01" confRev="0" buffered="false" bufTime="100" name="urcbH"&gt; &lt;Private type="Siemens-PredefinedControlBlock" /&gt; &lt;TrgOps dchg="true" qchg="true" dupd="true" period="true" /&gt; &lt;OptFields seqNum="true" timeStamp="true" dataSet="true" reasonCode="true" dataRef="false" configRef="true" /&gt; &lt;RptEnabled max="1" /&gt; &lt;/ReportControl&gt;</Private>
<Private type="Siemens-ControlBlockStorage">urcbI|&lt;ReportControl rptID="F2E801FDR/LLN0$RP$urcbI01" confRev="0" buffered="false" bufTime="100" name="urcbI"&gt; &lt;Private type="Siemens-PredefinedControlBlock" /&gt; &lt;TrgOps dchg="true" qchg="true" dupd="true" period="true" /&gt; &lt;OptFields seqNum="true" timeStamp="true" dataSet="true" reasonCode="true" dataRef="false" configRef="true" /&gt; &lt;RptEnabled max="1" /&gt; &lt;/ReportControl&gt;</Private>
<Private type="Siemens-ControlBlockStorage">urcbJ|&lt;ReportControl rptID="F2E801FDR/LLN0$RP$urcbJ01" confRev="0" buffered="false" bufTime="100" name="urcbJ"&gt; &lt;Private type="Siemens-PredefinedControlBlock" /&gt; &lt;TrgOps dchg="true" qchg="true" dupd="true" period="true" /&gt; &lt;OptFields seqNum="true" timeStamp="true" dataSet="true" reasonCode="true" dataRef="false" configRef="true" /&gt; &lt;RptEnabled max="1" /&gt; &lt;/ReportControl&gt;</Private>
<Private type="Siemens-ControlBlockStorage">brcbB|&lt;ReportControl rptID="F2E801FDR/LLN0$BR$brcbB01" confRev="0" buffered="true" bufTime="100" name="brcbB"&gt; &lt;Private type="Siemens-PredefinedControlBlock" /&gt; &lt;TrgOps dchg="true" qchg="true" dupd="true" period="true" /&gt; &lt;OptFields seqNum="true" timeStamp="true" dataSet="true" reasonCode="true" dataRef="false" entryID="true" configRef="true" /&gt; &lt;RptEnabled max="1" /&gt; &lt;/ReportControl&gt;</Private>
<DataSet name="dsRelayRec">
<FCDA doName="FltNum" fc="ST" ldInst="DR" lnClass="RDRE" lnInst="1" prefix="SC_"/>
<FCDA doName="RcdMade" fc="ST" ldInst="DR" lnClass="RDRE" lnInst="1" prefix="SC_"/>
<FCDA doName="RcdStr" fc="ST" ldInst="DR" lnClass="RDRE" lnInst="1" prefix="SC_"/>
<FCDA doName="GriFltNum" fc="ST" ldInst="DR" lnClass="RDRE" lnInst="1" prefix="SC_"/>
</DataSet>
<ReportControl bufTime="100" buffered="true" confRev="1" datSet="dsRelayRec" name="brcbA" rptID="DR/LLN0$BR$brcbA">
<TrgOps dchg="true" dupd="true" period="true" qchg="true"/>
<OptFields configRef="true" dataRef="false" dataSet="true" entryID="true" reasonCode="true" seqNum="true" timeStamp="true"/>
<RptEnabled max="8"/>
</ReportControl>
<DOI desc="模式" name="Mod">
<Private type="Siemens-AlternativeDesc">Mode</Private>
<DAI name="ctlModel">
<Val>status-only</Val>
</DAI>
</DOI>
<DOI desc="性能" name="Beh">
<Private type="Siemens-AlternativeDesc">Behaviour</Private>
</DOI>
<DOI desc="健康状况" name="Health">
<Private type="Siemens-AlternativeDesc">State</Private>
</DOI>
<DOI desc="铭牌" name="NamPlt">
<Private type="Siemens-AlternativeDesc">Info</Private>
<DAI name="configRev">
<Val>160304190901000</Val>
</DAI>
<DAI name="ldNs">
<Val>IEC 61850-7-4:2003</Val>
</DAI>
</DOI>
</LN0>
<LN desc="故障录波" inst="1" lnClass="RDRE" lnType="F2T202IN/DR/SC_RDRE1" prefix="SC_">
<Private type="Siemens-AlternativeDesc">Recording</Private>
<Private type="IsNodeProcessed"/>
<Private type="Siemens-ControlBlockStorage">urcbA|&lt;ReportControl rptID="F2E801FDR/SC_RDRE1$RP$urcbA01" confRev="0" buffered="false" bufTime="100" name="urcbA"&gt; &lt;Private type="Siemens-PredefinedControlBlock" /&gt; &lt;TrgOps dchg="true" qchg="true" dupd="true" period="true" /&gt; &lt;OptFields seqNum="true" timeStamp="true" dataSet="true" reasonCode="true" dataRef="false" configRef="true" /&gt; &lt;RptEnabled max="1" /&gt; &lt;/ReportControl&gt;</Private>
<Private type="Siemens-ControlBlockStorage">urcbB|&lt;ReportControl rptID="F2E801FDR/SC_RDRE1$RP$urcbB01" confRev="0" buffered="false" bufTime="100" name="urcbB"&gt; &lt;Private type="Siemens-PredefinedControlBlock" /&gt; &lt;TrgOps dchg="true" qchg="true" dupd="true" period="true" /&gt; &lt;OptFields seqNum="true" timeStamp="true" dataSet="true" reasonCode="true" dataRef="false" configRef="true" /&gt; &lt;RptEnabled max="1" /&gt; &lt;/ReportControl&gt;</Private>
<DOI desc="模式" name="Mod">
<Private type="Siemens-AlternativeDesc">Mode</Private>
<DAI name="ctlModel">
<Val>status-only</Val>
</DAI>
</DOI>
<DOI desc="性能" name="Beh">
<Private type="Siemens-AlternativeDesc">Behaviour</Private>
</DOI>
<DOI desc="健康状况" name="Health">
<Private type="Siemens-AlternativeDesc">State</Private>
</DOI>
<DOI desc="铭牌" name="NamPlt">
<Private type="Siemens-AlternativeDesc">Info</Private>
<DAI name="configRev">
<Val>160304190901000</Val>
</DAI>
</DOI>
<DOI desc="在记录" name="RcdMade">
<Private type="Siemens-AlternativeDesc">Made</Private>
</DOI>
<DOI desc="故障序号" name="FltNum">
<Private type="Siemens-AlternativeDesc">Fault number</Private>
</DOI>
<DOI desc="电网故障序号" name="GriFltNum">
<Private type="Siemens-AlternativeDesc">Grid fault num</Private>
</DOI>
<DOI desc="记录启动" name="RcdStr">
<Private type="Siemens-AlternativeDesc">Start</Private>
</DOI>
</LN>
<LN desc="设备" inst="1" lnClass="LPHD" lnType="F2T202IN/PROT/LPHD1" prefix="">
<Private type="Siemens-AlternativeDesc">Device</Private>
<Private type="IsNodeProcessed"/>
<Private type="Siemens-ControlBlockStorage">urcbA|&lt;ReportControl rptID="F2E801FDR/LPHD1$RP$urcbA01" confRev="0" buffered="false" bufTime="100" name="urcbA"&gt; &lt;Private type="Siemens-PredefinedControlBlock" /&gt; &lt;TrgOps dchg="true" qchg="true" dupd="true" period="true" /&gt; &lt;OptFields seqNum="true" timeStamp="true" dataSet="true" reasonCode="true" dataRef="false" configRef="true" /&gt; &lt;RptEnabled max="1" /&gt; &lt;/ReportControl&gt;</Private>
<Private type="Siemens-ControlBlockStorage">urcbB|&lt;ReportControl rptID="F2E801FDR/LPHD1$RP$urcbB01" confRev="0" buffered="false" bufTime="100" name="urcbB"&gt; &lt;Private type="Siemens-PredefinedControlBlock" /&gt; &lt;TrgOps dchg="true" qchg="true" dupd="true" period="true" /&gt; &lt;OptFields seqNum="true" timeStamp="true" dataSet="true" reasonCode="true" dataRef="false" configRef="true" /&gt; &lt;RptEnabled max="1" /&gt; &lt;/ReportControl&gt;</Private>
<DOI desc="物理装置铭牌" name="PhyNam">
<Private type="Siemens-AlternativeDesc">Info</Private>
</DOI>
<DOI desc="物理装置健康状况" name="PhyHealth">
<Private type="Siemens-AlternativeDesc">State</Private>
</DOI>
<DOI desc="代理" name="Proxy">
<Private type="Siemens-AlternativeDesc">Proxy</Private>
</DOI>
</LN>
</LDevice>
<LDevice desc="控制" inst="CTRL">
<Private type="Siemens-AlternativeDesc">Control</Private>
<Private type="IsNodeProcessed"/>
<LN0 desc="公用" inst="" lnClass="LLN0" lnType="F2T202IN/CTRL/LLN0">
<Private type="Siemens-AlternativeDesc">General</Private>
<Private type="Siemens-ControlBlockStorage">urcbA|&lt;ReportControl rptID="F2E801FCTRL/LLN0$RP$urcbA01" confRev="0" buffered="false" bufTime="100" name="urcbA"&gt; &lt;Private type="Siemens-PredefinedControlBlock" /&gt; &lt;TrgOps dchg="true" qchg="true" dupd="true" period="true" /&gt; &lt;OptFields seqNum="true" timeStamp="true" dataSet="true" reasonCode="true" dataRef="false" configRef="true" /&gt; &lt;RptEnabled max="1" /&gt; &lt;/ReportControl&gt;</Private>
<Private type="Siemens-ControlBlockStorage">urcbB|&lt;ReportControl rptID="F2E801FCTRL/LLN0$RP$urcbB01" confRev="0" buffered="false" bufTime="100" name="urcbB"&gt; &lt;Private type="Siemens-PredefinedControlBlock" /&gt; &lt;TrgOps dchg="true" qchg="true" dupd="true" period="true" /&gt; &lt;OptFields seqNum="true" timeStamp="true" dataSet="true" reasonCode="true" dataRef="false" configRef="true" /&gt; &lt;RptEnabled max="1" /&gt; &lt;/ReportControl&gt;</Private>
<Private type="Siemens-ControlBlockStorage">urcbC|&lt;ReportControl rptID="F2E801FCTRL/LLN0$RP$urcbC01" confRev="0" buffered="false" bufTime="100" name="urcbC"&gt; &lt;Private type="Siemens-PredefinedControlBlock" /&gt; &lt;TrgOps dchg="true" qchg="true" dupd="true" period="true" /&gt; &lt;OptFields seqNum="true" timeStamp="true" dataSet="true" reasonCode="true" dataRef="false" configRef="true" /&gt; &lt;RptEnabled max="1" /&gt; &lt;/ReportControl&gt;</Private>
<Private type="Siemens-ControlBlockStorage">urcbD|&lt;ReportControl rptID="F2E801FCTRL/LLN0$RP$urcbD01" confRev="0" buffered="false" bufTime="100" name="urcbD"&gt; &lt;Private type="Siemens-PredefinedControlBlock" /&gt; &lt;TrgOps dchg="true" qchg="true" dupd="true" period="true" /&gt; &lt;OptFields seqNum="true" timeStamp="true" dataSet="true" reasonCode="true" dataRef="false" configRef="true" /&gt; &lt;RptEnabled max="1" /&gt; &lt;/ReportControl&gt;</Private>
<Private type="Siemens-ControlBlockStorage">urcbE|&lt;ReportControl rptID="F2E801FCTRL/LLN0$RP$urcbE01" confRev="0" buffered="false" bufTime="100" name="urcbE"&gt; &lt;Private type="Siemens-PredefinedControlBlock" /&gt; &lt;TrgOps dchg="true" qchg="true" dupd="true" period="true" /&gt; &lt;OptFields seqNum="true" timeStamp="true" dataSet="true" reasonCode="true" dataRef="false" configRef="true" /&gt; &lt;RptEnabled max="1" /&gt; &lt;/ReportControl&gt;</Private>
<Private type="Siemens-ControlBlockStorage">urcbF|&lt;ReportControl rptID="F2E801FCTRL/LLN0$RP$urcbF01" confRev="0" buffered="false" bufTime="100" name="urcbF"&gt; &lt;Private type="Siemens-PredefinedControlBlock" /&gt; &lt;TrgOps dchg="true" qchg="true" dupd="true" period="true" /&gt; &lt;OptFields seqNum="true" timeStamp="true" dataSet="true" reasonCode="true" dataRef="false" configRef="true" /&gt; &lt;RptEnabled max="1" /&gt; &lt;/ReportControl&gt;</Private>
<Private type="Siemens-ControlBlockStorage">urcbG|&lt;ReportControl rptID="F2E801FCTRL/LLN0$RP$urcbG01" confRev="0" buffered="false" bufTime="100" name="urcbG"&gt; &lt;Private type="Siemens-PredefinedControlBlock" /&gt; &lt;TrgOps dchg="true" qchg="true" dupd="true" period="true" /&gt; &lt;OptFields seqNum="true" timeStamp="true" dataSet="true" reasonCode="true" dataRef="false" configRef="true" /&gt; &lt;RptEnabled max="1" /&gt; &lt;/ReportControl&gt;</Private>
<Private type="Siemens-ControlBlockStorage">urcbH|&lt;ReportControl rptID="F2E801FCTRL/LLN0$RP$urcbH01" confRev="0" buffered="false" bufTime="100" name="urcbH"&gt; &lt;Private type="Siemens-PredefinedControlBlock" /&gt; &lt;TrgOps dchg="true" qchg="true" dupd="true" period="true" /&gt; &lt;OptFields seqNum="true" timeStamp="true" dataSet="true" reasonCode="true" dataRef="false" configRef="true" /&gt; &lt;RptEnabled max="1" /&gt; &lt;/ReportControl&gt;</Private>
<Private type="Siemens-ControlBlockStorage">urcbI|&lt;ReportControl rptID="F2E801FCTRL/LLN0$RP$urcbI01" confRev="0" buffered="false" bufTime="100" name="urcbI"&gt; &lt;Private type="Siemens-PredefinedControlBlock" /&gt; &lt;TrgOps dchg="true" qchg="true" dupd="true" period="true" /&gt; &lt;OptFields seqNum="true" timeStamp="true" dataSet="true" reasonCode="true" dataRef="false" configRef="true" /&gt; &lt;RptEnabled max="1" /&gt; &lt;/ReportControl&gt;</Private>
<Private type="Siemens-ControlBlockStorage">urcbJ|&lt;ReportControl rptID="F2E801FCTRL/LLN0$RP$urcbJ01" confRev="0" buffered="false" bufTime="100" name="urcbJ"&gt; &lt;Private type="Siemens-PredefinedControlBlock" /&gt; &lt;TrgOps dchg="true" qchg="true" dupd="true" period="true" /&gt; &lt;OptFields seqNum="true" timeStamp="true" dataSet="true" reasonCode="true" dataRef="false" configRef="true" /&gt; &lt;RptEnabled max="1" /&gt; &lt;/ReportControl&gt;</Private>
<DataSet name="dsRelayDin">
<!--FCDA fc="ST" doName="VInd" ldInst="CTRL" prefix="" lnClass="RSYN" lnInst="1"/>
<FCDA fc="ST" doName="AngInd" ldInst="CTRL" prefix="" lnClass="RSYN" lnInst="1"/>
<FCDA fc="ST" doName="HzInd" ldInst="CTRL" prefix="" lnClass="RSYN" lnInst="1"/>
<FCDA fc="ST" doName="SynPrg" ldInst="CTRL" prefix="" lnClass="RSYN" lnInst="1"/>
<FCDA fc="ST" doName="Rel" ldInst="CTRL" prefix="" lnClass="RSYN" lnInst="1"/>
<FCDA fc="ST" doName="VInd" ldInst="CTRL" prefix="" lnClass="RSYN" lnInst="2"/>
<FCDA fc="ST" doName="AngInd" ldInst="CTRL" prefix="" lnClass="RSYN" lnInst="2"/>
<FCDA fc="ST" doName="HzInd" ldInst="CTRL" prefix="" lnClass="RSYN" lnInst="2"/>
<FCDA fc="ST" doName="SynPrg" ldInst="CTRL" prefix="" lnClass="RSYN" lnInst="2"/>
<FCDA fc="ST" doName="Rel" ldInst="CTRL" prefix="" lnClass="RSYN" lnInst="2"/-->
<FCDA doName="Pos" fc="ST" ldInst="CTRL" lnClass="CSWI" lnInst="1" prefix="Q0"/>
<FCDA doName="Pos" fc="ST" ldInst="CTRL" lnClass="CSWI" lnInst="1" prefix="Q1"/>
<FCDA doName="Pos" fc="ST" ldInst="CTRL" lnClass="CSWI" lnInst="1" prefix="Q8"/>
<FCDA doName="SPCSO1" fc="ST" ldInst="CTRL" lnClass="GGIO" lnInst="1" prefix="BI"/>
<FCDA doName="SPCSO2" fc="ST" ldInst="CTRL" lnClass="GGIO" lnInst="1" prefix="BI"/>
<FCDA doName="SPCSO3" fc="ST" ldInst="CTRL" lnClass="GGIO" lnInst="1" prefix="BI"/>
<FCDA doName="SPCSO4" fc="ST" ldInst="CTRL" lnClass="GGIO" lnInst="1" prefix="BI"/>
<FCDA doName="SPCSO5" fc="ST" ldInst="CTRL" lnClass="GGIO" lnInst="1" prefix="BI"/>
<FCDA doName="SPCSO6" fc="ST" ldInst="CTRL" lnClass="GGIO" lnInst="1" prefix="BI"/>
<FCDA doName="SPCSO7" fc="ST" ldInst="CTRL" lnClass="GGIO" lnInst="1" prefix="BI"/>
<FCDA doName="SPCSO8" fc="ST" ldInst="CTRL" lnClass="GGIO" lnInst="1" prefix="BI"/>
<FCDA doName="SPCSO9" fc="ST" ldInst="CTRL" lnClass="GGIO" lnInst="1" prefix="BI"/>
<FCDA doName="SPCSO10" fc="ST" ldInst="CTRL" lnClass="GGIO" lnInst="1" prefix="BI"/>
<FCDA doName="SPCSO11" fc="ST" ldInst="CTRL" lnClass="GGIO" lnInst="1" prefix="BI"/>
<FCDA doName="SPCSO12" fc="ST" ldInst="CTRL" lnClass="GGIO" lnInst="1" prefix="BI"/>
<FCDA doName="SPCSO13" fc="ST" ldInst="CTRL" lnClass="GGIO" lnInst="1" prefix="BI"/>
<FCDA doName="SPCSO14" fc="ST" ldInst="CTRL" lnClass="GGIO" lnInst="1" prefix="BI"/>
<FCDA doName="SPCSO15" fc="ST" ldInst="CTRL" lnClass="GGIO" lnInst="1" prefix="BI"/>
<FCDA doName="SPCSO16" fc="ST" ldInst="CTRL" lnClass="GGIO" lnInst="1" prefix="BI"/>
</DataSet>
<DataSet name="dsRelayEna">
<FCDA doName="PhOCEna" fc="ST" ldInst="PROT" lnClass="LLN0" prefix=""/>
<FCDA doName="ZerOCEna" fc="ST" ldInst="PROT" lnClass="LLN0" prefix=""/>
</DataSet>
<ReportControl bufTime="100" buffered="true" confRev="10001" datSet="dsRelayDin" name="brcbA" rptID="CTRL/LLN0$BR$brcbA">
<TrgOps dchg="true" dupd="true" period="true" qchg="true"/>
<OptFields configRef="true" dataRef="false" dataSet="true" entryID="true" reasonCode="true" seqNum="true" timeStamp="true"/>
<RptEnabled max="8"/>
</ReportControl>
<ReportControl bufTime="100" buffered="true" confRev="1" datSet="dsRelayEna" name="brcbB" rptID="CTRL/LLN0$BR$brcbB">
<TrgOps dchg="true" dupd="true" period="true" qchg="true"/>
<OptFields configRef="true" dataRef="false" dataSet="true" entryID="true" reasonCode="true" seqNum="true" timeStamp="true"/>
<RptEnabled max="8"/>
</ReportControl>
<DOI desc="模式" name="Mod">
<Private type="Siemens-AlternativeDesc">Mode</Private>
<DAI name="ctlModel">
<Val>status-only</Val>
</DAI>
</DOI>
<DOI desc="性能" name="Beh">
<Private type="Siemens-AlternativeDesc">Behaviour</Private>
</DOI>
<DOI desc="健康状况" name="Health">
<Private type="Siemens-AlternativeDesc">State</Private>
</DOI>
<DOI desc="铭牌" name="NamPlt">
<Private type="Siemens-AlternativeDesc">Info</Private>
<DAI name="configRev">
<Val>080820153605447</Val>
</DAI>
<DAI name="ldNs">
<Val>IEC 61850-7-4:2003</Val>
</DAI>
</DOI>
<DOI desc="本地操作" name="Loc">
<Private type="Siemens-AlternativeDesc">Control Auth</Private>
</DOI>
<DOI desc="运行小时数" name="OpTmh">
<Private type="Siemens-AlternativeDesc">Operating hours</Private>
</DOI>
<DOI desc="复归信号" name="LEDRs">
<Private type="Siemens-AlternativeDesc">LED acknwldgmnt</Private>
<DAI name="ctlModel">
<Val>direct-with-normal-security</Val>
</DAI>
</DOI>
</LN0>
<LN desc="设备" inst="1" lnClass="LPHD" lnType="F2T202IN/LD0/LPHD1" prefix="">
<Private type="Siemens-AlternativeDesc">Device</Private>
<Private type="IsNodeProcessed"/>
<Private type="Siemens-ControlBlockStorage">urcbA|&lt;ReportControl rptID="F2E801FCTRL/LPHD1$RP$urcbA01" confRev="0" buffered="false" bufTime="100" name="urcbA"&gt; &lt;Private type="Siemens-PredefinedControlBlock" /&gt; &lt;TrgOps dchg="true" qchg="true" dupd="true" period="true" /&gt; &lt;OptFields seqNum="true" timeStamp="true" dataSet="true" reasonCode="true" dataRef="false" configRef="true" /&gt; &lt;RptEnabled max="1" /&gt; &lt;/ReportControl&gt;</Private>
<Private type="Siemens-ControlBlockStorage">urcbB|&lt;ReportControl rptID="F2E801FCTRL/LPHD1$RP$urcbB01" confRev="0" buffered="false" bufTime="100" name="urcbB"&gt; &lt;Private type="Siemens-PredefinedControlBlock" /&gt; &lt;TrgOps dchg="true" qchg="true" dupd="true" period="true" /&gt; &lt;OptFields seqNum="true" timeStamp="true" dataSet="true" reasonCode="true" dataRef="false" configRef="true" /&gt; &lt;RptEnabled max="1" /&gt; &lt;/ReportControl&gt;</Private>
<DOI desc="物理装置铭牌" name="PhyNam">
<Private type="Siemens-AlternativeDesc">Info</Private>
</DOI>
<DOI desc="物理装置健康状况" name="PhyHealth">
<Private type="Siemens-AlternativeDesc">State</Private>
</DOI>
<DOI desc="代理" name="Proxy">
<Private type="Siemens-AlternativeDesc">Proxy</Private>
</DOI>
<DOI desc="装置上电" name="DevStr">
<!-- SIEMENS-spezifisch -->
<Private type="Siemens-AlternativeDesc">Startup</Private>
<DAI name="d">
<Val>DevStr stands for either InitialStart or Resume</Val>
</DAI>
<DAI name="dataNs">
<Val>SIEMENS EXT</Val>
</DAI>
</DOI>
<DOI desc="控制计数" name="CtlNum">
<!-- SIEMENS-spezifisch -->
<Private type="Siemens-AlternativeDesc">Test oper Nr</Private>
<DAI name="d">
<Val>CtlNum stands for number of Test Operations</Val>
</DAI>
<DAI name="dataNs">
<Val>SIEMENS EXT</Val>
</DAI>
</DOI>
</LN>
<LN desc="BIGGIO1" inst="1" lnClass="GGIO" lnType="F2T202A/CTRL/BIGGIO1" prefix="BI">
<Private type="Siemens-AlternativeDesc">BIGGIO1</Private>
<Private type="IsNodeProcessed"/>
<Private type="Siemens-ControlBlockStorage">urcbA|&lt;ReportControl rptID="F2E801FCTRL/BIGGIO1$RP$urcbA01" confRev="0" buffered="false" bufTime="100" name="urcbA"&gt; &lt;Private type="Siemens-PredefinedControlBlock" /&gt; &lt;TrgOps dchg="true" qchg="true" dupd="true" period="true" /&gt; &lt;OptFields seqNum="true" timeStamp="true" dataSet="true" reasonCode="true" dataRef="false" configRef="true" /&gt; &lt;RptEnabled max="1" /&gt; &lt;/ReportControl&gt;</Private>
<Private type="Siemens-ControlBlockStorage">urcbB|&lt;ReportControl rptID="F2E801FCTRL/BIGGIO1$RP$urcbB01" confRev="0" buffered="false" bufTime="100" name="urcbB"&gt; &lt;Private type="Siemens-PredefinedControlBlock" /&gt; &lt;TrgOps dchg="true" qchg="true" dupd="true" period="true" /&gt; &lt;OptFields seqNum="true" timeStamp="true" dataSet="true" reasonCode="true" dataRef="false" configRef="true" /&gt; &lt;RptEnabled max="1" /&gt; &lt;/ReportControl&gt;</Private>
<DOI desc="模式" name="Mod">
<Private type="Siemens-AlternativeDesc">Mode</Private>
<DAI name="ctlModel">
<Val>status-only</Val>
</DAI>
</DOI>
<DOI desc="性能" name="Beh">
<Private type="Siemens-AlternativeDesc">Behaviour</Private>
</DOI>
<DOI desc="健康状况" name="Health">
<Private type="Siemens-AlternativeDesc">State</Private>
</DOI>
<DOI desc="铭牌" name="NamPlt">
<Private type="Siemens-AlternativeDesc">Info</Private>
<DAI name="configRev">
<Val>080820153605447</Val>
</DAI>
</DOI>
<DOI desc="断路器分闸" name="SPCSO1">
<Private type="Siemens-AlternativeDesc">断路器分闸</Private>
<DAI name="ctlModel">
<Val>status-only</Val>
</DAI>
</DOI>
<DOI desc="断路器合闸" name="SPCSO2">
<Private type="Siemens-AlternativeDesc">断路器合闸</Private>
<DAI name="ctlModel">
<Val>status-only</Val>
</DAI>
</DOI>
<DOI desc="手车试验位置" name="SPCSO3">
<Private type="Siemens-AlternativeDesc">手车试验位置</Private>
<DAI name="ctlModel">
<Val>status-only</Val>
</DAI>
</DOI>
<DOI desc="手车工作位置" name="SPCSO4">
<Private type="Siemens-AlternativeDesc">手车工作位置</Private>
<DAI name="ctlModel">
<Val>status-only</Val>
</DAI>
</DOI>
<DOI desc="弹簧未储能" name="SPCSO5">
<Private type="Siemens-AlternativeDesc">弹簧未储能</Private>
<DAI name="ctlModel">
<Val>status-only</Val>
</DAI>
</DOI>
<DOI desc="接地开关分闸" name="SPCSO6">
<Private type="Siemens-AlternativeDesc">接地开关分闸</Private>
<DAI name="ctlModel">
<Val>status-only</Val>
</DAI>
</DOI>
<DOI desc="接地开关合闸" name="SPCSO7">
<Private type="Siemens-AlternativeDesc">接地开关合闸</Private>
<DAI name="ctlModel">
<Val>status-only</Val>
</DAI>
</DOI>
<DOI desc="遥控位置" name="SPCSO8">
<Private type="Siemens-AlternativeDesc">遥控位置</Private>
<DAI name="ctlModel">
<Val>status-only</Val>
</DAI>
</DOI>
<DOI desc="空开分闸" name="SPCSO9">
<Private type="Siemens-AlternativeDesc">空开分闸</Private>
<DAI name="ctlModel">
<Val>status-only</Val>
</DAI>
</DOI>
<DOI desc="相邻柜保护装置故障" name="SPCSO10">
<Private type="Siemens-AlternativeDesc">相邻柜保护装置故障</Private>
<DAI name="ctlModel">
<Val>status-only</Val>
</DAI>
</DOI>
<DOI desc="变压器高温" name="SPCSO11">
<Private type="Siemens-AlternativeDesc">变压器高温</Private>
<DAI name="ctlModel">
<Val>status-only</Val>
</DAI>
</DOI>
<DOI desc="变压器超温" name="SPCSO12">
<Private type="Siemens-AlternativeDesc">变压器超温</Private>
<DAI name="ctlModel">
<Val>status-only</Val>
</DAI>
</DOI>
<DOI desc="网门打开" name="SPCSO13">
<Private type="Siemens-AlternativeDesc">网门打开</Private>
<DAI name="ctlModel">
<Val>status-only</Val>
</DAI>
</DOI>
<DOI desc="备用1" name="SPCSO14">
<Private type="Siemens-AlternativeDesc">备用1</Private>
<DAI name="ctlModel">
<Val>status-only</Val>
</DAI>
</DOI>
<DOI desc="备用2" name="SPCSO15">
<Private type="Siemens-AlternativeDesc">备用2</Private>
<DAI name="ctlModel">
<Val>status-only</Val>
</DAI>
</DOI>
<DOI desc="备用3" name="SPCSO16">
<Private type="Siemens-AlternativeDesc">备用3</Private>
<DAI name="ctlModel">
<Val>status-only</Val>
</DAI>
</DOI>
</LN>
<LN desc="断路器XCBR" inst="1" lnClass="XCBR" lnType="F2T202IN/CTRL/Q0XCBR1" prefix="Q0">
<Private type="Siemens-AlternativeDesc">BreakerXCBR</Private>
<Private type="IsNodeProcessed"/>
<Private type="Siemens-ControlBlockStorage">urcbA|&lt;ReportControl rptID="F2E801FCTRL/Q0XCBR1$RP$urcbA01" confRev="0" buffered="false" bufTime="100" name="urcbA"&gt; &lt;Private type="Siemens-PredefinedControlBlock" /&gt; &lt;TrgOps dchg="true" qchg="true" dupd="true" period="true" /&gt; &lt;OptFields seqNum="true" timeStamp="true" dataSet="true" reasonCode="true" dataRef="false" configRef="true" /&gt; &lt;RptEnabled max="1" /&gt; &lt;/ReportControl&gt;</Private>
<Private type="Siemens-ControlBlockStorage">urcbB|&lt;ReportControl rptID="F2E801FCTRL/Q0XCBR1$RP$urcbB01" confRev="0" buffered="false" bufTime="100" name="urcbB"&gt; &lt;Private type="Siemens-PredefinedControlBlock" /&gt; &lt;TrgOps dchg="true" qchg="true" dupd="true" period="true" /&gt; &lt;OptFields seqNum="true" timeStamp="true" dataSet="true" reasonCode="true" dataRef="false" configRef="true" /&gt; &lt;RptEnabled max="1" /&gt; &lt;/ReportControl&gt;</Private>
<DOI desc="模式" name="Mod">
<Private type="Siemens-AlternativeDesc">Mode</Private>
<DAI name="ctlModel">
<Val>status-only</Val>
</DAI>
</DOI>
<DOI desc="性能" name="Beh">
<Private type="Siemens-AlternativeDesc">Behaviour</Private>
</DOI>
<DOI desc="健康状况" name="Health">
<Private type="Siemens-AlternativeDesc">State</Private>
</DOI>
<DOI desc="铭牌" name="NamPlt">
<Private type="Siemens-AlternativeDesc">Info</Private>
<DAI name="configRev">
<Val>160304190901000</Val>
</DAI>
</DOI>
<DOI desc="本地操作" name="Loc">
<Private type="Siemens-AlternativeDesc">Control Auth</Private>
</DOI>
<DOI desc="跳闸总次数" name="OpCnt">
<Private type="Siemens-AlternativeDesc">TripComdCounter</Private>
</DOI>
<DOI desc="位置" name="Pos">
<Private type="Siemens-AlternativeDesc">Position</Private>
<DAI name="ctlModel">
<Val>status-only</Val>
</DAI>
</DOI>
<DOI desc="跳闸闭锁" name="BlkOpn">
<Private type="Siemens-AlternativeDesc">Open block</Private>
<DAI name="ctlModel">
<Val>status-only</Val>
</DAI>
</DOI>
<DOI desc="合闸闭锁" name="BlkCls">
<Private type="Siemens-AlternativeDesc">Close block</Private>
<DAI name="ctlModel">
<Val>status-only</Val>
</DAI>
</DOI>
<DOI desc="断路器操作能力" name="CBOpCap">
<Private type="Siemens-AlternativeDesc">Switch capablty</Private>
<DAI name="stVal">
<Val>None</Val>
</DAI>
</DOI>
</LN>
<LN desc="断路器CSWI" inst="1" lnClass="CSWI" lnType="F2T202IN/CTRL/Q0CSWI1" prefix="Q0">
<Private type="Siemens-AlternativeDesc">BreakerCSWI</Private>
<Private type="IsNodeProcessed"/>
<Private type="Siemens-ControlBlockStorage">urcbA|&lt;ReportControl rptID="F2E801FCTRL/Q0CSWI1$RP$urcbA01" confRev="0" buffered="false" bufTime="100" name="urcbA"&gt; &lt;Private type="Siemens-PredefinedControlBlock" /&gt; &lt;TrgOps dchg="true" qchg="true" dupd="true" period="true" /&gt; &lt;OptFields seqNum="true" timeStamp="true" dataSet="true" reasonCode="true" dataRef="false" configRef="true" /&gt; &lt;RptEnabled max="1" /&gt; &lt;/ReportControl&gt;</Private>
<Private type="Siemens-ControlBlockStorage">urcbB|&lt;ReportControl rptID="F2E801FCTRL/Q0CSWI1$RP$urcbB01" confRev="0" buffered="false" bufTime="100" name="urcbB"&gt; &lt;Private type="Siemens-PredefinedControlBlock" /&gt; &lt;TrgOps dchg="true" qchg="true" dupd="true" period="true" /&gt; &lt;OptFields seqNum="true" timeStamp="true" dataSet="true" reasonCode="true" dataRef="false" configRef="true" /&gt; &lt;RptEnabled max="1" /&gt; &lt;/ReportControl&gt;</Private>
<DOI desc="模式" name="Mod">
<Private type="Siemens-AlternativeDesc">Mode</Private>
<DAI name="ctlModel">
<Val>status-only</Val>
</DAI>
</DOI>
<DOI desc="性能" name="Beh">
<Private type="Siemens-AlternativeDesc">Behaviour</Private>
</DOI>
<DOI desc="健康状况" name="Health">
<Private type="Siemens-AlternativeDesc">State</Private>
</DOI>
<DOI desc="铭牌" name="NamPlt">
<Private type="Siemens-AlternativeDesc">Info</Private>
<DAI name="configRev">
<Val>160304190901000</Val>
</DAI>
</DOI>
<DOI desc="本地操作" name="Loc">
<Private type="Siemens-AlternativeDesc">Control Auth</Private>
</DOI>
<DOI desc="位置" name="Pos">
<Private type="Siemens-AlternativeDesc">Position</Private>
<DAI name="ctlModel">
<Val>sbo-with-enhanced-security</Val>
</DAI>
<DAI name="sboTimeout">
<Val>300000</Val>
</DAI>
<DAI name="sboClass">
<Val>operate-once</Val>
</DAI>
</DOI>
</LN>
<LN desc="断路器CILO" inst="1" lnClass="CILO" lnType="F2T202IN/CTRL/Q0CILO1" prefix="Q0">
<Private type="Siemens-AlternativeDesc">BreakerCILO</Private>
<Private type="IsNodeProcessed"/>
<Private type="Siemens-ControlBlockStorage">urcbA|&lt;ReportControl rptID="F2E801FCTRL/Q0CILO1$RP$urcbA01" confRev="0" buffered="false" bufTime="100" name="urcbA"&gt; &lt;Private type="Siemens-PredefinedControlBlock" /&gt; &lt;TrgOps dchg="true" qchg="true" dupd="true" period="true" /&gt; &lt;OptFields seqNum="true" timeStamp="true" dataSet="true" reasonCode="true" dataRef="false" configRef="true" /&gt; &lt;RptEnabled max="1" /&gt; &lt;/ReportControl&gt;</Private>
<Private type="Siemens-ControlBlockStorage">urcbB|&lt;ReportControl rptID="F2E801FCTRL/Q0CILO1$RP$urcbB01" confRev="0" buffered="false" bufTime="100" name="urcbB"&gt; &lt;Private type="Siemens-PredefinedControlBlock" /&gt; &lt;TrgOps dchg="true" qchg="true" dupd="true" period="true" /&gt; &lt;OptFields seqNum="true" timeStamp="true" dataSet="true" reasonCode="true" dataRef="false" configRef="true" /&gt; &lt;RptEnabled max="1" /&gt; &lt;/ReportControl&gt;</Private>
<DOI desc="模式" name="Mod">
<Private type="Siemens-AlternativeDesc">Mode</Private>
<DAI name="ctlModel">
<Val>status-only</Val>
</DAI>
</DOI>
<DOI desc="性能" name="Beh">
<Private type="Siemens-AlternativeDesc">Behaviour</Private>
</DOI>
<DOI desc="健康状况" name="Health">
<Private type="Siemens-AlternativeDesc">State</Private>
</DOI>
<DOI desc="铭牌" name="NamPlt">
<Private type="Siemens-AlternativeDesc">Info</Private>
<DAI name="configRev">
<Val>160304190901000</Val>
</DAI>
</DOI>
<DOI desc="分闸允许" name="EnaOpn">
<Private type="Siemens-AlternativeDesc">Enable Open</Private>
</DOI>
<DOI desc="合闸允许" name="EnaCls">
<Private type="Siemens-AlternativeDesc">Enable Close</Private>
</DOI>
</LN>
<LN desc="隔离开关XSWI" inst="1" lnClass="XSWI" lnType="F2T202IN/CTRL/Q1XSWI1" prefix="Q1">
<Private type="Siemens-AlternativeDesc">Disc.Swit.XSWI</Private>
<Private type="IsNodeProcessed"/>
<Private type="Siemens-ControlBlockStorage">urcbA|&lt;ReportControl rptID="F2E801FCTRL/Q1XSWI1$RP$urcbA01" confRev="0" buffered="false" bufTime="100" name="urcbA"&gt; &lt;Private type="Siemens-PredefinedControlBlock" /&gt; &lt;TrgOps dchg="true" qchg="true" dupd="true" period="true" /&gt; &lt;OptFields seqNum="true" timeStamp="true" dataSet="true" reasonCode="true" dataRef="false" configRef="true" /&gt; &lt;RptEnabled max="1" /&gt; &lt;/ReportControl&gt;</Private>
<Private type="Siemens-ControlBlockStorage">urcbB|&lt;ReportControl rptID="F2E801FCTRL/Q1XSWI1$RP$urcbB01" confRev="0" buffered="false" bufTime="100" name="urcbB"&gt; &lt;Private type="Siemens-PredefinedControlBlock" /&gt; &lt;TrgOps dchg="true" qchg="true" dupd="true" period="true" /&gt; &lt;OptFields seqNum="true" timeStamp="true" dataSet="true" reasonCode="true" dataRef="false" configRef="true" /&gt; &lt;RptEnabled max="1" /&gt; &lt;/ReportControl&gt;</Private>
<DOI desc="模式" name="Mod">
<Private type="Siemens-AlternativeDesc">Mode</Private>
<DAI name="ctlModel">
<Val>status-only</Val>
</DAI>
</DOI>
<DOI desc="性能" name="Beh">
<Private type="Siemens-AlternativeDesc">Behaviour</Private>
</DOI>
<DOI desc="健康状况" name="Health">
<Private type="Siemens-AlternativeDesc">State</Private>
</DOI>
<DOI desc="铭牌" name="NamPlt">
<Private type="Siemens-AlternativeDesc">Info</Private>
<DAI name="configRev">
<Val>160304190901000</Val>
</DAI>
</DOI>
<DOI desc="本地操作" name="Loc">
<Private type="Siemens-AlternativeDesc">Control Auth</Private>
</DOI>
<DOI desc="跳闸总次数" name="OpCnt">
<Private type="Siemens-AlternativeDesc">TripComdCounter</Private>
</DOI>
<DOI desc="位置" name="Pos">
<Private type="Siemens-AlternativeDesc">Position</Private>
<DAI name="ctlModel">
<Val>status-only</Val>
</DAI>
</DOI>
<DOI desc="跳闸闭锁" name="BlkOpn">
<Private type="Siemens-AlternativeDesc">Open block</Private>
<DAI name="ctlModel">
<Val>status-only</Val>
</DAI>
</DOI>
<DOI desc="合闸闭锁" name="BlkCls">
<Private type="Siemens-AlternativeDesc">Close block</Private>
<DAI name="ctlModel">
<Val>status-only</Val>
</DAI>
</DOI>
<DOI desc="开关类型" name="SwTyp">
<Private type="Siemens-AlternativeDesc">Switch type</Private>
<DAI name="stVal">
<Val>Disconnector</Val>
</DAI>
</DOI>
<DOI desc="开关操作能力" name="SwOpCap">
<Private type="Siemens-AlternativeDesc">Switch capablty</Private>
<DAI name="stVal">
<Val>None</Val>
</DAI>
</DOI>
</LN>
<LN desc="隔离开关CSWI" inst="1" lnClass="CSWI" lnType="F2T202IN/CTRL/Q0CSWI1" prefix="Q1">
<Private type="Siemens-AlternativeDesc">Disc.Swit.CSWI</Private>
<Private type="IsNodeProcessed"/>
<Private type="Siemens-ControlBlockStorage">urcbA|&lt;ReportControl rptID="F2E801FCTRL/Q1CSWI1$RP$urcbA01" confRev="0" buffered="false" bufTime="100" name="urcbA"&gt; &lt;Private type="Siemens-PredefinedControlBlock" /&gt; &lt;TrgOps dchg="true" qchg="true" dupd="true" period="true" /&gt; &lt;OptFields seqNum="true" timeStamp="true" dataSet="true" reasonCode="true" dataRef="false" configRef="true" /&gt; &lt;RptEnabled max="1" /&gt; &lt;/ReportControl&gt;</Private>
<Private type="Siemens-ControlBlockStorage">urcbB|&lt;ReportControl rptID="F2E801FCTRL/Q1CSWI1$RP$urcbB01" confRev="0" buffered="false" bufTime="100" name="urcbB"&gt; &lt;Private type="Siemens-PredefinedControlBlock" /&gt; &lt;TrgOps dchg="true" qchg="true" dupd="true" period="true" /&gt; &lt;OptFields seqNum="true" timeStamp="true" dataSet="true" reasonCode="true" dataRef="false" configRef="true" /&gt; &lt;RptEnabled max="1" /&gt; &lt;/ReportControl&gt;</Private>
<DOI desc="模式" name="Mod">
<Private type="Siemens-AlternativeDesc">Mode</Private>
<DAI name="ctlModel">
<Val>status-only</Val>
</DAI>
</DOI>
<DOI desc="性能" name="Beh">
<Private type="Siemens-AlternativeDesc">Behaviour</Private>
</DOI>
<DOI desc="健康状况" name="Health">
<Private type="Siemens-AlternativeDesc">State</Private>
</DOI>
<DOI desc="铭牌" name="NamPlt">
<Private type="Siemens-AlternativeDesc">Info</Private>
<DAI name="configRev">
<Val>160304190901000</Val>
</DAI>
</DOI>
<DOI desc="本地操作" name="Loc">
<Private type="Siemens-AlternativeDesc">Control Auth</Private>
</DOI>
<DOI desc="位置" name="Pos">
<Private type="Siemens-AlternativeDesc">Position</Private>
<DAI name="ctlModel">
<Val>sbo-with-enhanced-security</Val>
</DAI>
<DAI name="sboTimeout">
<Val>300000</Val>
</DAI>
<DAI name="sboClass">
<Val>operate-once</Val>
</DAI>
</DOI>
</LN>
<LN desc="隔离开关CILO" inst="1" lnClass="CILO" lnType="F2T202IN/CTRL/Q0CILO1" prefix="Q1">
<Private type="Siemens-AlternativeDesc">Disc.Swit.CILO</Private>
<Private type="IsNodeProcessed"/>
<Private type="Siemens-ControlBlockStorage">urcbA|&lt;ReportControl rptID="F2E801FCTRL/Q1CILO1$RP$urcbA01" confRev="0" buffered="false" bufTime="100" name="urcbA"&gt; &lt;Private type="Siemens-PredefinedControlBlock" /&gt; &lt;TrgOps dchg="true" qchg="true" dupd="true" period="true" /&gt; &lt;OptFields seqNum="true" timeStamp="true" dataSet="true" reasonCode="true" dataRef="false" configRef="true" /&gt; &lt;RptEnabled max="1" /&gt; &lt;/ReportControl&gt;</Private>
<Private type="Siemens-ControlBlockStorage">urcbB|&lt;ReportControl rptID="F2E801FCTRL/Q1CILO1$RP$urcbB01" confRev="0" buffered="false" bufTime="100" name="urcbB"&gt; &lt;Private type="Siemens-PredefinedControlBlock" /&gt; &lt;TrgOps dchg="true" qchg="true" dupd="true" period="true" /&gt; &lt;OptFields seqNum="true" timeStamp="true" dataSet="true" reasonCode="true" dataRef="false" configRef="true" /&gt; &lt;RptEnabled max="1" /&gt; &lt;/ReportControl&gt;</Private>
<DOI desc="模式" name="Mod">
<Private type="Siemens-AlternativeDesc">Mode</Private>
<DAI name="ctlModel">
<Val>status-only</Val>
</DAI>
</DOI>
<DOI desc="性能" name="Beh">
<Private type="Siemens-AlternativeDesc">Behaviour</Private>
</DOI>
<DOI desc="健康状况" name="Health">
<Private type="Siemens-AlternativeDesc">State</Private>
</DOI>
<DOI desc="铭牌" name="NamPlt">
<Private type="Siemens-AlternativeDesc">Info</Private>
<DAI name="configRev">
<Val>160304190901000</Val>
</DAI>
</DOI>
<DOI desc="分闸允许" name="EnaOpn">
<Private type="Siemens-AlternativeDesc">Enable Open</Private>
</DOI>
<DOI desc="合闸允许" name="EnaCls">
<Private type="Siemens-AlternativeDesc">Enable Close</Private>
</DOI>
</LN>
<LN desc="接地刀闸XSWI" inst="1" lnClass="XSWI" lnType="F2T202IN/CTRL/Q1XSWI1" prefix="Q8">
<Private type="Siemens-AlternativeDesc">EarthSwitXSWI</Private>
<Private type="IsNodeProcessed"/>
<Private type="Siemens-ControlBlockStorage">urcbA|&lt;ReportControl rptID="F2E801FCTRL/Q8XSWI1$RP$urcbA01" confRev="0" buffered="false" bufTime="100" name="urcbA"&gt; &lt;Private type="Siemens-PredefinedControlBlock" /&gt; &lt;TrgOps dchg="true" qchg="true" dupd="true" period="true" /&gt; &lt;OptFields seqNum="true" timeStamp="true" dataSet="true" reasonCode="true" dataRef="false" configRef="true" /&gt; &lt;RptEnabled max="1" /&gt; &lt;/ReportControl&gt;</Private>
<Private type="Siemens-ControlBlockStorage">urcbB|&lt;ReportControl rptID="F2E801FCTRL/Q8XSWI1$RP$urcbB01" confRev="0" buffered="false" bufTime="100" name="urcbB"&gt; &lt;Private type="Siemens-PredefinedControlBlock" /&gt; &lt;TrgOps dchg="true" qchg="true" dupd="true" period="true" /&gt; &lt;OptFields seqNum="true" timeStamp="true" dataSet="true" reasonCode="true" dataRef="false" configRef="true" /&gt; &lt;RptEnabled max="1" /&gt; &lt;/ReportControl&gt;</Private>
<DOI desc="模式" name="Mod">
<Private type="Siemens-AlternativeDesc">Mode</Private>
<DAI name="ctlModel">
<Val>status-only</Val>
</DAI>
</DOI>
<DOI desc="性能" name="Beh">
<Private type="Siemens-AlternativeDesc">Behaviour</Private>
</DOI>
<DOI desc="健康状况" name="Health">
<Private type="Siemens-AlternativeDesc">State</Private>
</DOI>
<DOI desc="铭牌" name="NamPlt">
<Private type="Siemens-AlternativeDesc">Info</Private>
<DAI name="configRev">
<Val>160304190901000</Val>
</DAI>
</DOI>
<DOI desc="本地操作" name="Loc">
<Private type="Siemens-AlternativeDesc">Control Auth</Private>
</DOI>
<DOI desc="跳闸总次数" name="OpCnt">
<Private type="Siemens-AlternativeDesc">TripComdCounter</Private>
</DOI>
<DOI desc="位置" name="Pos">
<Private type="Siemens-AlternativeDesc">Position</Private>
<DAI name="ctlModel">
<Val>status-only</Val>
</DAI>
</DOI>
<DOI desc="跳闸闭锁" name="BlkOpn">
<Private type="Siemens-AlternativeDesc">Open block</Private>
<DAI name="ctlModel">
<Val>status-only</Val>
</DAI>
</DOI>
<DOI desc="合闸闭锁" name="BlkCls">
<Private type="Siemens-AlternativeDesc">Close block</Private>
<DAI name="ctlModel">
<Val>status-only</Val>
</DAI>
</DOI>
<DOI desc="开关类型" name="SwTyp">
<Private type="Siemens-AlternativeDesc">Switch type</Private>
<DAI name="stVal">
<Val>Earthing Switch</Val>
</DAI>
</DOI>
<DOI desc="开关操作能力" name="SwOpCap">
<Private type="Siemens-AlternativeDesc">Switch capablty</Private>
<DAI name="stVal">
<Val>None</Val>
</DAI>
</DOI>
</LN>
<LN desc="接地刀闸CSWI" inst="1" lnClass="CSWI" lnType="F2T202IN/CTRL/Q0CSWI1" prefix="Q8">
<Private type="Siemens-AlternativeDesc">EarthSwitCSWI</Private>
<Private type="IsNodeProcessed"/>
<Private type="Siemens-ControlBlockStorage">urcbA|&lt;ReportControl rptID="F2E801FCTRL/Q8CSWI1$RP$urcbA01" confRev="0" buffered="false" bufTime="100" name="urcbA"&gt; &lt;Private type="Siemens-PredefinedControlBlock" /&gt; &lt;TrgOps dchg="true" qchg="true" dupd="true" period="true" /&gt; &lt;OptFields seqNum="true" timeStamp="true" dataSet="true" reasonCode="true" dataRef="false" configRef="true" /&gt; &lt;RptEnabled max="1" /&gt; &lt;/ReportControl&gt;</Private>
<Private type="Siemens-ControlBlockStorage">urcbB|&lt;ReportControl rptID="F2E801FCTRL/Q8CSWI1$RP$urcbB01" confRev="0" buffered="false" bufTime="100" name="urcbB"&gt; &lt;Private type="Siemens-PredefinedControlBlock" /&gt; &lt;TrgOps dchg="true" qchg="true" dupd="true" period="true" /&gt; &lt;OptFields seqNum="true" timeStamp="true" dataSet="true" reasonCode="true" dataRef="false" configRef="true" /&gt; &lt;RptEnabled max="1" /&gt; &lt;/ReportControl&gt;</Private>
<DOI desc="模式" name="Mod">
<Private type="Siemens-AlternativeDesc">Mode</Private>
<DAI name="ctlModel">
<Val>status-only</Val>
</DAI>
</DOI>
<DOI desc="性能" name="Beh">
<Private type="Siemens-AlternativeDesc">Behaviour</Private>
</DOI>
<DOI desc="健康状况" name="Health">
<Private type="Siemens-AlternativeDesc">State</Private>
</DOI>
<DOI desc="铭牌" name="NamPlt">
<Private type="Siemens-AlternativeDesc">Info</Private>
<DAI name="configRev">
<Val>160304190901000</Val>
</DAI>
</DOI>
<DOI desc="本地操作" name="Loc">
<Private type="Siemens-AlternativeDesc">Control Auth</Private>
</DOI>
<DOI desc="位置" name="Pos">
<Private type="Siemens-AlternativeDesc">Position</Private>
<DAI name="ctlModel">
<Val>sbo-with-enhanced-security</Val>
</DAI>
<DAI name="sboTimeout">
<Val>300000</Val>
</DAI>
<DAI name="sboClass">
<Val>operate-once</Val>
</DAI>
</DOI>
</LN>
<LN desc="接地刀闸CILO" inst="1" lnClass="CILO" lnType="F2T202IN/CTRL/Q0CILO1" prefix="Q8">
<Private type="Siemens-AlternativeDesc">EarthSwitCILO</Private>
<Private type="IsNodeProcessed"/>
<Private type="Siemens-ControlBlockStorage">urcbA|&lt;ReportControl rptID="F2E801FCTRL/Q8CILO1$RP$urcbA01" confRev="0" buffered="false" bufTime="100" name="urcbA"&gt; &lt;Private type="Siemens-PredefinedControlBlock" /&gt; &lt;TrgOps dchg="true" qchg="true" dupd="true" period="true" /&gt; &lt;OptFields seqNum="true" timeStamp="true" dataSet="true" reasonCode="true" dataRef="false" configRef="true" /&gt; &lt;RptEnabled max="1" /&gt; &lt;/ReportControl&gt;</Private>
<Private type="Siemens-ControlBlockStorage">urcbB|&lt;ReportControl rptID="F2E801FCTRL/Q8CILO1$RP$urcbB01" confRev="0" buffered="false" bufTime="100" name="urcbB"&gt; &lt;Private type="Siemens-PredefinedControlBlock" /&gt; &lt;TrgOps dchg="true" qchg="true" dupd="true" period="true" /&gt; &lt;OptFields seqNum="true" timeStamp="true" dataSet="true" reasonCode="true" dataRef="false" configRef="true" /&gt; &lt;RptEnabled max="1" /&gt; &lt;/ReportControl&gt;</Private>
<DOI desc="模式" name="Mod">
<Private type="Siemens-AlternativeDesc">Mode</Private>
<DAI name="ctlModel">
<Val>status-only</Val>
</DAI>
</DOI>
<DOI desc="性能" name="Beh">
<Private type="Siemens-AlternativeDesc">Behaviour</Private>
</DOI>
<DOI desc="健康状况" name="Health">
<Private type="Siemens-AlternativeDesc">State</Private>
</DOI>
<DOI desc="铭牌" name="NamPlt">
<Private type="Siemens-AlternativeDesc">Info</Private>
<DAI name="configRev">
<Val>160304190901000</Val>
</DAI>
</DOI>
<DOI desc="分闸允许" name="EnaOpn">
<Private type="Siemens-AlternativeDesc">Enable Open</Private>
</DOI>
<DOI desc="合闸允许" name="EnaCls">
<Private type="Siemens-AlternativeDesc">Enable Close</Private>
</DOI>
</LN>
</LDevice>
</Server>
</AccessPoint>
</IED>
<DataTypeTemplates>
<LNodeType id="F2T202A/PROT/NonEleGGIO1" lnClass="GGIO">
<DO name="Mod" type="myMod_0"/>
<DO name="Beh" type="myBeh_1"/>
<DO name="Health" type="myHealth_2"/>
<DO name="NamPlt" type="myNamPlt_9"/>
<DO name="SPCSO1" type="mySPCSO1_27"/>
<DO name="SPCSO2" type="mySPCSO1_27"/>
<DO name="SPCSO3" type="mySPCSO1_27"/>
<DO name="SPCSO4" type="mySPCSO1_27"/>
<DO name="SPCSO5" type="mySPCSO1_27"/>
<DO name="SPCSO6" type="mySPCSO1_27"/>
<DO name="SPCSO7" type="mySPCSO1_27"/>
<DO name="SPCSO8" type="mySPCSO1_27"/>
<DO name="SPCSO9" type="mySPCSO1_27"/>
<DO name="SPCSO10" type="mySPCSO1_27"/>
<DO name="SPCSO11" type="mySPCSO1_27"/>
<DO name="SPCSO12" type="mySPCSO1_27"/>
<DO name="SPCSO13" type="mySPCSO1_27"/>
<DO name="SPCSO14" type="mySPCSO1_27"/>
<DO name="SPCSO15" type="mySPCSO1_27"/>
<DO name="SPCSO16" type="mySPCSO1_27"/>
<DO name="SPCSO17" type="mySPCSO1_27"/>
<DO name="SPCSO18" type="mySPCSO1_27"/>
</LNodeType>
<LNodeType id="F2T202IN/DR/SC_RDRE1" lnClass="RDRE">
<DO name="Mod" type="myMod_0"/>
<DO name="Beh" type="myBeh_1"/>
<DO name="Health" type="myHealth_2"/>
<DO name="NamPlt" type="myNamPlt_9"/>
<DO name="RcdMade" type="myLoc_4"/>
<DO name="FltNum" type="myOpTmh_5"/>
<DO name="GriFltNum" type="myOpTmh_5"/>
<DO name="RcdStr" type="myLoc_4"/>
</LNodeType>
<LNodeType id="F2T202IN/PROT/PhIIPTOC1" lnClass="PTOC">
<DO name="Mod" type="myMod_0"/>
<DO name="Beh" type="myBeh_1"/>
<DO name="Health" type="myHealth_2"/>
<DO name="NamPlt" type="myNamPlt_9"/>
<DO name="Str" type="myStr_51"/>
<DO name="Op" type="myOp_52"/>
<DO name="Mode" type="myMode_53"/>
<DO name="VCtrl" type="myBlkDir_54"/>
<DO name="StrVal" type="myStrVal_55"/>
<DO name="OpDlTmms" type="myOpDlTmms_61"/>
<DO name="DirMod" type="myDirMod_62"/>
</LNodeType>
<LNodeType id="F2T202IN/PROT/ZerIIPTOC1" lnClass="PTOC">
<DO name="Mod" type="myMod_0"/>
<DO name="Beh" type="myBeh_1"/>
<DO name="Health" type="myHealth_2"/>
<DO name="NamPlt" type="myNamPlt_9"/>
<DO name="Str" type="myStr_51"/>
<DO name="Op" type="myOp_52"/>
<DO name="Mode" type="myMode_53"/>
<DO name="StrVal" type="myStrVal_55"/>
<DO name="OpDlTmms" type="myOpDlTmms_61"/>
<DO name="DirMod" type="myDirMod_62"/>
</LNodeType>
<LNodeType id="F2T202IN/PROT/LLN0" lnClass="LLN0">
<DO name="Mod" type="myMod_0"/>
<DO name="Beh" type="myBeh_1"/>
<DO name="Health" type="myHealth_2"/>
<DO name="NamPlt" type="myNamPlt_3"/>
<DO name="OpTmh" type="myOpTmh_5"/>
<DO name="PhOCEna" type="myPhOCEna_35"/>
<DO name="ZerOCEna" type="myPhOCEna_35"/>
</LNodeType>
<LNodeType id="F2T202IN/MEAS/LLN0" lnClass="LLN0">
<DO name="Mod" type="myMod_0"/>
<DO name="Beh" type="myBeh_1"/>
<DO name="Health" type="myHealth_2"/>
<DO name="NamPlt" type="myNamPlt_3"/>
</LNodeType>
<LNodeType id="F2T202IN/LD0/LPHD1" lnClass="LPHD">
<DO name="PhyNam" type="myPhyNam_18"/>
<DO name="PhyHealth" type="myHealth_2"/>
<DO name="Proxy" type="myLoc_4"/>
<DO name="DevStr" type="myDevStr_21"/>
<DO name="CtlNum" type="myDevStr_21"/>
</LNodeType>
<LNodeType id="F2T202IN/PROT/XCBR1" lnClass="XCBR">
<DO name="Mod" type="myMod_0"/>
<DO name="Beh" type="myBeh_1"/>
<DO name="Health" type="myHealth_2"/>
<DO name="NamPlt" type="myNamPlt_9"/>
<DO name="Loc" type="myLoc_4"/>
<DO name="OpCnt" type="myOpTmh_5"/>
<DO name="Pos" type="myPos_202"/>
<DO name="BlkOpn" type="mySPCSO1_27"/>
<DO name="BlkCls" type="mySPCSO1_27"/>
<DO name="SumSwARs1" type="mySumSwARs1_205"/>
<DO name="SumSwARs2" type="mySumSwARs1_205"/>
<DO name="SumSwARs3" type="mySumSwARs1_205"/>
<DO name="CBOpCap" type="myCBOpCap_211"/>
<DO name="LoadPro1" type="myLoadPro1_212"/>
<DO name="LoadPro2" type="myLoadPro1_212"/>
<DO name="LoadPro3" type="myLoadPro1_212"/>
<DO name="LoadPro4" type="myLoadPro1_212"/>
</LNodeType>
<LNodeType id="F2T202IN/PROT/PhIPTOC1" lnClass="PTOC">
<DO name="Mod" type="myMod_0"/>
<DO name="Beh" type="myBeh_1"/>
<DO name="Health" type="myHealth_2"/>
<DO name="NamPlt" type="myNamPlt_9"/>
<DO name="Str" type="myStr_51"/>
<DO name="Op" type="myOp_52"/>
<DO name="Mode" type="myMode_53"/>
<DO name="BlkDir" type="myBlkDir_54"/>
<DO name="PTBlkV" type="myBlkDir_54"/>
<DO name="BlkVPhPh" type="myBlkVPhPh_118"/>
<DO name="BlkNgv" type="myBlkVPhPh_118"/>
<DO name="VCtrl" type="myBlkDir_54"/>
<DO name="StrVal" type="myStrVal_55"/>
<DO name="OpDlTmms" type="myOpDlTmms_61"/>
<DO name="DirMod" type="myDirMod_62"/>
</LNodeType>
<LNodeType id="F2T202IN/CTRL/Q1XSWI1" lnClass="XSWI">
<DO name="Mod" type="myMod_0"/>
<DO name="Beh" type="myBeh_1"/>
<DO name="Health" type="myHealth_2"/>
<DO name="NamPlt" type="myNamPlt_9"/>
<DO name="Loc" type="myLoc_4"/>
<DO name="OpCnt" type="myOpTmh_5"/>
<DO name="Pos" type="myPos_202"/>
<DO name="BlkOpn" type="mySPCSO1_27"/>
<DO name="BlkCls" type="mySPCSO1_27"/>
<DO name="SwTyp" type="mySwTyp_665"/>
<DO name="SwOpCap" type="mySwOpCap_666"/>
</LNodeType>
<LNodeType id="F2T202IN/CTRL/Q0CILO1" lnClass="CILO">
<DO name="Mod" type="myMod_0"/>
<DO name="Beh" type="myBeh_1"/>
<DO name="Health" type="myHealth_2"/>
<DO name="NamPlt" type="myNamPlt_9"/>
<DO name="EnaOpn" type="myLoc_4"/>
<DO name="EnaCls" type="myLoc_4"/>
</LNodeType>
<LNodeType id="F2T202IN/PROT/LPHD1" lnClass="LPHD">
<DO name="PhyNam" type="myPhyNam_18"/>
<DO name="PhyHealth" type="myHealth_2"/>
<DO name="Proxy" type="myLoc_4"/>
</LNodeType>
<LNodeType id="F2T202IN/LD0/ComGGIO1" lnClass="GGIO">
<DO name="Mod" type="myMod_0"/>
<DO name="Beh" type="myBeh_1"/>
<DO name="Health" type="myHealth_2"/>
<DO name="NamPlt" type="myNamPlt_9"/>
<DO name="SPCSO1" type="mySPCSO1_27"/>
<DO name="SPCSO2" type="mySPCSO1_27"/>
<DO name="SPCSO3" type="mySPCSO1_27"/>
</LNodeType>
<LNodeType id="F2T202A/CTRL/BIGGIO1" lnClass="GGIO">
<DO name="Mod" type="myMod_0"/>
<DO name="Beh" type="myBeh_1"/>
<DO name="Health" type="myHealth_2"/>
<DO name="NamPlt" type="myNamPlt_9"/>
<DO name="SPCSO1" type="mySPCSO1_27"/>
<DO name="SPCSO2" type="mySPCSO1_27"/>
<DO name="SPCSO3" type="mySPCSO1_27"/>
<DO name="SPCSO4" type="mySPCSO1_27"/>
<DO name="SPCSO5" type="mySPCSO1_27"/>
<DO name="SPCSO6" type="mySPCSO1_27"/>
<DO name="SPCSO7" type="mySPCSO1_27"/>
<DO name="SPCSO8" type="mySPCSO1_27"/>
<DO name="SPCSO9" type="mySPCSO1_27"/>
<DO name="SPCSO10" type="mySPCSO1_27"/>
<DO name="SPCSO11" type="mySPCSO1_27"/>
<DO name="SPCSO12" type="mySPCSO1_27"/>
<DO name="SPCSO13" type="mySPCSO1_27"/>
<DO name="SPCSO14" type="mySPCSO1_27"/>
<DO name="SPCSO15" type="mySPCSO1_27"/>
<DO name="SPCSO16" type="mySPCSO1_27"/>
</LNodeType>
<LNodeType id="F2T202IN/CTRL/LLN0" lnClass="LLN0">
<DO name="Mod" type="myMod_0"/>
<DO name="Beh" type="myBeh_1"/>
<DO name="Health" type="myHealth_2"/>
<DO name="NamPlt" type="myNamPlt_3"/>
<DO name="Loc" type="myLoc_4"/>
<DO name="OpTmh" type="myOpTmh_5"/>
<DO name="LEDRs" type="myLEDRs_559"/>
</LNodeType>
<LNodeType id="F2T202IN/MEAS/MMXU2" lnClass="MMXU">
<DO name="Mod" type="myMod_0"/>
<DO name="Beh" type="myBeh_1"/>
<DO name="Health" type="myHealth_2"/>
<DO name="NamPlt" type="myNamPlt_9"/>
<DO name="TotW" type="myTotW_288"/>
<DO name="TotVAr" type="myTotW_288"/>
<DO name="TotVA" type="myTotW_288"/>
<DO name="TotPF" type="myTotW_288"/>
<DO name="Hz" type="myTotW_288"/>
<DO name="PPV" type="myPPV_303"/>
<DO name="PhV" type="myPhV_316"/>
<DO name="A" type="myPhV_316"/>
</LNodeType>
<LNodeType id="F2T202IN/CTRL/Q0XCBR1" lnClass="XCBR">
<DO name="Mod" type="myMod_0"/>
<DO name="Beh" type="myBeh_1"/>
<DO name="Health" type="myHealth_2"/>
<DO name="NamPlt" type="myNamPlt_9"/>
<DO name="Loc" type="myLoc_4"/>
<DO name="OpCnt" type="myOpTmh_5"/>
<DO name="Pos" type="myPos_202"/>
<DO name="BlkOpn" type="mySPCSO1_27"/>
<DO name="BlkCls" type="mySPCSO1_27"/>
<DO name="CBOpCap" type="myCBOpCap_211"/>
</LNodeType>
<LNodeType id="F2T202IN/MEAS/MSQI1" lnClass="MSQI">
<DO name="Mod" type="myMod_0"/>
<DO name="Beh" type="myBeh_1"/>
<DO name="Health" type="myHealth_2"/>
<DO name="NamPlt" type="myNamPlt_9"/>
<DO name="SeqA" type="mySeqA_255"/>
<DO name="SeqV" type="mySeqA_255"/>
</LNodeType>
<LNodeType id="F2T202IN/PROT/PTRC1" lnClass="PTRC">
<DO name="Mod" type="myMod_187"/>
<DO name="Beh" type="myBeh_1"/>
<DO name="Health" type="myHealth_2"/>
<DO name="NamPlt" type="myNamPlt_9"/>
<DO name="Tr" type="myOp_52"/>
<DO name="Str" type="myStr_51"/>
</LNodeType>
<LNodeType id="F2T202IN/MEAS/MMXN1" lnClass="MMXN">
<DO name="Mod" type="myMod_0"/>
<DO name="Beh" type="myBeh_1"/>
<DO name="Health" type="myHealth_2"/>
<DO name="NamPlt" type="myNamPlt_9"/>
<DO name="Watt" type="myWatt_354"/>
<DO name="VolAmpr" type="myWatt_354"/>
<DO name="PwrFact" type="myWatt_354"/>
<DO name="Hz" type="myWatt_354"/>
</LNodeType>
<LNodeType id="F2T202IN/PROT/SupVGGIO1" lnClass="GGIO">
<DO name="Mod" type="myMod_0"/>
<DO name="Beh" type="myBeh_1"/>
<DO name="Health" type="myHealth_2"/>
<DO name="NamPlt" type="myNamPlt_9"/>
<DO name="SPCSO1" type="mySPCSO1_27"/>
<DO name="SPCSO2" type="mySPCSO1_27"/>
<DO name="SPCSO3" type="mySPCSO1_27"/>
<DO name="SPCSO4" type="mySPCSO1_27"/>
<DO name="SPCSO6" type="mySPCSO1_27"/>
</LNodeType>
<LNodeType id="F2T202IN/MEAS/MMTR1" lnClass="MMTR">
<DO name="Mod" type="myMod_0"/>
<DO name="Beh" type="myBeh_1"/>
<DO name="Health" type="myHealth_2"/>
<DO name="NamPlt" type="myNamPlt_9"/>
<DO name="SupWh" type="mySupWh_243"/>
<DO name="SupVArh" type="mySupWh_243"/>
<DO name="DmdWh" type="mySupWh_243"/>
<DO name="DmdVArh" type="mySupWh_243"/>
</LNodeType>
<LNodeType id="F2T202IN/PROT/ZerRPTOC1" lnClass="PTOC">
<DO name="Mod" type="myMod_0"/>
<DO name="Beh" type="myBeh_1"/>
<DO name="Health" type="myHealth_2"/>
<DO name="NamPlt" type="myNamPlt_9"/>
<DO name="Str" type="myStr_51"/>
<DO name="Op" type="myOp_52"/>
<DO name="Mode" type="myMode_53"/>
<DO name="TmACrv" type="myTmACrv_100"/>
<DO name="StrVal" type="myStrVal_55"/>
<DO name="OpDlTmms" type="myOpDlTmms_61"/>
<DO name="DirMod" type="myDirMod_62"/>
</LNodeType>
<LNodeType id="F2T202IN/PROT/ZerIPTOC1" lnClass="PTOC">
<DO name="Mod" type="myMod_0"/>
<DO name="Beh" type="myBeh_1"/>
<DO name="Health" type="myHealth_2"/>
<DO name="NamPlt" type="myNamPlt_9"/>
<DO name="Str" type="myStr_51"/>
<DO name="Op" type="myOp_52"/>
<DO name="Mode" type="myMode_53"/>
<DO name="BlkDir" type="myBlkDir_54"/>
<DO name="StrVal" type="myStrVal_55"/>
<DO name="OpDlTmms" type="myOpDlTmms_61"/>
<DO name="DirMod" type="myDirMod_62"/>
</LNodeType>
<LNodeType id="F2T202IN/LD0/CALH1" lnClass="CALH">
<DO name="Mod" type="myMod_0"/>
<DO name="Beh" type="myBeh_1"/>
<DO name="Health" type="myHealth_2"/>
<DO name="NamPlt" type="myNamPlt_9"/>
<DO name="GrAlm" type="myLoc_4"/>
<DO name="GrWrn" type="myLoc_4"/>
<DO name="ErrBoard1" type="myErrBoard1_12"/>
<DO name="ErrBoard2" type="myErrBoard1_12"/>
<DO name="ErrBoard3" type="myErrBoard1_12"/>
<DO name="ErrBoard4" type="myErrBoard1_12"/>
<DO name="ErrBoard5" type="myErrBoard1_12"/>
<DO name="ErrBoardMCPU" type="myErrBoard1_12"/>
</LNodeType>
<LNodeType id="F2T202IN/LD0/LLN0" lnClass="LLN0">
<DO name="Mod" type="myMod_0"/>
<DO name="Beh" type="myBeh_1"/>
<DO name="Health" type="myHealth_2"/>
<DO name="NamPlt" type="myNamPlt_3"/>
<DO name="Loc" type="myLoc_4"/>
<DO name="OpTmh" type="myOpTmh_5"/>
</LNodeType>
<LNodeType id="F2T202IN/CTRL/Q0CSWI1" lnClass="CSWI">
<DO name="Mod" type="myMod_0"/>
<DO name="Beh" type="myBeh_1"/>
<DO name="Health" type="myHealth_2"/>
<DO name="NamPlt" type="myNamPlt_9"/>
<DO name="Loc" type="myLoc_4"/>
<DO name="Pos" type="myPos_642"/>
</LNodeType>
<DOType cdc="BCR" id="myLoadPro1_212">
<DA bType="INT32" dchg="true" fc="ST" name="actVal"/>
<DA bType="Quality" fc="ST" name="q" qchg="true"/>
<DA bType="Timestamp" fc="ST" name="t"/>
<DA bType="Struct" fc="CF" name="units" type="myunits_57"/>
<DA bType="FLOAT32" fc="CF" name="pulsQty" valKind="RO"/>
<DA bType="VisString255" fc="DC" name="d" valKind="RO"/>
<DA bType="VisString255" fc="EX" name="dataNs" valKind="RO"/>
</DOType>
<DOType cdc="ING" id="myDirMod_62">
<DA bType="Enum" fc="SG" name="setVal" type="TextSetting_2" valKind="Set"/>
</DOType>
<DOType cdc="INS" id="myOpTmh_5">
<DA bType="INT32" dchg="true" fc="ST" name="stVal"/>
<DA bType="Quality" fc="ST" name="q" qchg="true"/>
<DA bType="Timestamp" fc="ST" name="t"/>
</DOType>
<DOType cdc="INC" id="myMod_0">
<DA bType="Enum" dchg="true" fc="ST" name="stVal" type="Beh"/>
<DA bType="Quality" fc="ST" name="q" qchg="true"/>
<DA bType="Timestamp" fc="ST" name="t"/>
<DA bType="Enum" fc="CF" name="ctlModel" type="ctlModel" valKind="RO"/>
</DOType>
<DOType cdc="CMV" id="myc1_256">
<DA bType="Struct" fc="MX" name="cVal" type="mycVal_257"/>
<DA bType="Struct" fc="CF" name="units" type="myunits_57"/>
<DA bType="Quality" fc="MX" name="q" qchg="true"/>
<DA bType="Timestamp" fc="MX" name="t"/>
<DA bType="INT32U" fc="CF" name="db" valKind="Set"/>
</DOType>
<DOType cdc="INS" id="myDevStr_21">
<DA bType="INT32" dchg="true" fc="ST" name="stVal"/>
<DA bType="Quality" fc="ST" name="q" qchg="true"/>
<DA bType="Timestamp" fc="ST" name="t"/>
<DA bType="VisString255" fc="DC" name="d" valKind="RO"/>
<DA bType="VisString255" fc="EX" name="dataNs" valKind="RO"/>
</DOType>
<DOType cdc="ING" id="myOpDlTmms_61">
<DA bType="INT32" fc="SG" name="setVal" valKind="Set"/>
<DA bType="INT32" fc="CF" name="minVal" valKind="RO"/>
<DA bType="INT32" fc="CF" name="maxVal" valKind="RO"/>
<DA bType="INT32U" fc="CF" name="stepSize" valKind="RO"/>
</DOType>
<DOType cdc="DPL" id="myPhyNam_18">
<DA bType="VisString255" fc="DC" name="vendor" valKind="RO"/>
<DA bType="VisString255" fc="DC" name="hwRev" valKind="RO"/>
<DA bType="VisString255" fc="DC" name="swRev" valKind="RO"/>
<DA bType="VisString255" fc="DC" name="serNum" valKind="RO"/>
<DA bType="VisString255" fc="DC" name="model" valKind="RO"/>
<DA bType="VisString255" fc="DC" name="location" valKind="RO"/>
</DOType>
<DOType cdc="LPL" id="myNamPlt_9">
<DA bType="VisString255" fc="DC" name="vendor" valKind="RO"/>
<DA bType="VisString255" fc="DC" name="swRev" valKind="RO"/>
<DA bType="VisString255" fc="DC" name="d" valKind="RO"/>
<DA bType="VisString255" fc="DC" name="configRev" valKind="RO"/>
</DOType>
<DOType cdc="LPL" id="myNamPlt_3">
<DA bType="VisString255" fc="DC" name="vendor" valKind="RO"/>
<DA bType="VisString255" fc="DC" name="swRev" valKind="RO"/>
<DA bType="VisString255" fc="DC" name="d" valKind="RO"/>
<DA bType="VisString255" fc="DC" name="configRev" valKind="RO"/>
<DA bType="VisString255" fc="EX" name="ldNs" valKind="RO"/>
</DOType>
<DOType cdc="WYE" id="myPhV_316">
<SDO name="phsA" type="myc1_256"/>
<SDO name="phsB" type="myc1_256"/>
<SDO name="phsC" type="myc1_256"/>
<SDO name="neut" type="myc1_256"/>
</DOType>
<DOType cdc="DPC" id="myPos_202">
<DA bType="Dbpos" dchg="true" fc="ST" name="stVal"/>
<DA bType="Quality" fc="ST" name="q" qchg="true"/>
<DA bType="Timestamp" fc="ST" name="t"/>
<DA bType="Enum" fc="CF" name="ctlModel" type="ctlModel" valKind="RO"/>
</DOType>
<DOType cdc="ASG" id="myBlkVPhPh_118">
<DA bType="Struct" fc="SG" name="setMag" type="mysetMag_56"/>
<DA bType="Struct" fc="CF" name="units" type="myunits_57"/>
<DA bType="Struct" fc="CF" name="minVal" type="mysetMag_56"/>
<DA bType="Struct" fc="CF" name="maxVal" type="mysetMag_56"/>
<DA bType="Struct" fc="CF" name="stepSize" type="mysetMag_56"/>
<DA bType="VisString255" fc="EX" name="dataNs" valKind="RO"/>
</DOType>
<DOType cdc="CURVE" id="myTmACrv_100">
<DA bType="Enum" fc="SG" name="setCharact" type="TextSetting_3" valKind="Set"/>
</DOType>
<DOType cdc="ACT" id="myOp_52">
<DA bType="BOOLEAN" dchg="true" fc="ST" name="general"/>
<DA bType="Quality" fc="ST" name="q" qchg="true"/>
<DA bType="Timestamp" fc="ST" name="t"/>
</DOType>
<DOType cdc="INS" id="mySwOpCap_666">
<DA bType="Enum" dchg="true" fc="ST" name="stVal" type="SwOpCap"/>
<DA bType="Quality" fc="ST" name="q" qchg="true"/>
<DA bType="Timestamp" fc="ST" name="t"/>
</DOType>
<DOType cdc="DPC" id="myPos_642">
<DA bType="Struct" fc="ST" name="origin" type="myorigin_36"/>
<DA bType="INT8U" fc="ST" name="ctlNum"/>
<DA bType="Dbpos" dchg="true" fc="ST" name="stVal"/>
<DA bType="Quality" fc="ST" name="q" qchg="true"/>
<DA bType="Timestamp" fc="ST" name="t"/>
<DA bType="BOOLEAN" dchg="true" fc="ST" name="stSeld"/>
<DA bType="Enum" fc="CF" name="ctlModel" type="ctlModel" valKind="RO"/>
<DA bType="INT32U" fc="CF" name="sboTimeout" valKind="RO"/>
<DA bType="Enum" fc="CF" name="sboClass" type="sboClass" valKind="RO"/>
<DA bType="Struct" fc="CO" name="SBOw" type="myOper_37"/>
<DA bType="Struct" fc="CO" name="Oper" type="myOper_37"/>
<DA bType="Struct" fc="CO" name="Cancel" type="myCancel_648"/>
</DOType>
<DOType cdc="MV" id="myWatt_354">
<DA bType="Struct" fc="MX" name="instMag" type="mysetMag_56"/>
<DA bType="Struct" fc="MX" name="mag" type="mysetMag_56"/>
<DA bType="Quality" fc="MX" name="q" qchg="true"/>
<DA bType="Timestamp" fc="MX" name="t"/>
<DA bType="Struct" fc="CF" name="units" type="myunits_57"/>
<DA bType="INT32U" fc="CF" name="db" valKind="Set"/>
</DOType>
<DOType cdc="INS" id="myCBOpCap_211">
<DA bType="Enum" dchg="true" fc="ST" name="stVal" type="CBOpCap"/>
<DA bType="Quality" fc="ST" name="q" qchg="true"/>
<DA bType="Timestamp" fc="ST" name="t"/>
</DOType>
<DOType cdc="ING" id="myMode_53">
<DA bType="Enum" fc="SG" name="setVal" type="TextSetting_1" valKind="Set"/>
<DA bType="VisString255" fc="EX" name="dataNs" valKind="RO"/>
</DOType>
<DOType cdc="BCR" id="mySumSwARs1_205">
<DA bType="INT32" dchg="true" fc="ST" name="actVal"/>
<DA bType="Quality" fc="ST" name="q" qchg="true"/>
<DA bType="Timestamp" fc="ST" name="t"/>
<DA bType="Struct" fc="CF" name="units" type="myunits_57"/>
<DA bType="FLOAT32" fc="CF" name="pulsQty" valKind="RO"/>
<DA bType="VisString255" fc="DC" name="d" valKind="RO"/>
</DOType>
<DOType cdc="DEL" id="myPPV_303">
<SDO name="phsAB" type="myc1_256"/>
<SDO name="phsBC" type="myc1_256"/>
<SDO name="phsCA" type="myc1_256"/>
</DOType>
<DOType cdc="BCR" id="mySupWh_243">
<DA bType="INT32" dchg="true" fc="ST" name="actVal"/>
<DA bType="Quality" fc="ST" name="q" qchg="true"/>
<DA bType="Timestamp" fc="ST" name="t"/>
<DA bType="Struct" fc="CF" name="units" type="myunits_57"/>
<DA bType="FLOAT32" fc="CF" name="pulsQty" valKind="RO"/>
</DOType>
<DOType cdc="INS" id="myHealth_2">
<DA bType="Enum" dchg="true" fc="ST" name="stVal" type="Health"/>
<DA bType="Quality" fc="ST" name="q" qchg="true"/>
<DA bType="Timestamp" fc="ST" name="t"/>
</DOType>
<DOType cdc="SPC" id="mySPCSO1_27">
<DA bType="BOOLEAN" dchg="true" fc="ST" name="stVal"/>
<DA bType="Quality" fc="ST" name="q" qchg="true"/>
<DA bType="Timestamp" fc="ST" name="t"/>
<DA bType="Enum" fc="CF" name="ctlModel" type="ctlModel" valKind="RO"/>
</DOType>
<DOType cdc="INS" id="mySwTyp_665">
<DA bType="Enum" dchg="true" fc="ST" name="stVal" type="SwTyp"/>
<DA bType="Quality" fc="ST" name="q" qchg="true"/>
<DA bType="Timestamp" fc="ST" name="t"/>
</DOType>
<DOType cdc="MV" id="myTotW_288">
<DA bType="Struct" fc="MX" name="mag" type="mysetMag_56"/>
<DA bType="Quality" fc="MX" name="q" qchg="true"/>
<DA bType="Timestamp" fc="MX" name="t"/>
<DA bType="Struct" fc="CF" name="units" type="myunits_57"/>
<DA bType="INT32U" fc="CF" name="db" valKind="Set"/>
</DOType>
<DOType cdc="SEQ" id="mySeqA_255">
<SDO name="c1" type="myc1_256"/>
<SDO name="c2" type="myc1_256"/>
<SDO name="c3" type="myc1_256"/>
<DA bType="Enum" fc="MX" name="seqT" type="seqT"/>
</DOType>
<DOType cdc="ACD" id="myStr_51">
<DA bType="BOOLEAN" dchg="true" fc="ST" name="general"/>
<DA bType="Enum" dchg="true" fc="ST" name="dirGeneral" type="dir"/>
<DA bType="Quality" fc="ST" name="q" qchg="true"/>
<DA bType="Timestamp" fc="ST" name="t"/>
</DOType>
<DOType cdc="SPC" id="myPhOCEna_35">
<DA bType="Struct" fc="ST" name="origin" type="myorigin_36"/>
<DA bType="INT8U" fc="ST" name="ctlNum"/>
<DA bType="BOOLEAN" dchg="true" fc="ST" name="stVal"/>
<DA bType="Quality" fc="ST" name="q" qchg="true"/>
<DA bType="Timestamp" fc="ST" name="t"/>
<DA bType="Enum" fc="CF" name="ctlModel" type="ctlModel" valKind="RO"/>
<DA bType="Struct" fc="CO" name="Oper" type="myOper_37"/>
<DA bType="VisString255" fc="EX" name="dataNs" valKind="RO"/>
</DOType>
<DOType cdc="SPC" id="myLEDRs_559">
<DA bType="Struct" fc="ST" name="origin" type="myorigin_36"/>
<DA bType="INT8U" fc="ST" name="ctlNum"/>
<DA bType="BOOLEAN" dchg="true" fc="ST" name="stVal"/>
<DA bType="Quality" fc="ST" name="q" qchg="true"/>
<DA bType="Timestamp" fc="ST" name="t"/>
<DA bType="Enum" fc="CF" name="ctlModel" type="ctlModel" valKind="RO"/>
<DA bType="Struct" fc="CO" name="Oper" type="myOper_37"/>
</DOType>
<DOType cdc="SPG" id="myBlkDir_54">
<DA bType="BOOLEAN" fc="SG" name="setVal" valKind="Set"/>
<DA bType="VisString255" fc="EX" name="dataNs" valKind="RO"/>
</DOType>
<DOType cdc="SPS" id="myErrBoard1_12">
<DA bType="BOOLEAN" dchg="true" fc="ST" name="stVal"/>
<DA bType="Quality" fc="ST" name="q" qchg="true"/>
<DA bType="Timestamp" fc="ST" name="t"/>
<DA bType="VisString255" fc="DC" name="d" valKind="RO"/>
<DA bType="VisString255" fc="EX" name="dataNs" valKind="RO"/>
</DOType>
<DOType cdc="INS" id="myBeh_1">
<DA bType="Enum" dchg="true" fc="ST" name="stVal" type="Beh"/>
<DA bType="Quality" fc="ST" name="q" qchg="true"/>
<DA bType="Timestamp" fc="ST" name="t"/>
</DOType>
<DOType cdc="INC" id="myMod_187">
<DA bType="Struct" fc="ST" name="origin" type="myorigin_36"/>
<DA bType="INT8U" fc="ST" name="ctlNum"/>
<DA bType="Enum" dchg="true" fc="ST" name="stVal" type="Beh"/>
<DA bType="Quality" fc="ST" name="q" qchg="true"/>
<DA bType="Timestamp" fc="ST" name="t"/>
<DA bType="Enum" fc="CF" name="ctlModel" type="ctlModel" valKind="RO"/>
<DA bType="Struct" fc="CO" name="Oper" type="myOper_189"/>
</DOType>
<DOType cdc="ASG" id="myStrVal_55">
<DA bType="Struct" fc="SG" name="setMag" type="mysetMag_56"/>
<DA bType="Struct" fc="CF" name="units" type="myunits_57"/>
<DA bType="Struct" fc="CF" name="minVal" type="mysetMag_56"/>
<DA bType="Struct" fc="CF" name="maxVal" type="mysetMag_56"/>
<DA bType="Struct" fc="CF" name="stepSize" type="mysetMag_56"/>
</DOType>
<DOType cdc="SPS" id="myLoc_4">
<DA bType="BOOLEAN" dchg="true" fc="ST" name="stVal"/>
<DA bType="Quality" fc="ST" name="q" qchg="true"/>
<DA bType="Timestamp" fc="ST" name="t"/>
</DOType>
<DAType id="myOper_37">
<BDA bType="BOOLEAN" name="ctlVal"/>
<BDA bType="Struct" name="origin" type="myorigin_36"/>
<BDA bType="INT8U" name="ctlNum"/>
<BDA bType="Timestamp" name="T"/>
<BDA bType="BOOLEAN" name="Test"/>
<BDA bType="Check" name="Check"/>
</DAType>
<DAType id="myOper_189">
<BDA bType="Enum" name="ctlVal" type="Beh"/>
<BDA bType="Struct" name="origin" type="myorigin_36"/>
<BDA bType="INT8U" name="ctlNum"/>
<BDA bType="Timestamp" name="T"/>
<BDA bType="BOOLEAN" name="Test"/>
<BDA bType="Check" name="Check"/>
</DAType>
<DAType id="myCancel_648">
<BDA bType="BOOLEAN" name="ctlVal"/>
<BDA bType="Struct" name="origin" type="myorigin_36"/>
<BDA bType="INT8U" name="ctlNum"/>
<BDA bType="Timestamp" name="T"/>
<BDA bType="BOOLEAN" name="Test"/>
</DAType>
<DAType id="myorigin_36">
<BDA bType="Enum" name="orCat" type="orCategory"/>
<BDA bType="Octet64" name="orIdent"/>
</DAType>
<DAType id="myunits_57">
<BDA bType="Enum" name="SIUnit" type="SIUnit" valKind="RO"/>
<BDA bType="Enum" name="multiplier" type="multiplier" valKind="RO"/>
</DAType>
<DAType id="mysetMag_56">
<BDA bType="FLOAT32" name="f"/>
</DAType>
<DAType id="mycVal_257">
<BDA bType="Struct" name="mag" type="mysetMag_56"/>
</DAType>
<EnumType id="sboClass">
<EnumVal ord="0">operate-once</EnumVal>
<EnumVal ord="1">operate-many</EnumVal>
</EnumType>
<EnumType id="seqT">
<EnumVal ord="0">pos-neg-zero</EnumVal>
<EnumVal ord="1">dir-quad-zero</EnumVal>
</EnumType>
<EnumType id="TextSetting_1">
<EnumVal ord="1">ON</EnumVal>
<EnumVal ord="5">OFF</EnumVal>
</EnumType>
<EnumType id="TextSetting_2">
<EnumVal ord="1">Non-Directional</EnumVal>
<EnumVal ord="2">Forward</EnumVal>
<EnumVal ord="3">Reverse</EnumVal>
</EnumType>
<EnumType id="multiplier">
<EnumVal ord="-24">y</EnumVal>
<EnumVal ord="-21">z</EnumVal>
<EnumVal ord="-18">a</EnumVal>
<EnumVal ord="-15">f</EnumVal>
<EnumVal ord="-12">p</EnumVal>
<EnumVal ord="-9">n</EnumVal>
<EnumVal ord="-6">µ</EnumVal>
<EnumVal ord="-3">m</EnumVal>
<EnumVal ord="-2">c</EnumVal>
<EnumVal ord="-1">d</EnumVal>
<EnumVal ord="0"/>
<EnumVal ord="1">da</EnumVal>
<EnumVal ord="2">h</EnumVal>
<EnumVal ord="3">k</EnumVal>
<EnumVal ord="6">M</EnumVal>
<EnumVal ord="9">G</EnumVal>
<EnumVal ord="12">T</EnumVal>
<EnumVal ord="15">P</EnumVal>
<EnumVal ord="18">E</EnumVal>
<EnumVal ord="21">Z</EnumVal>
<EnumVal ord="24">Y</EnumVal>
</EnumType>
<EnumType id="CBOpCap">
<EnumVal ord="1">None</EnumVal>
<EnumVal ord="2">Open</EnumVal>
<EnumVal ord="3">Close-Open</EnumVal>
<EnumVal ord="4">Open-Close-Open</EnumVal>
<EnumVal ord="5">Close-Open-Close-Open</EnumVal>
</EnumType>
<EnumType id="TextSetting_3">
<EnumVal ord="1">Extremely Inv.</EnumVal>
<EnumVal ord="2">Very Inverse</EnumVal>
<EnumVal ord="3">Normal Inverse</EnumVal>
<EnumVal ord="8">Long Inverse</EnumVal>
</EnumType>
<EnumType id="dir">
<EnumVal ord="0">unknown</EnumVal>
<EnumVal ord="1">forward</EnumVal>
<EnumVal ord="2">backward</EnumVal>
<EnumVal ord="3">both</EnumVal>
</EnumType>
<EnumType id="ctlModel">
<EnumVal ord="0">status-only</EnumVal>
<EnumVal ord="1">direct-with-normal-security</EnumVal>
<EnumVal ord="2">sbo-with-normal-security</EnumVal>
<EnumVal ord="3">direct-with-enhanced-security</EnumVal>
<EnumVal ord="4">sbo-with-enhanced-security</EnumVal>
</EnumType>
<EnumType id="Health">
<EnumVal ord="1">Ok</EnumVal>
<EnumVal ord="2">Warning</EnumVal>
<EnumVal ord="3">Alarm</EnumVal>
</EnumType>
<EnumType id="Beh">
<EnumVal ord="1">on</EnumVal>
<EnumVal ord="2">blocked</EnumVal>
<EnumVal ord="3">test</EnumVal>
<EnumVal ord="4">test/blocked</EnumVal>
<EnumVal ord="5">off</EnumVal>
</EnumType>
<EnumType id="SwTyp">
<EnumVal ord="1">Load Break</EnumVal>
<EnumVal ord="2">Disconnector</EnumVal>
<EnumVal ord="3">Earthing Switch</EnumVal>
<EnumVal ord="4">High Speed Earthing Switch</EnumVal>
</EnumType>
<EnumType id="SIUnit">
<EnumVal ord="1"/>
<EnumVal ord="2">m</EnumVal>
<EnumVal ord="3">kg</EnumVal>
<EnumVal ord="4">s</EnumVal>
<EnumVal ord="5">A</EnumVal>
<EnumVal ord="6">K</EnumVal>
<EnumVal ord="7">mol</EnumVal>
<EnumVal ord="8">cd</EnumVal>
<EnumVal ord="9">deg</EnumVal>
<EnumVal ord="10">rad</EnumVal>
<EnumVal ord="11">sr</EnumVal>
<EnumVal ord="21">Gy</EnumVal>
<EnumVal ord="23">°C</EnumVal>
<EnumVal ord="24">Sv</EnumVal>
<EnumVal ord="25">F</EnumVal>
<EnumVal ord="26">C</EnumVal>
<EnumVal ord="27">S</EnumVal>
<EnumVal ord="28">H</EnumVal>
<EnumVal ord="29">V</EnumVal>
<EnumVal ord="30">ohm</EnumVal>
<EnumVal ord="31">J</EnumVal>
<EnumVal ord="32">N</EnumVal>
<EnumVal ord="33">Hz</EnumVal>
<EnumVal ord="34">lx</EnumVal>
<EnumVal ord="35">Lm</EnumVal>
<EnumVal ord="36">Wb</EnumVal>
<EnumVal ord="37">T</EnumVal>
<EnumVal ord="38">W</EnumVal>
<EnumVal ord="39">Pa</EnumVal>
<EnumVal ord="41"></EnumVal>
<EnumVal ord="42"></EnumVal>
<EnumVal ord="43">m/s</EnumVal>
<EnumVal ord="44">m/s²</EnumVal>
<EnumVal ord="45">m³/s</EnumVal>
<EnumVal ord="46">m/m³</EnumVal>
<EnumVal ord="47">M</EnumVal>
<EnumVal ord="48">kg/m³</EnumVal>
<EnumVal ord="49">m²/s</EnumVal>
<EnumVal ord="50">W/m K</EnumVal>
<EnumVal ord="51">J/K</EnumVal>
<EnumVal ord="52">ppm</EnumVal>
<EnumVal ord="53">1/s</EnumVal>
<EnumVal ord="54">rad/s</EnumVal>
<EnumVal ord="61">VA</EnumVal>
<EnumVal ord="62">Watts</EnumVal>
<EnumVal ord="63">VAr</EnumVal>
<EnumVal ord="64">phi</EnumVal>
<EnumVal ord="65">cos(phi)</EnumVal>
<EnumVal ord="66">Vs</EnumVal>
<EnumVal ord="67"></EnumVal>
<EnumVal ord="68">As</EnumVal>
<EnumVal ord="69"></EnumVal>
<EnumVal ord="70">A²t</EnumVal>
<EnumVal ord="71">VAh</EnumVal>
<EnumVal ord="72">Wh</EnumVal>
<EnumVal ord="73">VArh</EnumVal>
<EnumVal ord="74">V/Hz</EnumVal>
</EnumType>
<EnumType id="orCategory">
<EnumVal ord="0">not-supported</EnumVal>
<EnumVal ord="1">bay-control</EnumVal>
<EnumVal ord="2">station-control</EnumVal>
<EnumVal ord="3">remote-control</EnumVal>
<EnumVal ord="4">automatic-bay</EnumVal>
<EnumVal ord="5">automatic-station</EnumVal>
<EnumVal ord="6">automatic-remote</EnumVal>
<EnumVal ord="7">maintenance</EnumVal>
<EnumVal ord="8">process</EnumVal>
</EnumType>
<EnumType id="SwOpCap">
<EnumVal ord="1">None</EnumVal>
<EnumVal ord="2">Open</EnumVal>
<EnumVal ord="3">Close</EnumVal>
<EnumVal ord="4">Open and Close</EnumVal>
</EnumType>
</DataTypeTemplates>
</SCL>